PNO-79-135:on 790602,emergency Feedwater Sys Found Locked Out of Automatic Initiation Mode While Plant in Hot Shutdown.Cause Not Known.No Procedure for Returning Sys to Normal.Shutdown Order Issued 790602 Until Procedures Set Up
ML19256C586
Person / Time
Site: Arkansas Nuclear 
Issue date: 06/04/1979
From: Bryan S, Klinger G, Nolan F
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
TASK-TF, TASK-TMR PNO-79-135, NUDOCS 7910100530
Download: ML19256C586 (2)


Text

.

PRELIMINARY NOTIFICATION.

June 4, 1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-79-135 This preliminary notification constitutes EARLY notice of an event of POSSIBLE s tfety or public interest significance.

The infermation presented is as initially ~ received without verification cr evaluation and is bas cally all that is known by IE staff on this date.

FACILITY: Arkansas Power and Light Company Arkansas Nuclear One - Unit 1 Russellville, Arkansas Docket No. 50-313

SUBJECT:

Emergency Feedwater System was Locked Out of Automatic Initiation Mode.

~

The resident inspector, during a routine inspection of the Unit 1 control room at about 9:00 am on June 2,1979, noted that the Emergency Feedwater System was locked out of the automatic initiation mode.

The plcnt was in a hot shutdown condition.

A main feedwater check valve back leakage surveillance test was in progress.

The surveillance test procedure did not specify locking out the emergency feedwater auto initiation capability.

Lacking a procedural requirement to return the system to normal, there was no assurance that emergency feedwater would be provided automatically if needed. An order was issued June 2, 1979, which required the licensee to return to a cold shutdown condition until the licensee satisfied the following conditions:

(1) the licensee shall evaluate and modify as appropriate its methods for development, review and approval of procedures for all modes of plant operation; (2) the licensee shall evaluate existing procedures to assure that such procedures include all actions necessary for safety; and, (3) the licensee shall take appropriate steps to assure that all plant personnel adhere to approved procedures and not adt unauthorized steps to any procedure."

The plant was verified to be in cold shutdown by the resident inspector on June 3, 1979.

A special NRC inspection (NRR and IE personnel) is in progress.

The licensee has made a press release.

An NRC press release is being prepared.

Region IV, Dallas, initially received notification of the occurrence by tele-phone from the Resident Inspector, at 10:30 a.m. on June 2.

CONTINUED PRELIMINARY NOTIFICATION 1447 159 7910100 N O

Continued PNO-79-135 Page 2 June 4, 1979

Contact:

F. Nolan, IE x28019; S. E. Bryan, IE x28019; G. Klingler, IE x28019 Distribution:

Transmitted H St k.3 6 Chairman Hendrie Cornmissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA Commissioner Gilinsky ACRS (For Distribution)

Transmitted:

MNBBk.hO P. Bldg

/b J.G.Davs,If L. V. Gossick, ED0 H. R. Denton, NRR Region '

U.46 H. L. Ornstein, EDO R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR N. M. Haller, MPA V. Stello, NRR (MAIL)

R. G. Ryan, OSP R. S. Boyd, NRR J. J. Cummings, 0IA H. K. Shapar, ELD SS Bldg 4'. 36 R. Minogue, SD W. J. Dircks, NMSS S. Levine, RES PRELIMINARY NOTIFICAT11N 1447 160 m

.