.M C0HSUH18IS V)a P0wer j

C0H1pBHy SJ'f,*",";,""j',,,,

u oeneral Of fices: 1945 West Pernall Road, Jackson, Michigan 49201 + (517) 788 0453 October 31, 1979 Howe-283-79 Mr J G Keppler, Regional Director Office of Inspection and Enforcement US Nuclear Regulatory Co= mission Ecgion III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND MUCLEAR PIANT UNIT NO 1, DOCET NO 50-329 UNIT NO 2. DOCKET No 50-330 SAFE SHUIDOWN BORATION CAPABILITY In accordance with the requirements of 10 CFR 50 55(e), this letter constitutes an interim report concerning a potentially unsafe situation originally reported by a telephone call frcm B W Marguglio, CPCo QA-PEC, to R Cook, NRC Resident Inspector, on October 2, 1979 On October 1, 1979, Consumers Power Company received written notification from Babcock & Wilcox that the present Midland design does not permit achieving and ma htaining a 11 6 k/k chutdown margin with safety grade equipment assuming a most restrictive core condition and the control rod of highest worth stuck out of the core. This report resulted after en extensive review of the Midland shutdown boration capability. At present, several design changes, including hardware modifications and changes.to boron concentration, are under consideration as remedies for this situation.

Another report, either interim or final, will be sent on or before January 29, 1980.

NN cRE/lr CC: Director of Office of Innpection and Enforcement Att: Mr Victor Stello, U3NRC (15)

Director of Office of Management Infonnation and Program Control, USNRC (1) 1 ') O }

jg}

0 on' j

o

.