ML19254D894

From kanterella
Jump to navigation Jump to search
Forwards LER 79-024/03T-1
Date released: 09/25/2019 Download: ML19254D894


LER 79-024/03T-1:on 790214,safety Relief Valves 2B21-F013 C & G Failed to Open at 1,090 Psi Setpoints.Caused by Excessive Leakage in Valve Pilot Assembly Due to Scuffing of Pilot Disc & Seat.Mods Performed on Valve
ML19254D900
Person / Time
Site: Hatch Southern Nuclear icon.png
Issue date: 10/17/1979
From: Coggin C
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19254D900 (3)
Forwards LER 79-024/03T-1
ML19254D893
Person / Time
Site: Hatch Southern Nuclear icon.png
Issue date: 10/17/1979
From: Manry M
GEORGIA POWER CO.
To: ORELLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References