97,-r 7C

' s SNUPPS Standardized Nuclear Unit Povver Plant System 5 Choke Cherry Road Nicholas A. Petrick Rockvii.e, Maryland 20850 Executive Director (301)869 8010 October 26, 1979 SLNRC 79-17 FILE:

0278.10 SUBJ:

IE Bulletin 79-23:

Potential

_ Failure of Emergency Diesel Generator Field Exciter Transformer Mr. Boyce Grier Director, Region I Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 Docket Nos:

STN 50-482, STN 50-483, STN 50-485, STN 50-486

Dear Mr. Grier:

~

This letter is submitted in response to the subject IE Bulletin for the SNUPPS Utilities, Kansas Gas and Electric Company, Union Electric Company, and Rochester Gas and Electric Corporation.

The problem described in the subject Bulletin is not applicable to the SNUPPS diesel generators.

The design of the exciter power transformer consists of a delta-connected primary.

It does not have a neutral connection.

Therefore, the problem of circulating currents through the exciter power transformer primary ground connection does not exist on the SNUPPS units.

Testing of the diesel generators is described in the SNUPPS FSAR Sections 8.3.1.1.3 and 14.2.12.1.62.

The testing meets the requirements of the IE Bulletin. The testing will be completed prior to fuel load.

Very truly yours,

[

cW\\ c -

~

Nicholas A. Petrick RLS:heg cc:

Mr. Victor SteMo, Jr., Director, Office of Inspection and Enforcement, USNRC, Washington, D.C.

Mr. James G. Keppler, Director, Region III, USNRC.

p Mr. Karl V. Seyfrit, Director, Region IV, USNRC.

1506 301 b

7912060 556 v