NRC.PUBLIC DOCOIENT ROOM

  • ~

4 UNITED STATES OF AMERICA k

37 4 NUCLEAR REGULAICRY CCMMISSION

\\

  • J

& 9?45 BEFORE TEE AICMIC SAFETY LND LICENSING BOARD Ok a-

torney Portland General Electric Company Dated: Jane 20, 1979 340 00B Akk66.2738

m mm m/C Pcn!cr.d Ger.em! Eectnc Ccnnny

!r Nwud smaa:

--- IC-Ji June 20, 1979 Marshall E. Miller, Esq., Chairman Atomic Safety and Licensing Board U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Dr. Kenneth A. McCollom, Dean Division of Engineering, Architecture & Technology Oklahoma State University Stillwater, Oklahoma 74074 Dr. Hugh C. Paxton 1229-41st S treet Los Alamos, New Mexico 67544 Gentlemen:

Attached to this letter is a list of Requests for Design Changes (RDCs) associated with the modification program d,cribed in the Report on Design Modifications for the Trojan Control Building (PGE-1020). This item is a modification to a piping support necessary to qualify the piping system for response soectra developed in accordance with PCE-1020, Appendix 3.

The 1. tem on this list sill not individually or collectively with previous modifications reduce the shear capacity of any major shear wall by greater than 1 percent. Nor does the item involve weight addi-tions which may result in an increase of greater than 1 percent of the calculated lateral forces ia any major shear wall.

The Licensee will continue to keep the Board informed of activities at Trojan as described at the March 20, 1979 Prehearing Conference (Tr. 3204-05).

Sincerely, Ronald W. Johnsen Corpcrate Attorney Portland General Electric Cem.ny RWJ/LWE/4kk66.27310 Attachment c:

R. H. Engelken Nuclear Regulatory Ccamission Region V A. Schwencer Nuclear Regulatory Commission 009

ATTACIDCTr Following is the list of Request for Design Change (RDC) work items for which field work =ay be performed within the next few weeks.

The relationship of the work with the Control, Auxiliary, and Fuel Building structures is briefly su=marized below:

RDC No.

Modification Relationship 79-028 Job Nc. 54: Addition of a A seismic rectraint will be added seismic restraint to reac-for the 4 in. pipe at elevation tor coolant pump seal water 67 ft. in the Fuel building. The pioing, CS-151R-1-6 (SR303) restraint will be supported by steel attached to floor support steel and anchored to the slab above nica drilled anchors.

340 010