ML19224D781

From kanterella
Jump to navigation Jump to search
Confirms 790607 Telcon Re RO 50-313/79-06:tests Revealed That Under Certain Repeat Start Operating Modes,Turbocharger Thrust Bearing on Emergency Diesel Generator Could Be Damaged.Unit in Cold Shutdown
ML19224D781
Person / Time
Site: Arkansas Nuclear 
Issue date: 06/08/1979
From: Ohanlon J
ARKANSAS POWER & LIGHT CO.
To: Madsen G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
ANO:1797, NUDOCS 7907170032
Download: ML19224D781 (2)


Text

.

ARKANSAS POWER & LIGHT COMPANY June 8, 1979 AN0: 1797 Mr.

G.L. Madsen, Acting Diractor Office of Inspection & Enforcement Region IV U.S.

Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 Subject; Arkansas Nuclear One - Unit One Reportable Event 50-313/79-06

Dear Sir:

This letter is to confirm the telephone conversation between Mr.

W.D.

Johnson (NRC, Region IV) and Mr. J.P. O'Hanlon (Arkansas Nuclear One, General Manager) at 1130 on June 7, 1979.

This is reported to you in accordance with T.S.

6.12.3.1(i).

Arkansas Power & Light Co. has been informed that Electro-Motive, General Motors Corporation, as a result of extensive testing, has found that under certain repeat start operating modes, there is a possibility that the turbocharger thrust bearing could be damaged on the ANO-1 emergency diesel generator.

This damage might ultimately cause a turbocharger failure.

The potential problem occurs if the engine receivee a repeat rapid start within a minimum of 15 minutes and a maximum of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> after a " hot shutdown" from a previous run.

When a fast start occurs during this time period, sufficient " prime" oil will have drained to retard the buildup of engine oil pressure in event that a restart is required.

At least 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> of cooling must take place before the circulating system can replace the drained oil.

ANO-1 is presently in a cold shutdown condition.

The vendor has recommended interim operating precautions until hardware modifications are made to correct the above described situation.

Applicable plant procedures will be modified to incorporate the interim precautions prior to plant startup.

?, V f iG: ll d]d)Y Y

>J s

7907170dAL

/

MEM8EA viCC E SCUTW UT'UT?ES SYSTEM

At:0: 1797 Mr.

G.L. Madsen Reportable Event 50-313/79-06 Page Two Further details will be included in the follow up report.

Sincerely, W

v.P.

O'Hanlon General Manager JPO:cle cc:

J.M.

Griffin D.C.

Trimble JPO T-6/14/79 ci

,,n c,

)JO

.00