Puauc 3EmnCE IND(ANA June 29, 1979 D
Director, Office of Inspection & Enforcement U.S. Nuclear Regulatory Comission 799 Roosevelt Road Construction Pemit Nos.: CPPR-170 Glen Ellyn, Illinois 60137 CPPR-171 Marble Hill Nuclear Generating Station
[
Units 1 & 2 i
Gentlemen:
f On June 1,1979 Mr. F. R. Hodges of Public Service Company of Indiana, Inc.
l (PSI) telephoned your offico of a potentially reportable incident involving i
possible damage to the Marble Hill Unit 1 containment liner. The specified
~
pour rate of 3 to 3 1/2 feet per hour was exceeded during the placement of l
concrete in Pour #1CW-Ext-2. The excessive pour rate of 10 feet in 70 minutes resulted in the branHng of a whaler on the lover portion of the formwork and possible bowing of the conem h t liner.
2
[
Visual inspection indicated that there may be some deformatien in the liner at the bottom of the subject pour.
i On June 28, 1979 Chicago Bridge & Iron perfomed dimensional measurements i
on the subJact liner. PSI is currently analyzing this data to determine if tha defome. tion of the liner shall is within specification tolerances.
1
}
PSI has not yet detamined if this incident is reportable as a significant deficiency under ICC7R50.55(e). This letter is intended to fulfill the requirements of an interim report as defined in 10CFR50.55(e)(3). A com-I plate report will be filed when the evaluation has been ecmpleted.
i Sincerely l
r i
l D/h%\\)
'? ' m i
I l
James Coug PAB:jb Vice President-Nuclear cc: Director of Inspection & Enforcement /