ML19224B284

From kanterella
Jump to navigation Jump to search
Final Rept, Sys Description:Heating,Ventilating & Air Conditioning Sys Control Room,Control Bldg, Ref Burns & Roe Drawing 2044,Revision 13
ML19224B284
Person / Time
Site: Crane Constellation icon.png
Issue date: 12/31/1975
From:
Metropolitan Edison Co
To: Mullinix W
NRC/IE
References
TM-0298, TM-298, ZAR-751231, NUDOCS 7906140377
Download: ML19224B284 (47)


Text

.

t-

'*t TMI DOCUMENTS

_7//7 -[,-2 /

~

DOCUMENT NO:

t COPY MADE ON f/

OF DOCUMENT PROVIDED BY 4

(

/

METROto?,lTAN EDISON COMPANY.

!! W Wilda R. Mullinix, NRC b

7906140377 e

~

196 315-e

  • f e

N

~

~

\\,...

-.7 i

SYS"JRIPTICN (Inc 38B)

HEATING ;IATING AND A IR CONDITIONING SYSTEM - )L R OCM, CCNTROL BUILDING B&R Dwg. '44, Rev. 13)

JERSEY CENTRAR & LIG HT C CMPANY

'IHREE MILE INUCLEAR STATICN O.

2 s

/

/

Iate:

Lx.,

1975 Pr by:

J.Khreys

-~'.

Burns b, Inc.

3 700 Kindek Road Ora d e. J.

0 ~,

195 316

3 2

s TA BLE OF CCNTENTS FCR HEA TING, VENTIIATING AND

~

A IR CONDITIONING SYSTEM - C ONTR OL R OCl4, CCNTROL BUILDING Section Pace

1.0 INTRODUCTION

1 1.1 System Functions 1

1.2 Summary Description of System 1

1.3 System Design Requirements 3

2.0 DETAILED DESCRIPTION CF SYSTEM 5

2.1 Components 5

2.2 Instruments, Controls, A la rms and Protective Devices 15 3.0 PRINCIPAL MCDES OF OPERATION 18 3.1 Startup 18 3.2 Normal Operation 20 3.3 Special or Infrequent Operation 21 3.4 Shutdown 22 3.5 Emergency 23 4.0 HAZA RDS AND PRECA UTIONS 24 3

.a 9

)9h b\\l

l s

A PPENDIX TITLE TA BLE NO.

Control Room Fan Coil Units 1

Control Room Supply Filter 2

Control Room Bypass Supply Fans 3

Control Room Bypass Roll, Aire Filter 4

Control Room Bypass Absolute Filter 5

Control Room Bypass Carbon Filter 6

Control Room Exhaust Fan 7

Kitchen Exhaust Fan 8

Toilet Exhaust Fan 9

Control Building Liquid Chiller Unit 10 control Building Liquid Cooler Pumps 11 Chilled Wa ter Expansion Tank 12 Chilled Water Chemical Feed Tank 13 Instrumentation and Controls 14 Panel Mounted Annuncia tors and Computer Inputs 15 e

I:

E

-7 0

146 31a m

a

/

e IETING, VENTILATING AND AIR CCNDITIONING SYSTEM - CONTROL ROCM, CCNTROL BUILDING 1.0 INTRCDUCTION 1.1 System Funct.icns

~

The functions of the Control Room Heating, Ventilating and Air Conditioning System are:

a.

To provide frech, filtered, tempered ventilating air to all spaces within the Control Room, office, toilet,

. kitchen, locker room and associated corridors during normal plant'~operatiiin End to maintain rocm temperatures suitable for the operating personnel and the mechanical and electrical equipment.

To supply chilled water in a closed loop to both the Control Room and Cable Room cool-ing coils.

1.1

b. To provide 100% recirculation en detection of an incipient explosion, fire or chlorine gas in the Air Intake Tunnel.

To recirculate filtered air with minimum ou'. side air (1000 CFM) during LOCA and detection of high radiation in the supply duct to provide a positive pressure in the Control Room which prevents in leakage of contaminated air.

1.2 Summarv Description of Svstem (Refer to B&R Dwc. 2044, Rev. 13)

The system is a push-pull heating, ventilating and air condi-ticning system with recirculation.

It consi.;te or the follow-ing subsystems:

a.

Supply system b.

Main exhaust system c.

Kitchen exhaust system d.

Toilet exhaust system e.

Recirculation system

-j f.

Chilled water system 196 319 e.-

t e

t The supply system consists of two 100% capacity centri-fugal fans with filters, electric heating coils, cooling coils, and necessary sheet metal ducts arranged to take outside air from the Air Intake Tunnel and deliver it to the various spaces in and associated with the Control Room.

The Control Room air supply duct is provided with a sound attenuator.

The main exhaust system consists of one 100% capacity centiidagal fan with a bypass and necessary sheet metal ducts arranged to exhaust air from all ventilated spaces 4xcept the kitchen and toilet )directly to atmosphere vL a an opening in the building wall.

The exhaust fa n a-ir inlet duct is provided with a sound attenuator.

The kitchen and toilet exhaust systers each consist of a 100% capacity fan with sheet natal ductwork to carry ex-haust air directly to atmosphere through an aperture in the building wall.

The kitchen exhaust air passes through a grease filter before entering the fan.

The recirculation system consists of ducts from the Control Room exhaust fan discharge to the inlet of the supply air fans, and a parallel high efficiency filtration path through which Control Room air is recirculated when the Control Room bypass supply fans are energized.

This high efficiency filtraticn path contains two 100% capacity centrifugal fans together with a filter train that includes a prefilter, a high efficiency particulate air (HEPA)

}

filter, a charcoal filter and a second high efficiency particulate air filter in series.

},

.,_J

1 9

The chilled wa ter system is a closed loop that consists of a two 100% capacity centrifugal pumps, which are used to pump water through 100% capacity chiller to any of the air cooling coils in the Control Room ducts.

An expansion tank at the suction of the chilled water pumps and a chemical feed tank are provided along with piping connecting the tanks with the closed loop.

A line from the Demineralized Service Water System provides makeup water to the chilled water loop.

The Nuclear Services River Water System consists of two 100%

capacity Control Building river water booster pumps, which can take suction from either of the redundant Nuclear Services River Water System Headers and supply cooling water to the condenser of either liquid chiller and from there, discharge to the Mechanical Draft Cooling Tower.

The system also includes river water piping that supplies Nuclear Services River Water directly to the air cooling coils of the Mechanical Equipment Room and discharges from there to the Mechanical Draft Cooling Tower.

1.3 Svstem Desicn Recuirements The ventilating system is designed to provide fresh air to the Control Rocm during normal operation.

When outside air temperature is below 70 F, fresh air will he ucmitted-in sufficient quantity to maintain a Control Room temperature o

o of 75 F.

If the outside air temperature is above 70 F, or when the Control Room bypass fans are energized, 1000 CFM of fresh air will be supplied through the minimum outside air duct for replenishment purposes.

On a sig:al from the chlorine gas monitoring System or the Fire Protection System, the air i

supply damper AH-D4092C shuts and no fresh air is supplied to the

{

control Room.

196 321

The system is designed to provide 100% outside air at the option of the operator during normal operation.

The supply fans deliver LATER CFM of fresh air which is sufficient for more than LATER air changes per hour.

Two chiller units are each designed to supply all the required cooling of the Control Room and Cable Room to maintain a 75 F temperature when the ventilation system is in the minimum outside air recirculation mode with an outside air o

air temperature of 92 F.

The units are rated at 110 tons of air condi+-ioning.

Chilled water is circulated through cooling coils in the Control Room (35 tons) and the Cable, Battery and Switchgear Rooms (75 tons).

The heaters are designed to heat the replenishment and recirculation air mixture. to maintain a 75 F temperature in the Cont.rol Room.

The heater coils are rated at 51 IG each and are interlocked with supply fans so that the heaters can-not be energized unless its corresponding fan is operating.

The heaters are designed to maintain the 75 F temperature during the minimum outside air recirculation mode with an outside temperature of 4 F.

The system is designed to minimize the possibility of introducing radioactive contamination, smoke or vapors into the Control Room.

A LOCA or detection of high i.ation in the Control Room supply duct will provide signals which will start one of the Centrol Room bypass supply fans which automatically places minimum outside air recirculation mode.

the system in a

All the air passes through th? Control Room bypass filter unib before it enters the Control Room spaces.

The 1000 CFM of 196 322

~4-

l outside air will cause a slight overpressure in the Contro' Room spaces which will preclude any in leakage from surrounc ing areas.

In the mode, Control Room personnel on eight hour sh.tfts during a 90 day period following a LOCA would not receive an integrated whole body dose in excess of 3 rem from all sources of direct radiation, including exposure during egress and ingress for shift changes.

If an incipient explosion, fire or chlorine gas in detected in the Air Intake Tunnel Auxiliary relays will automatically shut the Control Room air supply shutoff damper,

AH-D4092C, and place the Centrol Room Ventilating System in the 100% recirculation mode.

The detection of combustable vapors in the Air Intake Tunnel i; alarmed on Panels No.

7.

The operator then can place the Control Room Ventilating System in the minimum outside air recirculation mode by starting the Control Room bypass supply fans from Panel No. 25.

In either recirculation mode the chiller units will supply the necessary cooling.

2.0 DETAILED DESCRIPTION OF SYF"EM 2.1 Comconents The following major components are employed in tne Control Room heating, ventilating and air condition. system:

2.1.1 Maior System Dameers Air Sucolv Shutoff Dameer - AH-D4092C A pneumatic cylinder operated, quick closing, opposed' blade damper is located in the supply duct upstream of the minimum outside air duct.

The damper shuts automatically on detection of fire or smoke in the Control Room or detection of fire, incipient explosion or chlorine gas in the Air Intake Tunnel.

c An accumulator is located in the air supply line to ensure i

the damper remains open during a LTA.

A limit switch on the damper is interlocked with solenoid valves AH-V125A & B which ~.

position the recirculatio? dampers, AH-D4092D, AH-D4092E and forrecirculationwhenAH-D4092Cisclpggy.} ~ AH-ED4098

r Air is supplied frcm the Instrument Air System the 3-way solenoid, AH-EP-5290, receives power from 120V AC (Green) circuit Panel No. 25. Normal Air Supply Shutoff Damper, AH-D4092A, and Bypass Air Sucolv Shutoff Damper, AH-D4092B One pneumatic cylinder operated, quick closing, opposed blade damper is located in the normal supply duct to the control Room fan coil units and one pneumatic cylinder operated, quick opening, opposed blade damper is located in the supply duct to the Control Room bypass supply fans. The dampers are interlocked with the Cont-rol Room bypass supply fans to simultaneously divert supply air through the Control Room bypass supply fans and filter unit when the either Control Room bypass supply fan is energired. Air is supplied by the instrument air system, 3-way solenoid valves AH-V124A and AE-124B receive power from l'20v AC Cabinet 173 and 174 respectively. Damper position is indicated on Panel No. 13. Recirculation Contrql Damcers - AH-D4092D & E and AH -ED4098 Three pneumatic cylinder actuated opposed blade damper-with positioners are used to control air recirculation. AH-D4092D (quick-closing) in the supply duct and AH-D40922 (quick opening) in the unfiltered recirculation duct are ope rated to control re-circulation flow. AH-ED4098 (quick-closing), located in Control Room air exhaust duct, is used to control the exhaust air flow rate. AH-D4092D & E and AH-ED4098 are operated as a unit by the same control signal. These dampers are modulated'by thermostat AH-TS-5209 and positioned for.100% outside air by push button AH-KHS-5209 on Pat el 25. The dampers are positioned for re-3.- k

1 circulation by AH-TIC-5209 at outside air temperature over _~ 0 70 F, ES Signal, local pushbuttons, interlocks with the control Room bypass supply fans and supply damper AH-D4092C limit switch and a signal from the Fire Protection System. Air is supplied by the Instrument Air System, power for 3-way solenoid valves AH-V125A & 125B is supplied from 120v AC Cabinet 173 and 174 respectively. Damper position is indicated'on Panel No. 13. Supolv Fan Discharce Damoers - AH-D4096A & B - and Bvpass Sucolv Fan Discharce Damcers - AH-D4091A & B Cne pneumatic cylinder operated, parallel blade damper, located at the discharge of each supply and bypass supply fan, opens automatically when the associated fan starts and closes auto-matically when the fan stops. Air is supplied by the Instrument Air System, the 4-way solenoid valves receives power their associated fan control circuit. Accumulatort are provided with each damper to ensure the damper can b e properly po sitioned during accident conditions. Fitchen and Toilet Exhaust Fan Discharce Dammers AH-D4093 and AH-D4094 Cne electric motor operated, parallel blade shutoff damper in the discharge duct of each fan opens automatically when the associated fan starts and closes automatically when the fan stops.

,ath dampers receive power from 120v power panel MP2-42C.

Control Room Exhaust Fan Bvoass Dameer - AH-D4092G Cne pneumatic cylinder operated, parallel blade damper closes automatically when the exhaust fan is operating and opens automatically when the exhaust fan shuts down. Air is supplied -l by the Instrument Air System, the 4-way solenoid,. AH-EP-5207 receives from the exhaust fan control circuit. 196 325

i Centrol Room Bvrass Sucolv ran Inlet Dameers, AH-Vr4091A & B Cne pneumatic operated, variable pitch, vortex damper is located at the inlet to each of the Control Room bypass supply fans. The damper blade pitch is controlled by differential pressure controller, AH-DP IC -5 211, to maintain a constant pressure drop, i.e.

flow, across the Control Room bypass filter unit.

Air is supplied by the Instrument Air system. Miscellaneous Dameers In addition to the dampers described above, hand operated opposed blade dampers are provided at the inlet and outlet of the Control Room exhaust fan and the inlets of the Control Room bypass supply fans for isolation of the fans. Hand operated opposed blade dampers are provided in the supply duct, the un-filtered recirculation duct, the minimum outside air supply .c t, the Control Room supply fan inlets, and the Control Room exhaust duct. 2.1. 2 Maior Svstam Valves The following valves are utilized in the operation of the chilled water and Nuclear Services River Water Systems used to cool Control Room air: coolina Coil Water Flow Reaulatinc Valves - AH-V337. & B Cne 3" 150 psi ANSI, 100 F CS, bypass control valve with a pneumatic operator and a positioner is located at the dis-charge of each cooling coil to regulate : hilled water flow to the cooling coils duri the air conditioning mode of operation. These valves are controlled by thermostat AH-TS-5209. Air is supplied from the Instrument Air System. 196 326 -e w

  • e e

i t-i Coolina Coil Water Suculv Shutoff Valves - AH-V3 2A & B

Cne, 3",

150 psi ANSI, 100 F CS, butterfly valve with a pneumatic operator is located in the chilled water supply line to each cooling coil and opens. automatically when the associated fan starts and closes automatically when the fan stops. Air is supplied from the Instruinent Air System, the 4-way solenoid valves receives power from the associated fan control circuit. The valves are providec with accumulators to ensure proper positioning during accident conditions. Licuid Chillar River Water Flow Reculatine_jalves - NR-V145A & B one 4", 150 psi ANSI, 160 F CS, butterfly valve with a pneumatic operator and positionet is located et the dis-charge of each liquid chiller condenser to regulate condenser pressure by throttling river water. These values are controlled by refrigeration temperature controllers AH-TIC-5204 & 5250. Air is supplied from the Instrument Air System, the valves fail open on loss of air. Licuid Chiller River Water Shutoff Valves -NR-V144A &B Cne 4", 150 psi ANSI, 85 F CS, butterfly valve located in the Nuclear Services River Water supply line to each liquid chiller condenser opens automatically when chilled water flow is detected passing through the associated water cooler and closes automatically when flow stops. Air is supplied frca the Instrument Air S;'stcm and the valves are fitted with accumulators to ensure proper operation during accident conditions. The 4-way solenoid valves receive power from their associated chiller control circuit. -j ~ l96 327 _e_

Miscellaneous Valves In addition to the above valves, manually operated valves are provided for vents, drains and instrument connections, and for isolation of cooling coils, liquid cooler pumps, water coolers and condensers in the liquid chiller units, and chemical feed and expansion tanks in the chilled water loops. Makeup valve DW-vl5) is provided to admit makeup water automatically to the chilled water loops. 2.1.3 Control Room Fan-Coil Units AH-C-16A & B Two Control Room fan-coil units (see Table 1) are located in the Mech' nical Equipment Room in the Control Bui.' ding, a Elev. 351.5'. Each fan coil unit is designed for 100% capacity (15,620 CFM) and provides a fully redundant ventilating air supply to the Control Roor.. The corresponding fan outlet damper and chilled water inlet valve to the cooling coil are interlocked with the fan to open when their respective fan is energized and closed when the fan is de-energized. If the operating fan trips for any reason, the second fan coil unit will start automatically and the trip condicion will be annunciated on Panel No. 25. The fans can be controlled locally by pushbuttons, with indicating lights, or remotely by selector switches ( P ULL-T O-L OCK-S T CP -A UT O--S TART ), AH-HS-5 216 & 5 217 on Panel No. 25 also with indicating lights. The fans AH-C-16A and 16B, are driven by 15 HP motors which are powered from 480V Buses 2-12E & 2-22E respectively. The cooling coils are designed to cool air from 75.4 F Dry Bulb /63.2 F Wet Bulb to 57.1 F Dry Bulb /55.3 F Wet Bulb (440,000 BTU /hr) with 45 F chilled water. Both three step 51 KW electric heaters h-' (17KW/ step) are powered frcm MCC 2-42C. The electric heaters and the bypass control for the cooling coils valves are controlled 196 328

A by temperature controller AH-TS-5209. 2.1.4 Control Room Supolv Air Filters - AH-F-2A & B Cne Control Room supply air filtar (see Table 2) is located in the inlet duct of each Contrcl Room fan coil unit. Both filters are 2 in. thick, glass fiber media, Roll-Aire filters, automatically progressed to maintain uniform pres-sure drip, followed by replaceable cartridge type filte s. A 1/16 HP motor receives power from Panel MP-2-42C. Local controls and indicating lights are provided. 2.1.5 Control Room Bvoass Sucolv Fans AH-E-4A & 4B Two Control Room bypass supply fans (see Table 3), are located in the Mechanical Equipment Rocm Elev. 351.5'. Each consists of a cabir.et nousing a 100% capacity (15,620 CFM) centrifugal fan. The fans are automatically circulate air thru the control Room bypass filters furing LOCA, hign radiation in the Control Room supply du:t and chlorine gas in the Air Intake Tunnel. The fan s can be controlled locally by pushbuttons or remotely by selector switches (P ULL-TO-LOCK-STOP-AUTO-START), AH-HS-5 265 and 5266 on Panel No. 25. Each fan moter, AH-E-4A & B,is rated at 40 HP each and powered from 480V BUS 2-12E & 2-72E respectively. Pilot lights are provided both locally and on Panel no. 25 in the Control Room to indicabe fan operation. 2.1.6 Control Room Bvoass Filter Unit The Control nocm bypass filter unit (see 2.1.6.1 through 2.1.6.3) is a 100% capacity (15,620 CFM) filter train located in the Mechanical Equipment Room, Elev. 351. 5 '. The filter train consists of the following compoatnt filters. y 196 329

i 2.1.6.1 Roll-Aire Filter, AH-F-3 The Rolle-Aire filter (see Table 4) is located at the upstream end of the filter train. The filter is constructed of 2" thick fEber glass, reinforced by steel wires, and is automatically progressed to maintain a uniform pressure drop across the filter. The Roll-Aire filters have a 2/16 HP motor with local controls and indicating lights. The mucor receives power from 120V power panel MP 2-35. .l.6.2 HEPA Filters, AH-F-4 and 29 The high efficiency particulate air filters (see Table 5) are the second and fourth filters in the filter train. The HEPA filters are constructed of a dry, fibrous, high inter-ception, sub-micron glass fiber which has an efficiency of 99.97% for particles larger than 0.3 microns. The pressure drop across a clean filter at rated capacity is 1.2 inches H 0. 2 2.1.6.3 Activated carbon Filter, AH-F-5 The activated carbon filter (see Tabel o) is located between the HEPA filters in the filter traln. The carbon filter is constructed of impregnated activated charcoal and is water repellant and fire resistant. The carbon filter is designed to trap and remove gaseous contaminants from the air stream. A delu9e system is provided for spraying the cells at a minimum flow rate of 1.5 gpm per nozzle on the ~ air entering side of the bank for fire protection. 2.1.7 Control Room Exhaust Fan AH-E-35 Cne control Room exhaust fan (see Table 7), is located in the ? -t Mechanical Equipment Room, Elev. 351.S'. The fan is 100% 196 330 6

1 capacity (15,620 CFM) and is controlled automatically by an interlock with fan-coil unit fans AH-C-16A & B. The fan may be controlled locally by a pushbutton or remotely from Panel No. 25 by selector switches (P ULL-TO-L OCK-S T OP-AUT O-S TART ) AH-HS-5207. The fan, rated at 10HP is powered from 480V BUS 2-12E. Local and remote pilot lights indicata the fan's operating condition. 2.1.8 Miscellaneous Fans one kitchen exhaust fan with grease filter and one toilet exhaust fan (see Tables 8 & 9) are both rated at 200 CFM. Each fan is controlled by an interlock with its associaeted light switch. The kitchen exhaust fan, rated at 1/6 HP, is powered from MP2-42C, the toilet exhaust rated at 1/6 HP, from MP 2-42C. 2.1.9 Control Buildina Licuid chiller Units AH-C-8A & B Two 100% capacity Control Room liquid chiller units (see TrSle 10) are located in the Mechanical Equipment Rocm Elev. 351.5', each rated at 110 tons refrigeration capacity. These units cool water in the closed chilled water system and reject heat to water supplied by the Control Building river water booster puutps.. The chiller units are controlled locally by a pushbutton station with indicating lights and remotely by a selector switch (PULL-To-LOCK-STOP-AUTO-STAItT) with indicating lights located on Panel No. 25. The chiller units AH-C-8A & B, are powered from 480V BUS 2-12E & 2-22E respectively. i 196 331 -1

~ 2.1.10 control Buildino Licuid cooler Pumor AH-P-1A and B Two 100% capacity Control Building liquid cooler pumps (see Table 11) single-stage, centrifugal type, located in the Mechanical Equipnent Room, Elev. 351.5', are rated at 275 gpm each with a total discharge -head of 220 ft. The pumps cir-culate chilled water through the water coolers of the Control Room liquid chillers and the cooling coils of the Control Rocm and Cable, Battery and Switchgear Rooms fan-coil units. The pumps are controlled locally by puslibuttons or remotely from Panel No. 25 by selector switche_ (CN-OFF), AH-ES-5206 &-5209. The pumps AH-P-1A & IB are rated at 10HP each and receive power from 480V BUS 2-12E & 2-22E respectively. Pump operation is indicated by pilot lights locally and on Panel No. 25 in the Control Room. 2.1.11 Chilled Water System Expansion Tank AH-T-1 The expansion tank,(see Table 12) is constructed of carbon steel. It has a capacity of 65 gallons and is l'6" in diameter. The tank is located in the Mechanical Equipment Room of the Control Building. near the liquid cooler pumps. The tank has a vent, a valve drain and is connected to the common suction of the liquid cooler pumps. 2.1.12 chilled Water System Chemical Feed 'iank AH-T-2 The Chemical feed tank (see Table 13) is constructed of carbon steel. It has a capacity of five gallons and is 8 " in diameter and 25-7/8" long. The tank is mounted horizontally in the Mechanical Equipment Room of the Control Building near the liquid cooler pumps. 196 332

The tank has a fill connection, vent and drain valves, a relief valve set at 55 psi and inlet and outlet connections common on loth liquid cooler pumps. 2.2 Instruments, Controls, Ala rms and Protective Devices The following instruments, controls, alarms and protective devices are used in the Control Room Heating, Ventilating and Air Condi-tioning System (see Tables 14 and 15) : Selector switches, with pilot lights to indicat operation, are furnished on HVAC Control Panel No. 25 in the Control Room for remote operation of the supply air fans. An electrical interlock starts the exhaust fan when either supply fan starts. Solenoid valves admit instrument air which opens the damper located in the discharge duct of each supply fan, and opens the shut-off valve at the water inlet of the cooling coil when the associated fan motor is energized. A solenoid valve, AH-EP-5207, admits instrument ai'r to the operator closing the damper located in the exhaust fan bypass when the exhaust fan motor is energired. The control Room bypass supply fans receive a start signal from the Safety Features Actuation System, Radiation Monitoring System (high radiation in the Control Room supply duct) and the Chlorine Gas Monitoring System (Air Intake Tunnel and Control Building Air Intake Duct). Interlocks _ with dampers place the control Room in the minimum outside in recirculatian mode when the far.s start. The Control Room bypass supply fnns may be started manually either locally or in the Control Room.

  • J 196 333

.~ The Control Room supply damper, AH-D4092C, is closed by detection of chlorine gas, fire or incipient explosion in the Air Intake Tunnel. A limit switch on the supply damper is interlocked with damper AH-D4092D & E and AH-ED 4098 to position them for recirculation when AH-D4092C is closed. Red pilot lights on Panel No. 25 indicate operation of all fans, green lights indicate the fan is de-energized. A selector switch for the exhaust fan is provided on Panel No. 25 for testing purposes. Interlocks with light switches place kitchen u:'d toilet fans in operation when the lights in these areas are turned on. The roll type filters in the supply air system and the con-trol Room bvpass system are progressed automatically by electric motors actuated by differential pressure ' Itches. A high differential pressure across the bypass filters, indicative of dirty fitlers, is indicated locally. Limit switches on each Roll-Aire filters actuates an alarm on Panel No. 25 when the roll has advanced to the end of its travel. A bypass supply differential pressure controller modulates the inlct vanes of the bypass supply fans to maintain constant flow through the filters as filter resistance builds up. Flow switetes in the outlet ducts fro.a the Control Roola supply fans are provided to energize red lights on Panel f No. 25 when flow is established. A flow alarm is actuated if a fan is energized and there is insufficient flow. 196 334 M

? Heating coils, recirculation dampers, and cooling water flow are controlled by the Control Room pneumatic thermostat AH-TS-5209. Heating coil operation is indicated by a local pilot light. A temperature controller is provided in the outside air supply duct to place the system on minimum out-side air recirculation when ever the outside air temperature rises above 70 F. The controller closes supply damper AH-D4092D and exhaust damper AH-ED4098 and opens recirculation damper AE-D4092E. Replenishmenc air (1000 CFM) enters through the minimum outside air duct to prevent the air from becoming stale. Level controllers on the chilled water expansion tank AH-T-1 control makeup water to the system by opening and shutting the demineralized water make-up valve DW-v15. If the tank level exceeds its normal operating band high and low level alarms are annuciated on Panel No. 25. The Control Room temperature is recorded by a multiple pen recorder on Panel No. 25. The recorder gives the operator a continuous record of Control Room temperature during normal and emergency conditions. Also the operator may detect trends which can be used in evaluating the operation of the ventilating system. The outside air temperature is indicated locally at the supply duct in the Mechanical Equipment Room. ~~ 196 335 e

selector -witches and indicating lights are provided on Panel No. 25 for remote operatien of Control Building river water booster pumps, liquid cooler pumps and liquid chillers. Chilled water and river water temperatures are recorded on a m;1tiple pen recorder on Panel No. 25 and are indicated locally. Local pressure indicators are also furnished ror river water chilled water pressure indication. A flow switch is provided in aach river water and chilled water circuit to energized indicating lights on Panel No. 25 whenever flow i established in its respective circuit. The flow switches in the chilled water lines are also interlocked to open the liquid chiller river water shutoff valve to the associated liquid chiller condenser and to permit starting of the associated liquid chiller compressor when chilled water flow is established. White and green pilot lights on Panel No. 13 indicate the position of NR-V144A & B. 3.0 JNCIPAL MODES OF OPERATICN 3.1 startuo The valves and damper positions are check d for proper line up. The fire dan.pers are checked by opening the adjacent access door. One ci the two fans 'AH-C-16A & 16B) in the fan coil unit is startec remotely from the Control Room (panel No. 25) by AH-HS-5216 or 5217. The second fan is a standby unit. Indication of which fan is opera. ting is shown in the Control Room. The second fan automatically starts if the first fan stops for any reason. When the fan is started, the associated solenoid valves are energized, wich allows instrument air to open the associated two-position [. 3-fan discharge damper (AH-D4096A or B) and cooling coil water supply shutoff valve (AH-V32A or B) in the chilled water supply pipe line. 4 XI/ J JJ0 o

.~ By electrical interlock, when either of the supply fans ( AH-E-16A & B) is started, the main exhaust-return air fan (AH-E-36) is started. When the exhaust-return air fan is operated, the associated solenoid valve is energized, which allows instrument air to' close the two-position damper in the bypass duct around the exhaust fan. If the exhaust-return air fan motor should fail or be stopped manually, the solenoid valve repositions and allows instrument air to open the damper in the by-pass duct allowing free passage of air to the exhaust-return duct system. After a Control Room supply fan has been started, flow switch AH-FS-5215 or 5219 in the supply fan inlet duct energized flow light AH-FL-5215 or 5219 or verify that air supply flow has been established. A flow alarm on Panel No. 25 will be actuated if a fan is energized and flew is not sufficient. After a supply fan has been, -started, chilled water supply to the Contr and Cable Rooms is established as follows: A chilled water pump, AH-P-1A or 1B, is started from Panel No. 25 using control switch AH-HS-5206 or 5269. Once chilled water flow is established through a water cooler a flow switch will open the river wat er inlet valve, NR-V144A or B, to the associated chiller condenser. A Control Building River Water Booster Pump NR-P-2A or 2B, is started from Panel No. 25 using control switch AE-HS-5267 or 5268. A chiller unit compressor is then started. Interlocks prevent starting a chiller unit unless chilled water flow have been established through the unit and one Control Bnilding River Water Booster pun.p is operating. 196 337 , o-

~: Flow lights AH-FL-5205 & 5282 and AH-FL-5280 & $281 are provided on Pane'. No. 25 to indicate flow into the chilled water pumps and from the control Building River Water booster pumps respectively. All fans, chillers and pumps have local controls in addition to those located on Panel No. 25. Red and green indicating lights are provided with local and remote control switches, When the controls are in the" PULL-TO-LOCK"or"AUTd' positions and the equipment is not running, the green light is energized and when.the equipment is operating the red light is energized. 3.2 Normal Coeraticn, The thermostat (AH-TS-5 209) in the Control Room maintains the set temperature as follows: As the room temperature drops o below the set point (75 F), the operating fan-coil unit electrical heating elements are energized in multiple stages. The heating elemc s in the idle fanm oil unit are not energized due to an electrical interlock with the fan motor. As the room temperature rises the heaters are de-energized and when the temperature is above the set point, the thermostat positions the outside, re-turn and exhaust dampers AH-D4092D, AH-4092E and AH-D4098 so as to increase the proportion of outside air handled by the fan, and decrease the proportion of recirculated air. If the room temperature continues to rise and the dampars are positioned for 100% outside air, the thermostat modulates the three-way valve (AH-V33A or 33B) ' located at the outlet'of the cooling coils ~ to admit ch111ed water to the cooling coils chiller. 196 338

l Control of the outside, return and exhaust dampers is re-moved from the Control Room thermostat whenever the outside air temperature is above 70 F. This is accomplished by the temperature indicating controller AH-TIC-5209, with its sensing element located in the outside air duct. The controller positions the damper for minimu outside are recirculation. In this mode, all of the cooling a supplied by the chiller units. The rolled media of inlet filters AH-F-2A & B are advanced automatically by a differential pressure switch when pressure drop across the filter reaches a predetermined value. The exhaust fans serving the kitchen (AH-E-25) and toilet (AH-E-5 ) areas and their associated dampurs are electrically N interlocked with the light switches for these areas so that they will operate whenever the lights are turned on. Annunciators are provided per Table 4 to annuciate deviations from normal operating conditions on Panel No. 25 in the control Room. 3.3 Soecial and Infrecuent Coeration Control switch AH-RS-5207 allows tne operator to test the exhaust fan AH-E-35 without starting either supply fan in fan-coil unit AH-C-16A or B. The switch also allows the operator to stop the exhaust fan by placing the switch in the " PULL-TO-LOCK" position without de--energizing supply fans. To remove smoke-and vapors from the Control Room, the toggle switch in the local fire detection panel must be placed to {I 196 339 M

1 " DISCONNECT". This overrides al ,e interlocks cssociated with the local fire fatection panel and allows the dampers to be positioned for 100% outside air and the supply fans to be starte'd. The override switch may be returned to normal when the smoke and vapors have been reduced sufficiently to reset the detectors. Provision is made to allow the system to being in all outside air, with no recirculation air, regardless of the outside air temperature. This is accomplished by a Manual Sw..cch (AH-KHS-5 209 ) on Panel No. 25 in-the Control Room which actuates an electric / pneumatic rela.y in the control ine to the outside, return and exhaust dampers. When this is activated, the cooling coils may not have sufficient cooling capacity to maintain Control Room temperature at 75 F. This mode would be used to clear the Control Room of smoke and vapors after a fire. 3.4 Shutdown The chiller units shoulm be shutdown first; however, ensure tha t they are not required for cooling the Cable Room. The chiller units and the liquid cooler pump can hutdown locally or re-motely from 'anel No. 25. Before stopping the supply fans or the bypass supply fans, if they are running, the control switch for the standby fans must be placed in "P ULL-T O-L OCK ". The running bypass supply fan is de-energized and ten (10) seconds later the control switch on the standby fan may be placed in "A UTO ". The control switch for the supply fans must be placed in " PULL-TO-LOCK" to prevant restarting af ter it has been stopped. The exhaust fan will stop automatically when both supply fans are de-energized. f 196 340 O _22_

) ? 3.5 Emercency A signal from the Safety Features Actuation System, Radiation Monitoring System or Chlorine Gas Monitoring System automatically starts one Control Room bypass supply fan which are interlocked with AH-V 124A & B and AH-V125A & B to position dampers AH-D4092A, B, D and AH-ED4098 for recirculation. A signal from the chlorine Gas Monitoring System also closes damper AH-D4092C which places the ventilation system in the 100% recirculation mode. The SFAS system also starts Control Building RW Bocater punps, a chilled water pump and a liquid chiller uvit. After detection of an incipient explosion, fir"cor chlorine gas in the Air Intake Tunnel, the system is shifted to 100% recir-culation, by shutting the air supply shutoff damper, AH-D4092C. Cperation of a Control Room bypass fan energizes its associated solenoid valve which allows instrument air to open the two-position damper in the fan discharge duct. A differential press-ure controller (AH-DPIC-5211), controls the inlet vane dampers to allow constant flow as the filters become loaded. A differen-tail pressure switch ( AH-dPS-5 212) actuates an alarm in the Control Room dhen the filters be5 cme ~ loaded with

dust, as indicated by an increased pressure drop across the filters.

A signal from the local fire detection panel stops all the fans and itions the dampers AH-D-4092A, B, C and AH-ED-40 3 2 for. recirculation when fires or smoke is detected in the contro l Room. ? 196 341 O

t 4.0 .1AZARDS AND PRECAUTIONS Care must be taken w start a liqu'd cooler pump before starting a Control Building river water booster pump and stopping these booster pumps if there is no demand for river water to prevent them from running at a shutoff head for long periods of time. The filters in the control Rocm bypass filter train must be treated as potentially contaminated. Care must be taken when changing these filters especially after a LCCA or high radiation emergency. Combustable vapors in the Air Intake Tunnel alarm on Panels No. 1 but no automatic action is provided. 196 342 e _RA

_~ 3 = '2A B L E 1 CONTROL ROCM FA N - COIL UNITS Unit Details ~ Identification A H-C-16A & B No. Installed 2 Manufacturer Buffalo Forge Model No. 160 PC Coolinc Coil Details Manufacturer Buffalo Forge Model No. 160 PC Cooling coil Area, ft 27.7 ~ Rows and Nominal Fins per inch 6;2.4 6.ircuit Full Cooling Capacity, BTU /hr. 440,000 Cooling Water Flow, GPM 82 A ir Velocity, F PM. 564 Cooling Water Head Loss, ft H C 15 2 Cooling Water Temperature, In F/Out, F. 45/55.7 Entering Air,. Dry-Bulb, F/ Wet-Bulb,UF 75.4/63.2 Leaving A ir, Dry-Bulb, F/ Wet-Bulb, F. 57.1/55.3 Fan Details Model No. 1-365 BLD Type ' Centrifugal Rated Capacity, CFM: 15,620 S ta tic Press., in. H0 2.5 2 s' 196 343

TABLE 1 (Continued) CONTROL ROO4 FA N _C OIL UNITS _ Fan Details Ra ted Speed (rpm) 2093 Other N/A Fan Motor Details Ma nufacturer Westinghouse Type 2847 Enclosure Open Rated hp 15 Ra ted Speed, rpm 180a Lubricant-Coolant Oii/A ir Power Requirements 46 OV, 3g,' 60Hz Power Source 480V B.ses 2-12E for AH-C-16A 2-22E for AH-C-16D. Heater Details Manufactur ar I Model No. Type Electric Coil capacity,Kw/ step 15, 15 & 20 Power Requirements 480V,35,60Hz Power Source 480V MCC 2-42C Classification Code C Quality 4 Seismic I Cleanliness C 196 344.

TA BLE 2 CONTROL ROOM SUPPLY FILTER Filter Details Identification Control Room Supply Filter - A H-F -2A &B No. Installed 2 Manufacturer MSA Type Horizontal Roll Filter Model No. H66AC Size 3'O X 10'11" Capacity 15,620 Pressure Drop, Clean, in H O 0.16 2 Efficiency 85% (NBS Dust Spot Test) Drive Motor Details Manufacturer Type Induction Motor Enclosure Open Rated hp 1/6 Rated Speed, -1450 Lubricant Coolant oil / Air Power Requirements 1 1 5 V,1 5.,6 0 H z Power source 120V Power Panel MP2-42C Classification Code C Quality 4 s eismic I Cleanliness D 196 345 [ G W W

_~.i TABLE 3 CONTROL ROOi - BYEASS SUP PLY FA NS Fan Details ~ Identification Control Room Bypass Suoply Fans AH-E-4A &B Number Instalied z Manufacturer Buffalo Forge Mode 1 No. Later Type C en trifuga l Ra ted Capacity,.CFM. 15,620 ^ Static Press., in. H0 ll 2 Rated Speed, rpm 2187 Other variable inlet vane with air operator and positioner Qn Motor Details Manufacturer Westinghouse Type Squirrel Cage Induction Enclosure Open Rated hp 40 Rated Speed, rpm 1800 Lubricant-Coolant Oil /A ir Power Requirements 460v,'35,60 H: Power Source 480V BUSSES 2-12E for AH-E-4A 2-22E for AH-E-4B Classification Code C Quality F7ismic I Cleanliness D ~ .g. 196 346

.5 e TABLE 4 C_ONTROL ROOM BYPASS ROLL-A IRE FILTER Filter Details Identification Control Room Bypass Roll-Aire Filter AH-F-3 Number Installed 1 .V.nufacturer MSA Type Vertical Roll Filter Model No, V66AC Size 5'0" X 7'8" Capacity 15,620 Pressure Drop, clean, in H O 0.16 2 Efficiency, 85 (NBS Dust Spot Test) Drive Motor Details Manufacturer Type Induction Enclosure Open Rated hp 1/6 Xated Speed, 1450 Lubricant-Coolant Oil / Air Power Requirements 115V{3;3,,60 HZ Power Source 120V Power Panel MP2-42C Classification Code C Quality 4 Seismic I Cleanliness D 5 T_.

.i TABLE 5 CONTROL ROCM BYPASS ABS OLUTE AI_R_ FILTERS Filter Details Identifica tion Control Room Bypass Absolute Filter AH-F-4, AH-F-29 Number Installed 2 Manufacturer MSA Type HEPA Model No. None Size 24 " X 24 " X 11 Capacity, CFM 15,620 Pressur : Drop, Clee.n,in H 0' l.2 2 Efficiency, 99.97% Cla ss ifica tio:t Code C Quality 4 Seismic 1 Cleanliness D 'S 196 348

.3 TA BLE 6 C OPTR OL R OCM BYPA S S CA RB CN A IR F ILTER Filter Details Identification Control Room Bypass Activated Carbon Filter AH-F-5 Number Installed 1 Manufacturer MSA Type Activated Charccal Model No. None Size 24" X 40" X 7-3/4" Capacity,CFM 15,620 Pressure Drop, Clean,in H O 1.0 2 Efficiency, 99 (Retention) 99.9 (Iodine) Classification Code C Quality 4 Seismic I Cleanliness D r., 196 349

TABLE 7 CONTROL ROCM EmmUST FA N_ Fan Details Identificat #on Control Room Exhaust Fan A H-E-3 5 Number Installed 1 Manufacturer Buffalo Forge Model No. 730 Type Centrifugal Rated Capacity,:CFM 15,620 Static Press., in. H0 2 2 Ra ted Speed, (RPM) 772 Other N/A Fan Motor Details Manufacturer Westinghouse Type Squirrel Cage Induction Enclosure Open Rated hp 10 Rated Speed, (RPM) 1600 Lubricant-Coolant Oil / Air Power Requirements 460V,35 60,Hz Power Source 480V BUS 2-12E Classification r de C o Quality 4 Seismic I Ij Cleanliness D 196 350 l

] TABLE 8 KITCHEN EXHAUST FAN Fan Details Identifica tion Kitchen Exhaus t Fan AH-E-Number Installed 1 Manufacturer Buffalo Forge Model No. C Type Centrifugal Rated Capacity, CFM. 200 S ta tic Press.,. in. H O 3/4 2 Rated Speed, -(RPM) 1725 Other N/A Fan Motor Details Manufacturer General Electric Type Induction Open Enclosure Rated hp 1/6 Rated Speed, rra 1725 Lubricant-Coolant Oil / Air Power Requirements 115v,14,60 Hz Power Source 120V Power Panel MP2-42C Cla ssifica tion Code C Quality 4 Seismic II f Cleanliness D 196 351 ~ O m"

T TABLE 9 T OILET EXFA UST FA N Fan Details Identification Toilet Exhaust Fan AH-E-5 Number Installed 1 Manufacturer Buffalo Forge Model No. C Type Centrifugal Rated Capacity,.CFM 200 S ta tic Prens.,,in. E0 5/4 2 Ra ted Speed, RPM. 1.25 Other N/A Fan Motor Details Manufacturer General Electric Typ Induction Enclosure Open Rated hp 1/6 Rated Speed, RPM 1725 Lubricant-Coolant Oil /A ir Power Requirements 115V,'15,60 H Power Source 120V Power Panel MP2-42C Classification Code C Quality 4 Seismic II Cleanliness D i a 196 352

_~ 5 TA BLE 10_ CONTROL _ BUILDING LIQUID _._ CHILLER UNIT Unit Details Identification A H-C -8A & B Number Installed 2 Manufacturer York Model No. HT-A 3 -A 4-A B Type Hermehic Turbopak Capacity,' tons 110 Chilled Water Flow, 'GPM. 275 Chilled Water Inlet ~ Temperature, F 54.6 Chilled Water Outlet Tempera cure, F 45.O Chilled Water Cooler Pressure Drop, ft. 13.6 River Wa ter Flow, G PM 243 River Water Inlet Temperature, F 85 River Water Condenser Pressure Drop, ft. 7.1 Chilled Water Cooler Fouling Factor, in. .0005 Cndenser Fouling Factor, in. .001 Condensing Temperature, F 110 Compressor Motor Details Manufacturer Borge Warner Type Induction Enclosure Closed (Hermetic) 3, Rated hp 95 Rated Speed, rpm Later !96 353 ~ =-

.i TABLE 10 (Continued) CONTROL BUILDING LIQUID CHILLER UNIT Compressor Motor Details Lubricant <oolant Oil / Air Power Requirements 4604 3g,60 HZ ~ Power Supply 4 80V. BUS ES 2 -12 E for AH-C-8A 2-22E for AH-C-8B Classification Code C Quality Control 4 Seismic I Cleanliness D 9 e m /

TA BLE 11 CONTROL BUILDING LIQUID COOLER PUMPS Pumo Details Identification Control Building Liquid Cooler Pumps AH-P-1A &B Number Installed 2 Manufacturer Crane-Deming Model No. A 40 Type Horizontal Centrifugal Rated Speed, RPM 1750 Rated Capacity, gpm 275 Rated Total Dynamic Head, ft. 60 Submergency Required at Rated Flow, ft. 4 Cesign Pressure, Casing, psig 50 Design Temperature, F 45-55 Lubricant-Coolant Oil / Water Min. Flow Requirements, gpm 3 Motor Details Manufacturer Westinghousa Type Squirrel Cage Induction Enclosure Open Rated hp 10 Speed, rpm 1750 Lubricant-Coolant oil / Air Power Requirements 460V,35,~60 HZ Full Load Current Power Source (for each y Pump motor) 480V, BUSES 2-12E for AH-P-1A 3 2-22E for AH-P-1B. 2 196 355

4 e TABLE 11 (Continued) C ONTR OL BUILDING. LIQUID COOLER SUMPS Classification Code C Ouality Control 4 Seismic I Cleanliness D e-en ~ !96 356 '

~ i ~ TABT-E 12 CIIILLED WATER SYSTEM EXPANSION TANK Identification AH4-1 Manufacturer RECO Capacity, gallons 65 Ins talla tion Indoor Out. side diameter & length 18" X 5'0" Shell Material A53 Carbon Steel Shell rhickness, in. .562 Design Temperature, F 100 Design Pressure, psig 75 Corrosion Allowance, in. None Design Code ASME Code Stamp Required Yes Lining ENC OR-PC-7 00 -HB Classification Code C Quality Control 4 Saismic I Cleanliness D G

  • =

e 196 357 ~.

TABLE 13 CHILLED WATER SYSTEM CHEMICAL FEED TANK Identification A H-T -2 Manufac turer Neptune Capacity, gal. 5 Ins talla tion Horizontal O.D. & Length, in. 8 X 25-7/8" Shell Material CS Shell Thicknecs, in.

1. 2 Design Temperature, F

65 Design Pressure, psi 50 Corrosion Allowance, in. None Design Code N/A Code Stamp Required N,'A Classification Code C Quality Control 4 Seismic I Cleanliness D ~. 126 358 [ ., A n

.. v O c..g * ' K ' ' ' '.. 5 ._ g e . f [ '. -~~ ^

  • L L

.... _ g-

\\.

_ 'e ..- f y ..L

e.. <...:... -
c. ;.....

y CN. Ln e v. ........ o u s........ euosaev............................. eae ee ao. . o r.... c =o. e v...... oa e e........................................... aoe ao.. b.. tastz 14 3 M5TFUte'If1ATIGM AHD C0er! pot 9 w Identification reecription Function !a stion g e_ Ieput pa rrJ e rutgut BAnge Set Twint AH-rs.5180/5181 Flow twitch Detect it = in the 4* river water inlet line to the 1.iquid Chillere ripe vane later N/h 30 9p AH-C-8A & 88 roe petively. Actuated An-FL 5180/5181 Indicating anJ1cate (rtow.Ho riow) condition in the 4* river water triot 11ae Panel 25 pod-Creen N/A e/A N/A Light to the Liquid Ch!!1ers An-C-8A : *e respectively An.rs.5182 /5 2 05 Flow Vwitch Detect f!cna in the intet to the Liquid Cem.ier rusys AH-r-13 s 1A Pipe vane later N/A 137 gp toegwctively. Interlocked with HR-V14a4 & a arm! All-C.8A s as. Actuated AH-FL.5 U * /52 05 Indiceking Indicate (Flow-eu riow) condition in the inlet to the Livia Coolant isnel 25 ped-Green N/A N/A M/A Light Pumpe All-r-la 4 1A respectively. "4 ritter Lielt N/A N/2. End of An-Es-518?/5213 Lielt switch Provide indication of when replaceaent of filter Au-r-2e reegetively le necessary switch Travel An-L2-5185 tavel Irmlicate level in Chilled Water ripension Tarl. Tank ca g e Glase 0-5' 0-5* m/4 InJ!cator An-rd-51a 4/5185 ' Tank 14 vel Provide indication of high and low levet in CMlled water tipension Tann Tonk Pressare 1-45" W.Q. H/A 3g./26* Contsol Switcle An-rg-5186/5189 Tank levd Provide *Open" and

  • shot
  • signet to Chit.3d water Espenelon Tank fit!

Tank Pressure 1-45' W.C. H/A 31.5*/27.5* Control valve [W-vl5. switch An-TE-5199 p o s i s t a nce Detect toeperature of Control Room and traneult signal to recorder ripe RTD 0- 2 00*r 92.93-115.97 A M/A Thereaseter AH-m -5199 An-m -5199 pecorder secord on multipoint temperature secorder temperaturee received s'enet 25 Hultipoint 92.91-135.9 7 A 0-200 r m/A twint from resist ances therscuaeter AH-TE-5199 socorder An-Tt-5200/5201 peelstance Detect cFille d water teoperature entering the water cooler in rire RfD 0-200*r 93.93-135.97n N/A Tvermometer Liquid Chillere AH-C-0S & BA respectively. A n-m-52 00/5201 p ecor der secord on asuttipoint temperstore recorder temperatures.eceived renet 25 Multipoint 92.93-135.92 A 0-200 r N/A twint from resistance thermoseters An-TE-5200 s 5201 respectively. pecorder An-Ts-5202/5203 poeletance Detect river water to perature leaving the condenser in the ripe ' r0 0-200*r 92.9 3-13 5.9 7 n N/A Thermanee t e r Liquid C2)!!1ers AH-C-en s BA respectively. An-m -5202/5203 pecorder pecced on s=31ttpoint te=rerature recorder temperatures received Panel 25 Multipoint 92.93-13 5.97 A. 0-200 r M/A Point from reelstance thermometers AH-TE-5202 a 5203 roepectively. socorder A H-T10- 5204/' 2 5 0 'esperature peyulate river water flow to Liquid Chiller ConJereers Chiller fneunatio Controller -10 to 124,r 3-15 peig 70,r Controller An-its-5206/5269 pt> t or Provide Leuto-on-of f) contset for Liquid Cooler rumps AH-r-1A & le renet 25 SSM N/A N /A N/A Operator respectively. Switch rooo ee.mee e amm. 'l I 8.'s18 'e e 4 'i e44 4

7'egIt; l* I. Q 4"Q g% i g t n o f g c P S o gw 3"l P r F p t A A A F A A A A A d, F e / / / / / / / 5 5 / / n, 3 5 5 N N N N N N 7 7 N N 3 E 7 5 1 1 e gna l G p l l e W e l e t p p p ' e u r r p 5 e e S 5 .I-p 5 t t t A A A A A 1 A m 1 j A 0 / / / 3 n a / / 2 A 2 o / W N N N o I l N 3 N / C N 0 3 N e F M gn 4 F S 2 C a l S t 1 0 G G P R e R W F P e 2 p 5 F p o 6 t 1 0 0 t u 5 2 5 5 8 3 p A A A 0 A A 3 A 2 0 1 n / / / - / 5 / / I N N N 0 N 5 0 2 N b N 0 0 1 0 h t n n c n n o o y oa o m e g d o t o d e t t rd t t t e i e ee o o G S C aCs t t a n t s t a u a w r t a a l a ao u r h t T my my l mm b h t c r a e eu - ua ue ieb ur h p l t e eu t p J N d ntJ el el pbl e o s a ai t nt y e B e a ce n e n e a uu o n u i i w a a c T A S p VAp Pp Pp CTB rn l P D LS l VA i P n 5 5 5 5 5 o 2 2 2 2 2 i r SI a e e e t a c h k k e t t t k t t l l l k t e ) O c n n n c n a c c c n c c l c t d R o e a a h e R a a a a u u i a c e T l r P F t P S b p F D D F R u u H D n C t C t r D i o N C ( A N 4 O 1 I E y T E s l L N 9 a s o a v r s e B 0 r r - e A E 2 e onD g nt t p s i T_ M 5 5 1 f a n a e a s t U a 3 f e 1 F2 i n t l r y a c ou os 9 d o ne B p e D i C T u s I rr n0 i m fi p p e S q T ss t oi4 r e yo o n y s N i H a s nt D r c b e i p e I L A M e e oa e - e c sho r r r cr! v s st t r s M o e n e t e e e r n t P e! o 5 a r s ppo h a r ga t ca 1 6 f 3 F es p s teocs n t F t nm l r. l r ue r o si u i c t E t l e l s oge i n y pt e f a s o. e e s ot t p t ng t i l us n o n H n 5 u ra cu gt a p up r e A i e A a 3 a t e uD nal a l w psj p r 6 p p h nh d i mod i o8. u rd a u 1 n I a o o t uo t l 4 S ea e s l a l B cd tt a ecn n f t h h s C o r o M m ga 2 l l epei v e sibi r H n e rn o e s sl yt t e r r o... t t t o n 9 na p h t t A af w f p A h n s n n r is 0 in oet a r a4 p d o o Y o u o a f t e 4 g h l i c - - s es t a n c, a s 1 la c F a v D mi yt ou a i E ys nn t s t s t cl 5 o s b t c d - B oia n i i m o ee s e t e i a o s r e nH raF e t n hv E h s l d v H' R c mr ei d iA ect m n If s J ti t u t n A i oe v c i ha iny e e t r a u i e l t otl e s d e t l c r l nc o n h o l d oa ma ar t n n pa p a, e l ee f o x et n rm ev u p E e rt a t u lt e ne, a a h omp l y f o F gr u pr f C h uo n e o sh l d ud ss ea i f) s l ) f t t r D on rost so a y o i rs d n e o f f r r f o ah C p ti a 0 r el re s s a o t o n rt nrpd 0t h y h rps ne h F - a n t i e C ea ot yn 1 n t uoa ec g rl o r e pl 2 h Cet a o eq r s rp h e i f e c e5 l ) eo 0 i nl wB t u oe y si 9 t t t oc rS wsd - wn h o w6 ) w3 t w u o t c 4 nm8 i ao e s s l r es f e f t PA f PB o l D i s9 l & t r s e f pue ol o e n-o n H" .F mg n0 eef f u ee 1 f e on H ea2 rh A i t r p t t sh na nk, l t oP oA h o ri A r r5 ut r6 h a p-nnst or on u J n t N fl ut - t e1 sr y aa e i a i a o rN o rn o e t S art - e oB t t r n t B t B n eA ee t w l o r adP r oaC 4 l p l as pi a a t o ws o s T a o ac r nD ef w8 a m ao nn cr cr a p ea - p H9 ue at > ot s e i e i t t l n P p u P F gl m p H m8 dA 0 nt n rcnr lJt dt w t ( u ( ea f e t t er 5li D c m a I t w ( i o a m sA e1 e 4 a yt a e nl nl o s o n u l sr D ee t2 l t - mc d c sat p ii ii l u eP i u n s m F F f F t e t h t en l po l in - et ed i gna e e a r J a a t a vo o t yt oshUt J a an od d y

d. l y

t c e icB c c i c r cb c r c A 1 m ut J t ic il c i l v e i e t e e t4 l vo s e np e vp vp e a d o o d r t d cd n t el n1 el d ot al i e en op op t no r no e n en o eh e o2 hon r u e n a a ru ru e I C P I f D I p a c DtS C5 tCa Pa Mi Nkenv Ps PS D t' 8 m c. i a.. 8-J a h 8 s.. r - l c u o y y io t S t s a l d r h li l l n a t e n an c iaw h o g r g e g a e rgr t o i I n t c i n e n t n p p une a t t o i t t t i p i i i til t t n eC w ne i p t O t w t at l s u ,t l t s er w eug i a a s a o e r u S r a o o B n r w r ct r ct ct r s ecr m e e s n t es ih o ih w ih t t pit r h ,m c. f si i f s w s s e ni d g o d g n n md n o s o e f et r m f e o d g t o~ o g n i. l ni eno n u l i re e i i r l D I L M I 1 F IL C C TI C e 4

r P

E CP cl L DP F t T D. 0 9 9 1 e n 6 3 2 v. o s i 3 3 1 A 8 1 2 / t / 9 9 9 9 1 1 5 a 6 7 7 0 4 u 0 0 9 0 1 2 2 2 1 o c 0 0 0 0 0 2 2 2 0 2 1 5 1 5 2 a 5 5 C 5 S v M i 2 2 2 2 2 5 5 5 2 5 2 2 5 f 5 5 5 5 5 i r C S I P 5 a C g t L S L s t v Y F S H E P s d F I F. n E R K r F T T K F d E e H M i' d M M M n M M r H n M m H N A A s I A A A A .A A A A A A A 1 A .a

A ?s '4, O 9 ~N

  • $@$%'A

/// ln, t %d7( $/e% \\W/// VN" IMAGE EVALUATION TEST TARGET (MT-3) 1.0 l"""=31: P p2 2.2

.
m [j=

Ulll l,l h=*bN lr'. ,M l.25 I l.4 !: 1.6 I 11 6" wl,)/////8 6/>// /$ <a a #$ "qf' (o: j;fh, s 07 <e' e ,p (

s'f)M>W) O o

  • '+[

V /p $ '<@ h'~>O[, , kfe f $ ' ),9 /qV,*?p

  • l:+p

'E ,,// p \\ IMAGE EVALUATION TEST TARGET (MT-3) lIl l.0 I'1"28 .12 5 m l ? pgM pn 3

== l l,l h, hN I ~ g I.25['4 ]i.6 4 6" [% + eh*>),W ? 4 '4 v O '+ + ge s

e5) . 4 '<g) O S ( f' ' f>g $lY,0' ~'~~ / 'a hl" ,0 hy (YlM p,',4 ,, l)' ~*' v' IMAGE EVALUATION N TEST TARGET (MT-3) 1,0 til 72_8===Cl 2 5_ gg Lw 3h E !'; ll]== l 2.0 l,l

t..,.

e I IN l.8 ll11 I.25 ml IA I 1 I .6 lm V d*' % %+ v%p 4 &w'y s m s %V.. p t,* 6, y ep (

sh'> b ? '<$> +')gf,, AA /N 0 o ?: \\> ' 4 ;. b9 , E, ~??, f / IMAGE EVALUATION TEST TARGET (MT-3) 1.0. In [28 ?12 5 '=^ ^ . ', E2 u. 3,'? n== p, 1' l.1 ["; IUM l]l.8 1.25 1.4 "!'t I.6l!_ 6"

  1. 4 44
  2. $6.04%

JV $% ! ?v s,/,, // oN e,u, ~ go

N

.15 s

.xv. Qlsj. a; ' w 'ig ' -z, eveJact.. ene st no.... ...or...... Q of . -- oat s. cnan. av......onv a.. Jos no. TAh!2 14 (Continued) m ItSTuteENTATION Ate) COff!H0tJ 3dentification Description Function location M Input pange Output penge Set Point AH-Ftr5215/5219 Indicating Indicate (Flow-Ho riow) at the outist of Fan-Coil U11te AH-C-16A & Panel 25 Red-Green M/A N/A N/A Light 168 respectively. An-le-5216/5217 control switcle Provide f auto-on-off) control for the f ane in ran-Coil Unite Panel 25 SSH H/A N/A N/A AH-C-16A & 16 B respectively. Switch AM-rL-5216/5217 Indicating Indicate (Power-en Power-off) on the control panel for the Panel 25 Red-Creen M/A N/A N/A Light fane in Fan-Coll Unite AH-C-16A & 169 respectively. AH-ns-5265/5266 Control switch Provide (auto-on-off) contsol for sy-pase sun ty rans Fanel 25 san N/A N/A N/A AH-E-44 6 48 respectively. Switch An-K1,5265/5266 Indicating Indicate (Power-on poter-of f) on the control panel for tanel 25 bed-Greea N/A N/A N/A Light By-pass Supply Fame AH-E-44 6 4B respectively'. AH-MS-5770/5771 control Swhah Provide remoto (auto-on-off) control for the Liquid Ch111ere Penet 25 SBN N/A N/A. H/h AH-C-SA & 8B respectively Switch AH-Kir5770/5771 Indicating . Provide (Power-on, Power-off) on Panel 25 for I.iquid rhillere Panet 25 pod-creen tyA/ M/A N/A Lights AH-C-8A & SB respectively. i e 9 6 .S.e 90 0 h 8 Of 0 4 4 gg gg* g

u % 0 sg. ,?

e..r t

1 - - * ~ ._g, N,'. b a v........... o A15...... eveJaCT................... esse E F peo...... o F.... O caen.av.......ai........................... so. no..._........ O N TASIX 15 CX I ANEL MrR]WTrD AHHUICIA1TRS Alarm I* identification Meesured E.eecript ion, Unite g low toput Source Ver. Sange grg t An-53A-5183/5213 End of treeel for Aalled Media r!! tere AH-r-2A & D respectively. WA N/A AH-FJB-51al/5 213 N/A 25 AN-1A-5184 High or low level in Chilled water Espansion Tank AH-r-1 34". 26' AH-LS-5165/51G5 1-45* w.G. 25 kH-KAA-5212 End of travel for polled Media rret11ter AH-r-3 f:/A M/A A H-EJ - 5212 N/A 25 AH-disA-5212 Nigh differential pressure acrosa By pees ritter Bank , S *WG N/A AH-tePS-5 212 3 20 pel 25 Control poem ran-Coil Unit AH-C-1f.A & B ran overload N/A ' N/A 012 N/A 25 Control h Dy-pees Supply rene AH-B-4A & B overload N/A N,A OLX N/A 25 Control h Enheuet ran AH.E.35 overload N/A N/A CIJE WA 25 Control pu11 ding Liquid Coolar Pumps AH-P-1A & 3 overload N/A N/A 012 N/t 25 i CCs4Ptfrt2 INPim! H)NE swan se some a g 8.Ma ' 4 g,., 'l. e}}