ML19224B104

From kanterella
Jump to navigation Jump to search
Operating Procedure 2104-5.11,Revision 0:circulating Water Pumphouse Heating & Ventilation
ML19224B104
Person / Time
Site: Crane 
Issue date: 08/20/1975
From:
Metropolitan Edison Co
To: Mullinix W
NRC/IE
References
2104-5.11, TM-0162, TM-162, NUDOCS 7906140051
Download: ML19224B104 (6)


Text

,

..t o

TMI DOCUMENTS

~

DOCUMENT NO:

/

r COPY MADE ON OF DOCUMENT PROVIDED BY METROPOLITAN EDISON COMPANY.

lA Wilda R. Mullinix, NRC

-}

7906140051 186 296 m

e

Lu.lu<-l 0 08/20/75 2104-5.11 Revision 0 THREE MILE ISLAND NUCLEAR STATION UNIT #2 OPERATING PROCEDURE 2104-5.11 CIRCULATING WATER PUMP HOUSE HEATING AND V

.It Table of Effective Pages DQge N T R MOVE ate evision Page Date Revision Pace Date Revision 1.0 08/20/75 0

26.0 51.0 2.0 03/20/75 0

27.0 52.0 3.0 05/20/75 0

28.0 53.0 4.0 08/20/75 0

29.0 54.0 5.0 03/20/75 0

30.0 55.0 i

6.0 31.0 56.0 7.0 32.0 57 0 8.0 33.0 58.0 9.0 34.0 59.0 10.0 35.0 60.0 36.0 61.0 11.0 12.0 37.0 62.0 13.0 38.0 63.0 14.0 39.0 64.0 15.0 40.0 65.0 16.0 41.0 66.0 17.0 42.0 67.0 18.0 43.0 68.0 19.0 44.0 69.0 20.0 45.0 70.0 21.0 46 0 71.0 22.0 47.0 72.0 23.0 48.0 73.0 24.0 49.0 74.0 25.0 50.0 75.0 Unit 1 Staff Recommends Approval Unit 2 Staff Recommends Approval A-Date Approval Date Approval Cognizant Dc;:t. Head Cognizant Dept. Head 1 PORC Recotr.ruends Approval Unit 2 PO C Recommends Approval e

Date g ' thafiman of PORC

/

/

Cha % c I

v PORC comments A

included PORC comments of included

/ ' lhatt',

(date)

Date By By 79) @r e

~ ' Ap Date ova (Stat 6n Suppfinte'ndent/

b 2 h [ " 55'^ "",

~

~

Unit Superintendent

\\2

2104-5.11 08/20/75 Revision 0 THREE MILE ISLAND NUCLEAR STATION UNIT #2 OPERATING PROCEDURE 2104-5.11 CIRCULATING WATER PUMP HOUSE HEATING AND VENTILAT 0N 1.0 References 1.1 Drawings Applicable for Operation 1.1.1 B&R #2047, Heating and Ventilation, Circ. Water Pump House

1. 2, Operating Procedures Applicable for Operation 1.2.1 Circulating Water System, 2104-3.6 1.3 Manufacturers Instruction Manual 1.3.1 Buffalo. Forge Manual - Fan Coil Unit (63.05) 1.3.2 Chromalox Manual - Unit Heaters (63.19) 1.4 System Descriptions 1.4.1 H&V Circulating Water Pump House (Index No. 40) 1.4.2 Circulating Water System (Index No. 15) 2.0 Limits and Precautions 2.1 The MANUAL-OFF-AUTO switches controlling the roof ventilator fans should be lef t in the AUTO position to insure that the fans will start whenever the associated circulating water pump is started and thermostat setpoint is reached.

3.0 Prereauisites INITIAL EACH STEP 3.1 Check power available to BUS 2-51 and the following breakers closed:

i i

Unit DR2 AH-E,-22A Unit DR3 AH-E-22C 1.0 186 298 e

e

2104-5.11 08/20/75 Revision 0 Unit DR4 AH-E-22E Unit GR4 AH-C-21A Unit GR5 AH-C-21C Unit GR6 AH-C-21E Unit GR3 AH-C-22C 3.2 Check power available to BUS 2-61 and the folicwing breakers closed:

Unit BS2 AH-E-228 Unit BS3 AH-E-22D Unit BS4 AH-E-22F Unit #52 AH-C-218 Unit AS3 AH-C-21D Unic AS4 AH-C-23 Unit ASS AH-C-22A Unit AS6 AH-C-223

, Unit-BS5 AH-C-22D Unit FS3 AH-E-29 Unit GS3 MP-2-61 3.3 Check power available to panel MP-2-61 and the following breakers closed:

Brkr.

5 AH-C-21B control power T,r kr.

6 AH-C-22A control power Brkr. 7 AH-C-21D control power Brkr.

8 AH-C-22D control power Brkr. 9 AH-C-23 control power Brkr. 10 AH-C-22C control pcwer 2.0 186 299 O

n-

=-

2104-5.11 08/20/75 Revision 0 Brkr. 11 AH-C-223 control power Brkr. 12 AH-C-23E control power Brkr. 13 AH-C-21A control power Brkr. 15 AH-C-21C control power Brkr. 16 Control panel 321 power Brkr. 27 D5080A and D50803 Brkr. 29 D5081A Brkr. 30 D5081B Brkr. 31 D5081C Brkr. 32

.D5081D Brkr. 33 05081E Brkr. 34 D5081F 4.0 Pror.edure 4.1 Startuo 4.1.1 At the CW H&V control panel No. 321, set eadh exhaust fan MANUAL-Or F-AUTO switch to Avio.

AH-E-22A AH-E-22D AH-E-22B AH-E-22E AH-E-22C AH-E-22F AH-E-29 4.1.2 Set each local unit heater control switch to AUTO mounted on the MCC compartment.

AH-C-22A Loading Platform AH-C-22B Loading Platform AH-C-21A Pump Room, AH-C-21B Pump Room

' 3.0 186 300 e

e

2104-5.11 08/20/75 Revision 0 2

AH-C-21C Pump Room AH-C-210 Pump Room AH-C-21E Pump Room a

AH-C-23 Pump Room AH-C-22C Electrical Equip. Room AH-C-22D Electrical Equip. Room If heating is required, any or all of the electric heaters are started by turning the local thermostat selector switch to AUTO and setting the thermostat to the desired temperature.

In the electrical equipment room, set the local MANUAL-4.1.3 OFF-AUTO thermostat switch for AH-E-29 to AUTO.

4.2 Normal Operation During normal operation, the exhaust fans AH-E-22A thru F operates whenever the associated CW pump is running and the room temperature exceeds 100 F.

The associated intake damper also opens. When the pump motor shuts down, or the room U

temperature drops below 100 F, the associated exhaust fan stops and intake damper closes. Exhaust fan AH-E-29 will operate whenever ele'ctrical equipment room te.Tperature exceeds 75 F.

The unit heaters will start if ambient temperature U

falls below the associated thermostat setpoint.

4.3 Shutdown 4.3.1 To shut down pump room exhaust fans turn each fan selector switch at panel 321 to 0FF.

4.3.2 The unit heaters are shut down by turning the thernostat f

selector switch to 0FF. ' The unit heater control switches are also. turned 0FF.

186 301_

4' 6

=. -. -

2104-5.11 08/20/75 Revision 0 4.3.3 The electrical equipment room exhaust fan AH-E-29 is shut down by turning the thermostat selector switch to 0FF.

v i

~5 o 186 302 I

-