April 22, 1979 To:

Ben Rusche SU3 JECT:

CARBON A05CRSERS IN AUX I L I ARY BUI LD I NG U-2, "B"

TRA IN Cn 4/22, I dis.ussed with L. Kovach the events of 4/21 when the U-2 "B" Auxiliary Building charcoal adsorbers were wetted when the deluce valve was opened.

Kovach has recommended that the trays be renoved from the system in the next 4-5 days and that the carbon be removed from the trays.

Because of the low phi 5.5, he recommends

-t Fe t the trays be dropped in 1% potassium nitrate, reused with water and air dried to prevent corrosion of the stainless steel trays.

I pass this information on to you for your consideration.

J.

T.

Collins 7905230213 165 272

-,