ML19218A073

From kanterella
Jump to navigation Jump to search
Revised - NEIs Proposed Guidance for Section 1.8 of BTP 7-19
ML19218A073
Person / Time
Site: Nuclear Energy Institute
Issue date: 08/01/2019
From: Vaughn S
Nuclear Energy Institute
To: Tekia Govan, Wendell Morton
NRC/NRR/DE/EICA, NRC/NRR/DIRS/IRGB
Govan T, 415-6197, NRR/DIRS
References
Download: ML19218A073 (2)


Text

From:

VAUGHN, Stephen To:

Morton, Wendell; Govan, Tekia

Subject:

[External_Sender] NEI Proposed Guidance for Section 1.8 of BTP 7-19 Date:

Thursday, August 01, 2019 3:34:28 PM Attachments:

Revision to Section 1.8 of BTP 7 Spurious Actuations - Revision 5.docx Wendell and Tekia,

Based on the technical discussion during the public meeting today, the NEI Digital I&C working group made some edits to the draft we provided via email on 7/25. Please find the updated version attached to this email for your consideration as the staff continues the BTP 7-19 revision process.

We look forward to reviewing the draft revision of BTP 7-19 in mid-August and the subsequent public discussion at the end of August.

Regards,

Steve

STEPHEN J. VAUGHNlSENIOR PROJECT MANAGER, ENGINEERING AND RISK 1201 F Street, NW, Suite 1100 l Washington, DC 20004 P: 202.739.8163 M: 202.256.5393 sjv@nei.org

This electronic message transmission contains information from the Nuclear Energy Institute, Inc. The information is intended solely for the use of the addressee and its use by any other person is not authorized. If you are not the intended recipient, you have received this communication in error, and any review, use, disclosure, copying or distribution of the contents of this communication is strictly prohibited. If you have received this electronic transmission in error, please notify the sender immediately by telephone or by electronic mail and permanently delete the original message. IRS Circular 230 disclosure: To ensure compliance with requirements imposed by the IRS and other taxing authorities, we inform you that any tax advice contained in this communication (including any attachments) is not intended or written to be used, and cannot be used, for the purpose of (i) avoiding penalties that may be imposed on any taxpayer or (ii) promoting, marketing or recommending to another party any transaction or matter addressed herein.

Sent through www.intermedia.com

1.8 CCF and Consideration of Spurious Actuations Guidance for addressing software common cause failures in safety-related systems is provided in IEEE Standard 379, Clause 5.5. Clause 4 of IEEE Standard 379 provides guidance on addressing spurious system actuations that cause, or are caused by, a design basis event which the safety function is required to mitigate.

Failure of software to perform as intended is a result of a deficiency in the software design.

Clause 5.5 of IEEE Standard 379states that common cause failures resulting from design deficiencies are not subject to the single failure criteria. As a result, software common cause failures are not subject to the single failure criteria.

Although software common cause failures are not subject to the single failure criteria, it is important to eliminate, to the extent practicable, software design deficiencies. Branch Technical Position (BTP) 7-14, Guidance on Software Reviews for Digital Computer-based I&C Systems, states that software quality is an important element in preventing the propagation of common-cause failures. The first barrier of defense against software design deficiencies is a high-quality design process and specifically, a high-quality software development process. The second barrier is the nuclear quality assurance program which ensures the high-quality software development process was properly implemented.

For A1 systems, the reviewer should compare the applicants software design and development process to the review guidance in BTP 7-14 to reach the conclusion that the software design and development process is of sufficient quality. In addition, the reviewer should assess the defensive design measures that were relied upon to reach a conclusion that the likelihood of a spurious actuation caused by a CCF is sufficiently low. Examples of defensive design measures that could significantly reduce the potential for spurious actuation are:

1. 2 out of 4 (2oo4) coincidence logic of four divisions before issuing an ESFAS or Reactor Trip system level initiation
2. 2oo2 coincidence logic within a single division for ESFAS actuations
3. Energize to actuate design for ESFAS to avoid spurious actuation versus a deactivate design for Reactor Trip
4. Use of only safety displays for manual soft control of A1 components with onerous spurious actuation consequences.

For B1, A2, and B2 systems, as part of the applicants qualitative assessment1 for the system, the reviewer should evaluate that the qualitative assessment supports a conclusion that a proposed digital I&C modification has a sufficiently low2 likelihood of a spurious actuation.

1 For guidance on a qualitative assessment see Regulatory Issue Summary, CLARIFICATION ON ENDORSEMENT OF NUCLEAR ENERGY INSTITUTE GUIDANCE IN DESIGNING DIGITAL UPGRADES IN INSTRUMENTATION AND CONTROL SYSTEMS, ML18143B633) 2 Sufficiently low means much lower than the likelihood of failures that are considered in the updated final safety analysis report (UFSAR) (e.g., single failures) and comparable to other CCFs that are not considered in the UFSAR (e.g., design flaws, maintenance errors, calibration errors).