ML19210D012

From kanterella
Jump to navigation Jump to search
Forwards Updated LERs 78-018/03L-1,78-037/03L-1,78-077/03L-1 & 78-084/03L-1
Date released: 08/12/2019 Download: ML19210D012


Updated LER 78-077/03L-1:on 781011,inner Stage Relief Valve on B Air Compressor Lifted & Stuck Open.Caused by Dessicant from Air Dryers.B Air Compressor Replaced,Dessicant Removed & Compressors Blown Out.Check Valves Installed
ML19210D024
Person / Time
Site: Farley 
Issue date: 11/14/1979
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19210D024 (1)
Updated LER 78-037/03L-1:on 780613,vacuum Pump Kept Tripping on Low Flow.Cause Not Stated.Vacuum Pump Replaced.Flow Trip Setpoint Not Adjusted.Design Change to Add Second Pump in Parallel Has Been Implemented
ML19210D022
Person / Time
Site: Farley 
Issue date: 11/14/1979
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19210D022 (1)
Updated 78-084/03L-1:on 791114,monitoring Sys Declared Inoperable After Vacuum Pump Tripped.Caused by Vibration in Low Flow Relay Unit Due to Broken Wire.Relay & Vacuum Pump/Motor Replaced & Tested
ML19210D019
Person / Time
Site: Farley 
Issue date: 11/14/1979
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19210D019 (1)
Updated LER 78-018/03L-1:on 780308,diesel Generator IC Failed to Start.Caused by Solenoid Valves Sticking Due to Corrosion Particles.Air Start Solenoid Valves Cleaned & Tested.Design Change Implemented
ML19210D015
Person / Time
Site: Farley 
Issue date: 11/14/1979
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19210D015 (3)
Forwards Updated LERs 78-018/03L-1,78-037/03L-1,78-077/03L-1 & 78-084/03L-1
ML19210D011
Person / Time
Site: Farley 
Issue date: 11/14/1979
From: Clayton F
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19210D011 (1)