i I

t-ATI h;i d ti L i

Lj BROOKHAVEN NATIONAL LASCRATOfn 1

((

ASSOCIATED UNNERSmES, INC L43 fort New YM 1197; c -,,,

Jor M rsem Ener,y,r (Sto) 345-2144 Sep^ a r 11, 1978 3

DIvisfon of Operating Reactors a

U.S. Nuclear Regulatory Corurf ss1on i

a Washington, D.C.

20555 3}

d Attention:

Mr Robert f.. Ferguson d

Plant Systemus Branch Subfect:

Addf tfons to Three M1Te Island - Unf t I CTMI-11 Safety Evaluatf on.

Rem i. Review cated Septerner 1,1978 i

Dear Bob:

As stated in the subject report, the following coments rtrieet Mr. J.

Riopelle's imajor concerns about the TMI-I draft SER dated August 17, 1978.

A.

SER 4.3.1.

Add the followfog: Establish a program to hydru-test all fire hoses at 220 psi and to maintain records of such tests.

The outside hoses to be tested annually and the instde hoses every three years. This is also a Bat. position.

B.

SER 5.20.

Add the followfng:

" Create a s1te where a numf cf pal f f re pumper can take suction from the cooling tower basin and pump into the yard Toop to supply a line for inside fire protection."

C.

SER 5.20.

Add the following:

" Inspect all outdoor fire hydrants for drainage of their dry-barrels fmed1ately prior to free 11ng wf n-ter weather, and for p,um functioning Irenediately after the wfnter season. This is also a Bit. position.

D.

SER 5.20.

Provide a 1-1/2" hose capaht11ty in the outside hydrant hose houses as fo1 Tows:

One 2-1/2* x 1-1/2" x 1-1/2" gated wye with 150' of 1-1/2" hose and 2 adjestable I-I/2" nozzias should be prvvided in each hose house dere it :may be necassary tu extend yard hydrant service into the structure to bacic (gr other systees.

Y Ty yours,

!.E.Hali.