Y' f$
+S
'o,,
UNITED STATES 8
NUCLEAR REGULATORY COMMISSION o
g a
REGION il o
I 101 MARIETTA ST., N.W.. SUITE 3100 4
e ATLANTA. GEORGIA 30303 SEP 171979 In Reply Refer To:
RII:JPO
'.50-437
.~
Offshore Power Systems Attn:
A. R. Collier, President P. O. Box 8000 Jacksonville, Florida 32211 Gentlemen:
The enclosed Information Notice provides information with regard to a potential unreviewed safety question involving high energy lines and control systems.
Sincerely, Ja s P. O'Re y
Director
Enclosures:
- 2. List of IE Information Notices Issued in the Last Six Months 9
e 1131 220 7010110285
t m-D S
oo a
Accession No: 79082201EF SSINS:
6870 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 September 14, 1979 IE Information Notice No. 79-22 QUALIFICATION OF CONTROL SYSTEMS Public Service Electric and Gas Company notified the NRC of a potential unreviewed safety question at their Salem Unit 1 facility. This notification was based on a coatinuing review by Westinghouse of the environmental qualifications of equipment that they supply for nuclear steam supply systems. Based on the present status of this effort, Westinghouse has informed their customers that the performance of non-safety grade equipment subjected to an adverse environment could impact the protective functions performed by safety grade equipment. These non-safety grade systems include:
Steam generator power operated relief valve control system Pressurizer power operated relief valve control system Main Zeedwater control system Automatic rod control system These systems could potentially malfunction due to a high energy line break inside or outside of containment. NRC is also concerned that the adverse environment could also give erroneous information to the plant operators.
Westinghouse states that the consequences of such an event could possibly be more limiting than results presented in Safety Analysis Reports, however, Westinghouse also states that the severity of the results can be limited by operator actions together with operating characterisitics of the safety systems. Further, Westinghouse has recommended to their customers that they review their systems to determine whether any unreviewed safety questions exist.
This Information Notice is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.
If NRC evaluations.so indicate, further licensee actions may be requested or required. If you have questions regarding this matter, please contact the Director of the ap;
' - " ^ " ' - -
No written response to this Informati.
DUPLICATE DOCUMENT Entire document previously entered into system under:
ANo M0722.olzif No. of pages: