ML19209A712

From kanterella
Jump to navigation Jump to search
Notification of 790921 Meeting in Bethesda,Md to Discuss Current Rulemaking Effort for Fire Protection Regulations. Position on Util Fire Review Encl
ML19209A712
Person / Time
Site: Calvert Cliffs  
Issue date: 09/20/1979
From: Sylvester E
Office of Nuclear Reactor Regulation
To: Long C, Matthews P, Notley D
Office of Nuclear Reactor Regulation, NRC OFFICE OF STANDARDS DEVELOPMENT
References
NUDOCS 7910050263
Download: ML19209A712 (4)


Text

.

f[

I%,

UNITED STATES

(

)

g NUCLEAR REGULATORY COMMISSION g

C WASHINGTON, D. C. 20555 September 20, 1979 MEMORANDUM FOR:

D. Notley, Engineering Metho'dology Branch, DES /0SD P. Matthex, Auxiliary Systems Branch, DSS C. f.ong, Technical A3sistant, DSS

~

G. Harrison, Auxiliary Systems Branch, DSS M. Williams, Technical Assistant, DPM T. Wambach, Operating Reactors Branch #2, D0R FROM:

E. Sylvester, Plant Systems Branch, D0R

SUBJECT:

FIRE PROTECTION REVIEW GROUP MEETING A meeting of the Fire Protection Review Group has been scheduled for Friday, September 21, 1979 at 9:00 a.m. in 6110 MNBB. The purpose of this meeting is to.obtain clarification of the intent and/or basis for certain requirements of Appendix A to Branch Technical Position 9.5-1 and tc discuss the current rulemaking effort for fire protection regulations.

The enclosure provides three staff positions from the Calvert Cliffs 1/2 fire review. The licensee may appeal these positions following a meeting scheduled for October 2,1979. Clarification of the basis and/or intent of the Appendix A guidelines from which these positions are derived is desired prior to the licensee meeting. The specific subjects for review group discussion are:

1.

Halon System Backuo Power Section E.1.(d) of Appendix t. requires that fire suppression actuation systems be connected to the plant emergency pcwer supply. The basis for this requirement should be clarified. Halon systems protecting safety-related rooms and electrical cabinets are usually contained completely within the protected space. A fire in the space could damage cables that supply emergency power to the Halon system actuation devices. The acceptability of individual batteries as a source of backup power to Halon systems should be discussed.

I106 077 7910050 2 @

Multiple Addressees September 20, 1979 2.

Emergent. Lighting Section D.5.(a) of Appendix A requires fixed emergency lighting units having individual 8-hour battery power supplies. The basis for the 8-hour minimum battery capability is not clear and the acceptability of a lower rating and the use of portable units should be discussed.

3.

Fire Pumo Separation Section E.2.(c) of Appendix A does not clearly specify the requirements for separation between redundant fire pumps. This section requires that fire pumps be separated from the " remaining pumps" by three hour barriers while Regulatory Guide 1.120, in Section 5.b.(3), specifically requires that fire pumps be separated from the " remaining fire pumps" by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> barriers. The DOR review teams have required fire protection for redundant fire pumps to preclude damage to both pumps from a single fire. However, because of the ambiguities in the Appendix A guidelines, 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> barriers have not always been required between redundant pumps. The intent of the Appendix A guide'ines should be clarified.

A Ernest D. Sylvester Plant Systems Branch Division of Operating Reactors

Enclosure:

Staff Positions - Calvert Cliffs 1/2 Fire Review cc w/ enclosure:

D. Eisenhut B. Grimes G. Lainas V. Benaraya R. Ferguson T. Lee P. Tam, ACRS G. Cunningham, OELD 1106 0/8

ENCLOSURE STAFF POSITIONS CALVERT CLIFFS 1/2 FIRE REVIEW 3.3.14 Halon System Ba6kup Power

~

Staff Position:

Automatic Halon suppression systems should be provided with backup onsite power.

Basis:

Halon systems are provided in (a) the computer room and (b) relay cabinets in cable spreading rooms. The Halon suppression systems are powered by the 125-volt AC system that is not backed up by emergency AC power.

The NRC guidelines (A-31) states that the Halon system should, as a minimum comply with the requirements of NFPA 12A; NFPA 12A requires capability for emergency manual operation.

The subject systems require electric power for automatic or manual operation; therefore, the systems as presently designed do not detect or suppress fires when off-site power is not available.

The NRC guidelines (A-23) state that fire detection and actuation systems should be connected to the plant emergency power supply. The NRR Fire Protection Review Group has indicated that this is a minimum requirement to comply with GDC 3.

3.3.25 Emergency Lighting Staff Position:

Fixed, sealed beam emergency lighting units with battery power rated at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> should be provided in safety-related areas and their access to facilitate fire fighting and energency operation of equipment.

Basis:

The NRC guideline (A-22) states that suitable fixed and portable emergency lighting should be provided to facilitate safe shutdown and emergency responses in the event of fire. The guideline further provides that fixed emergency lighting should consist of sealed beam units with individual 8-hour minimum battery power supplies.

I106 079

. Besides the control room which has a fixed emergency lighting system supplied by station batteries, there are fixed emergency lighting units in many plant areas. However, the battery power rating for these lighting units are only 1-1/2 hours. Moreover, the licensee has not verified that the distribution of existing lighting units provides adequate lighting for safe shutdown and emergency responses.

The NRR Fire Protection Re';iew Group has indicated that this is a minimum requirement to comply with GDC 3.

3.3.48 Fire Pumo Separation Staff Position:

A three-hour rated fire barrier should be provided to separate refundant fire water pumps +.o assure the availability of at least one fire water pump during the fire emergency.

Basis:

The NRC guidelines (A-25) state that the redundant fire pumps and drivers should be separated from each other and from other plant areas by a minimum 3-hour fire wall.

The Calvert Cliffs fire pumps (one electric and one diesel) are located in the same room together with the diesel oil day tank. The room is protected by an automatic sprinkler system. Fire water to this sprinkler can be provided by the 10,000 gallon pressure tank in case the pumps are not operable. However, when coupled with a possible fire water demand at other plant area the content of this pressure tank may only supply fire water for 3-5 minutes.

The NRC guidelines (A-2) state that a single failure in the fire suppression system should not impair both the primary and backup fire suppression capability.

One failure mode of the diesel fire pump could lead to a fira with a zone of influence that affects the electric fire pump.

The licensee has not demonstrated that the installed sprinkler system provides equivalent protection to the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barrier in limiting the effects of such a fire on the electric pump.

1106 080