ML19208D451

From kanterella
Jump to navigation Jump to search
Forwards LERs 79-058/03X-1,79-076/03L-0 & 79-077/03L-0
Date released: 08/10/2019 Download: ML19208D451


LER 79-077/03L-0:on 790826,safety Injection Tank 2T2D Level Could Not Be Maintained Above 80.1% Due to Makeup Valve 2CV-5064 Failing to Open on Command.Caused by Improper Spring Tension on Valve Operator Gate.Tension Adjusted
ML19208D464
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/20/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19208D464 (1)
LER 79-076/03L-0:on 790821,control Room Emergency Air Conditioning Unit 2VE1B Failed to Start.Caused by Crankcase Oil Leak.Leak Repaired,Oil & Freon Added
ML19208D461
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/20/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19208D461 (1)
LER 79-058/03X-1:on 790724,as Result of Analysis of Seismic Category I Pipe Supports,Nine Restraints Were Identified as Having Safety Factor of Less than Two.As Result,Reactor Bldg Sump Drain Declared Inoperable
ML19208D453
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/20/1979
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19208D453 (1)
Forwards LERs 79-058/03X-1,79-076/03L-0 & 79-077/03L-0
ML19208D450
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/20/1979
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: SEYFRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19208D450 (1)