ML19208C826

From kanterella
Jump to navigation Jump to search
Forwards LERs 79-110/01T-0 & 79-111/01T-0
Date released: 08/10/2019 Download: ML19208C826


LER 79-11/01T-0:on 790912,quench Spray Pumps Were Secured Prior to Pumping Required Amount of Water Into Containment as Specified in Fsar.Caused by Inaccurate Emergency Procedure for Loca.Pumps Secured
ML19208C836
Person / Time
Site: North Anna Dominion icon.png
Issue date: 09/24/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19208C836 (2)
LER 79-110/01T-0:on 790910,noted Ambient Temp Gauges Could Affect Capability of Diesel Generator Fan Cooling Sys So That Insufficient Cooling Would Be Provided.Caused by Improper Pitch Setting on Fan Blade
ML19208C833
Person / Time
Site: North Anna Dominion icon.png
Issue date: 09/24/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19208C833 (2)
Forwards LERs 79-110/01T-0 & 79-111/01T-0
ML19208C825
Person / Time
Site: North Anna Dominion icon.png
Issue date: 09/24/1979
From: Stallings C
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References