Text
.
g Appendix A NOTICE OF VIOLATION Consumers Power Company Docket No. 50-329 Docket No. 50-330 B aed on the investigation conducted June 12-14, and July 3, 1979, it appears that certain of your activities were in noncompliance with NRC requirements, as noted below. This item is considered an infraction.
10 CFR 50, Appendi:. B at Criteria V, states, in part:
" Activities affecting quality shall be prescribed by documented instructions, procedures or drawings, of a type appr>priate to the circumstances and shall be accomplished in accordanca with these instructions, procedures, or drawings..."
The Bechtel Power Corporation, General Purging Specification, GPS-1,
" Internal Gas Purging", at drawing number GPS-1-4 (Revised), which is entitled " Water Soluble Paper or Film Dams", states, in part:
" Wadding of the paper or film into the pipe is prohibited."
Contrary to the above, a review of records and interviews with personnel showed that on or about May 11, 1979, Field Weld Number 13, which joins 8-inch pipe runs 2G-CB-15-613-11 and 2G-CB-15-613-12, was made using a purge dam which consisted of a ball of wadded, soluble paper. This weld was made in the Unit 2, Reactor Building Spray system headers.
O D
O o6
- E
'a T
7 9 0 9 e 7 0 5.33
~
3 "AEA 1042 251