ML19208B386

From kanterella
Jump to navigation Jump to search
Notifies That Typographical Error Has Been Discovered in Attachment 1 to Response to IE Bulletin 79-01 Re Inboard Isolation Valve Actuators.Corrected Page 1 Encl
ML19208B386
Person / Time
Site: Monticello 
Issue date: 08/21/1979
From: Wachter L
NORTHERN STATES POWER CO.
To:
Office of Nuclear Reactor Regulation
References
NUDOCS 7909200134
Download: ML19208B386 (2)


Text

d NSP NORTHERN STATES POWER COMPANY MIN N E A PO LI S. MIN N E S OTA 55409 August 21, 1979 Director Division of Operating Reactors Office of Nuclear Reactor Regulation Nuclear Regulatory Commfssion Washington, D.C.

20555 MONTICELLO NUCLEAR GENERATING PLANT Docket No. 50-263 License No. DPR-22 A typographical error has been discovered in Attachment 1 to the response to IE Bulletin 79-01.

The entry in the REMARKS column for the third item on page 1 of attachment 1, " Inboard Isolation Valve Actuators", should read " Note #2" rather than " Note #4."

A revised page for the submittal is attached.

This matter was discussed in a telephone conversation with Mr. J. Ilughes of the Region III IE Of fice on August 17, 1979.

Yours very truly,

?

GW

,1 '

f5I7 '

1

/

L. J. Wachter Vice President - Power Production and System Operation cc:

Mr. G. Charnof f M James G. Keppler Enclosure p j [,,

AJG 2319/s 09 sob 39

Qualification Data for Safety Related Electrical Equipment Required to Function in an Accident Environment COMPONENT ACCIDENT QUALIFICATION QUALIFICATION QUALIFICATION DESCRIPTION ENVIRONMENT ENVIRONMENT METHOD DOCUMENT REMARKS MSIV Solenoid. Valves Note #1 345*F, 110 psig Test / Analysis Rockwell Report #2792-Note #2 (Automatic Valve' Cb.

03-02, Rev. 1.

Model No. C-4988-15) 340*F,765 psig, Sequential GE Plant Equipment SRV Solenoid Valves Note #1 3 x 10 Rads Test Design Memo #126-62.

(Automatic Valve Co.

Model No. C-5450)

Inboard Isolation Note #1 329'F, 90 psig Test / Analysis Franklin Institute Note #2 Report #F-C2232-01 Valve Actuators (Limitorque Type SFB)

Inboard Reactor Water Note #1 Note #3 Analysis SRI #168 Note #3 Sample Isolation Valve Soleno,id Valve (Asco Model No. THT-8317A23)

Recire Pump Dis-Note #1 210*F, 7" W.G.

Test / Analysis Franklin Institute Note #4 Report #F-C3271 charge valve Actuators (Limi-torque Type SMB)

Containment Electrical Note #1 340*F,756 psig, Sequential Letter, G.G. Sherwood Penetrations (General 4 x 10 Rads Test (GE) to USNRC, dated 12/2/77 and "Qualifi-Electric Type NS0-2, cation Report for F01 NSO-3, NSO-4)

Electrical Penetration Assembly" w

Control Cables (inside Note #1 340*F,762 psig, Sequential Wyle Labs Reports 4 x 10 Rads Test 44114-1 and 44114-2.

containment) (General Electric SI-58109)

{

,,a va s

O