\\a.

,p" "8cg

[!

j NUCLEAR REGULATORY COMMISSION 0,

UNITED STATES c y3 3.p

. p WASHINGTON, O. C 20555 1,' ~.[,[/

JUL 2 01979 MEMORANDUM FOR:

D. Ziemann, Chief, Cperating Reactors Branch #2, Division of Operating Reactors FROM:

G. Lainas, Chief, Plant Systems Branch, Division of Operating Reactors

SUBJECT:

LACROSSE, REQUEST FOR ADDITIONAL INFORMATION FOR DEGRADED GRID VOLTAGE (TAC 10031)

Plant Name: Lacrosse Boiling Water Reactor Docket No.: 50-409 Responsible Branch: ORB f2 Project Manager:

J. Shea Reviewing Branch: Plant Systems Branch Status: Awaiting Information In response to technical assistance request TAC 10031, the Plant Systems Branch has reviewed the licensee's submittal of July 22, 1977 and found that additional information is required in order to complete our review.

The attached request for additional infonnation should be forwarded to the licensee as soon as possible with a request for response within 45 days.

m O

G. Lainas, Chief Plant Systems Branch Division of Operating Reactors

Contact:

S. Rhow, X28077 C. Cleveland, EG&G

Enclosure:

As stated 786104 i

2 9 o s e s o 17 i

L

/

~ s

.~

x.

.. cc w/ enclosure:

D. Eisenhut R. Vollmer

'd. Russell B. Grimes J. Shea G. Lainas D. Tondi M. Chiramal P. Shemanski S. Rhow C. Cleveland 76atC5

~

REQUEST FOR ADDITIONAL INFORMATION LACROSSE BOILING WATER REACTOR DEGRADED GRID '/0LTAGE (TAC 10031)

Based upon our review of your subnittal dated July 22, 1977 we have concluded that the use of the existing undervoltage relaying to protect against a sustained degraded grid condition is not acceptable. Hence, we require that you provide your proposed design modification ad changes in the Technical Specification based on the guidance contained in the staff positions submitted to. you by our letter dated June 3,1977.

76oiC6