ML19165A103

From kanterella
Jump to navigation Jump to search
NRR E-mail Capture - Draft RAI for STP TS 3.8.1.1 Sbdg SR Change
ML19165A103
Person / Time
Site: South Texas  
Issue date: 06/14/2019
From: Ed Miller
Special Projects and Process Branch
To: Brost W, Richards D
South Texas
References
Download: ML19165A103 (2)


Text

1 NRR-DRMAPEm Resource From:

Miller, Ed Sent:

Friday, June 14, 2019 9:54 AM To:

Richards, Drew; Brost, Wendy

Subject:

Draft RAI for STP TS 3.8.1.1 SBDG SR Change L-2018-LLA-0078 Drew & Wendy, Provided below is the NRC staffs draft RAI for the subject license amendment request. The question is being transmitted to you to determine 1) If the question clearly conveys the NRC informational needs, 2) Whether the regulatory basis for the question is clear, and 3) If the information has already been provided in existing docketed correspondence. Additionally, review of the draft question will allow you to determine whether you are able to support a 30 day response time. After youve had a chance to review the draft information request, please contact me to set up a conference call, if needed. Thank you.

Ed Miller (301) 415-2481 Draft Request for Additional Information:

In the submittal dated March 27, 2018, information is provided regarding the frequency results of selected EDG surveillance runs. In the supplement dated December 6, 2018 voltage results are provided for a different selection of EDG surveillance runs. Please confirm that for all fast-start surveillance runs in the last 3 years in which measurements were taken by digital recorders, the results demonstrated that the EDGs frequency and voltage were within the limits proposed in TS SR 4.8.1.1.2.5. For any instances where the parameters were not within TS limits, please provide a discussion with a focus on how the STI remains appropriate given the failure to meet the proposed parameters.

Hearing Identifier:

NRR_DRMA Email Number:

50 Mail Envelope Properties (BN7PR09MB2755B3ED8DCAAD614B12A091E9EE0)

Subject:

Draft RAI for STP TS 3.8.1.1 SBDG SR Change Sent Date:

6/14/2019 9:54:27 AM Received Date:

6/14/2019 9:54:00 AM From:

Miller, Ed Created By:

Ed.Miller@nrc.gov Recipients:

"Richards, Drew" <amrichards@STPEGS.COM>

Tracking Status: None "Brost, Wendy" <webrost@STPEGS.COM>

Tracking Status: None Post Office:

BN7PR09MB2755.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 1455 6/14/2019 9:54:00 AM Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received: