Curtiss-Wright Nuclear Division - Notification Report for Potential Part 21 Update
ML19158A130
Person / Time
Site: Quad Cities  
Issue date: 05/31/2019
From: Hover M
Curtiss-Wright Corp
To: Hoc H
Office of Nuclear Reactor Regulation
References
Download: ML19158A130 (5)


Text

From:

To:

Cc:

Subject:

Date:

Attachments:

Dear Customer,

Hover. Margie Hoc HOO X Hover. Margie

[Extemal_Sender] Curtiss-Wright Transmittal DT193199 (PO# N/A): Response required [#DDDTIHUIHYQE#]

Friday, May 31, 2019 11:06:22 AM Notification Report for Potential Part 21 Update Event ML18289A457 Log No. 2018-24-00.pdf Document Control Workflow Notification Please confirm receipt of attached documentation by replying Yes to this email.

Responding Yes not only confirms your receipt, but also initiates an update of our Submittal/Tracking Transmittal Database.

Thank you.

NOTICE: The documents listed in the DT below will be delivered via attachments to this email.

[J

__ J DOCUMENT TRANSMITTAL Contract N/A

Nuclear Division 4600 East Tech Drive, Cincinnati, OH 45245 T: 513.528.7900 I F:

513.528.4537 Originated By Hover, Margie Name Number DT193199 Originated Date 5/30/2019 Company Customer/Vendor Purchase Order Number N/A Project 10CFR PART 21 REPORT UPDATE Email Headquarters Operation U.S. Nuclear Regulatory hoo.hoc@nrc.gov Officer Commission Document Number Rev Document Type Qty For...

10CFR Part 21 Report N/A Report 1

Final Record

Remarks Contact Information for Originator of Part-21 Notification:

TIM FRANCHUK Curtiss-Wright Nuclear Division Director of Quality (513) 201-2176, tfranchuk@curtisswright.com Notification Report for Potential Part 21 Update:

Namco Limit Switch PIN: EA 700-90964 U.S. Nuclear Regulatory Commission ATTN: NRC Document Control Desk Washington, DC 20555-0001 Phone: (301) 816-5100 Fax: (301) 816-5151 Document Control Use Only Transmitted By Hover, Margie 020-07-91 Rev. 6 Transmitted Date 5/31/2019 ACKNOWLEDGMENT:

Please confirm receipt of the referenced documentation by replying "YES" to the email you received. The referenced documentation will default to a status of UNCONTROLLED if your "YES" reply is not received within 30 days.

For simplicity, EasyResponse is enabled; You can simply reply with a valid outcome such. as yes or no on a line by

_us_e_lf_at-th_e_t_op_o_if_th_e_re-tu_r_n _em_a_il_. __

. ____ _,,f2e,~ W.aoeJ_P-e.,.. k/~f!_,Olle. Q,1,~6tM.

-/- -tu(RtLT-i /:-rqicft1.1ftt_-e);,, C/s(r.017 This e-mail and any files transmitted with it an~i,~ an@! mtended solely for the use of the individual or entity to whom they &re addressed. If you have reason to believe that you have received this e-mail in error, please notify the sender and destroy this e-mail and any attached files. Please note that any views or opinions presented in this e-mail are solely those of the author and do not necessarily represent those of the Curtiss-Wright Corporation or any*

  • of its subsidiaries. Documents attached hereto may contain technology subject to the U.S.

Export Regulations. Recipient is solely responsible for ensuring that any re-export, transfer or disclosure of this information is in accordance with U.S. Export Regulations. The recipient should check this e-mail and any attachments for the presence of viruses. Curtiss-Wright Corporation and its subsid1aries accept no liability for any damage caused by any virus transmitted by this e-mail.

  • CURl1SS-WRIGHT U.S.. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001

Subject:

Notification Report for Potential Part 21 update.

Dear Sir or Madam:

Nuclear Division 4600 East Tech Drive Cincinnati, OH 45245 T: 513.528.7900 IF: 513.528.9292 www.curtisswright.com/NuclearDivision May 31, 2019 In reference to the Curtiss-Wright Interim Notification Report dated 10/8/2018 (Event No. ML18289A457/Log No. 2018-24-00) for an EA700-90964 limit switch failure, the following updates are provided.

Curtiss-Wright was notified on August 7th, 2018 by Exelon's Quad Cities Plan~,that a Curtiss-Wright Supplied*Namco Limit Switch, PIN: EA 700-90964 had failed during a planned maintenance test.

The switch was found to be sluggish in returning to the normal shelf state after actuation, or would not return at all. The switch was identified as Curtiss-Wright Tag# ST34603 and was provided as a safety related component to Exelon in September 2005. According to Exelon, the item was stored for 8 years then failure occurred roughly four and a half years into service. The part has a manufacturer date coded as August 2005.

The switch was subsequently sent to Exelon Powerlabs where a detailed failure evaluation was performed (See QDC-07067). Exelon Powerlabs confirmed the failure mode and determined that there was insufficient lubrication in place to support normal switch function. The switch was then sent to Namco for further evaluation and Namco confirmed the lack of lubrication.

Note that in subsequent discussions after release of the QDC-07067 report, Namco indicated that their statement on the lack of lubrication was an observation of the switch's current condition, and not the cause of the failure.

References (attached):

Exelon Powerlabs Initial Report QDC-07067 08/08/2018 on failed Switch Exelon Powerlabs 2nd Report QDC-62770 Rl 05/09/2019 on used Switches Namco Report Mechanical Cycle Testing, EA700-90964 Commercial Limit Switch (Final Report-28May2019)

Initial Report QDC-07067

Conclusions:

Initial Failure occurred roughly four and a half years in service where switch* "binding was due to insufficient (i.e. dried out) lubrication on the moving parts". The shaft 0-ring was sevijrely hardened.from aging, "which could have contributed to binding".

Second Report QDC-62770:

Per Table 1, pg. 3: SN 05, 09, & 02 were installed for 6 years without a failure.

Pages 16 & 17 photos show these 3 switches are without lubrication and had wear patterns between tile slide & the outer housing, similar to the failed switch.

Per pg. 1: CQ1400801 S/N 03 was installed for approximately 9 months.

Page 17 photo shows significant lubrication and the same wear pattern.

The foreign material found in the switches were identified as paint residue (due to wear).

Page 1 of 2

  • CURTISS-WRIGHT Nuclear Division 4600 East Tech Drive Cincinnati, OH 45245 T: 513.528.7900 IF: 513.528.9292 www.curtisswright.com1Nuclear0ivision Shaft 0-Rings on the 6 years in service switches were severely hardened and embrlttled due to aging, while the 9 month switch's 0-Ring was still in good condition, but beginning to show signs of aging as noted by an increase in hardness.

NAMCO Cycle Aging Report:

Report showed the results of Mechanical Cycle Testing on two new switches, which was performed in the same orientation as the Exelon application. The purpose of this test was to prove that with/without lubrication, at the known rate of cydes, these units would not have experienced the amount of wear indications noted in Exelon Powerlabs' reports r~gardless of the amount of lubrication present. One switch was completely lubricated and one was without any lubrication. These were cycled for 4800 cycles and were both functional at the end of testing.

Curtiss-Wright noted that Namco's testing was done at laboratory ambient conditions, and did not account for other external factors such as typical system vibrations and operating temperature present in Quad Cities application.

CW

Conclusion:

Based upon similar wear patterns, the presence of "significant grease" does not resolve wear pattern issue caused in a shorter period of time, thus the lack of grease can be considered to "not be a significant credible failure mechanism" (same or no grease between shuttle and housing). Based upon the NAMCO report, the presence or lack of grease has no impact on wear or operability and thus does not affect the safety function.

, In addition, the CQ1400801 S/Nj)3 installed for9 months, the 0-Ring measured an 81 durometer hardness (showing aging) but not brittle. The other 3 installed for 6 years were brittle but did not affect operability. Thus the hardness of the 0-Rings can be considered to "not be a significant credible failure mechanism".

All four switches in Report QDC-62770 had paint scrapings caused by wear which was present and operated properly after being in service for an extended period of time. Thus the presence of paint residue due to wear can be considered to "not be a significant credible failure mechanism".

There have been no other reported failures of this type. The root cause failure mechanism has not been identified, thus this switch faihire does not aP. ear to represent a common mode failure.

m Tim Franchuk Director, Quality Assurance Curtiss-Wright Nuclear Division, Cincinnati Operations 513-201-2176 TFranchuk@CurtissWright.com Page 2 of Z