ML19031C723

From kanterella
Jump to navigation Jump to search
Response to IE Bulletin No. 77-03 on On-Line Testing of the Westinghouse (W) Solid State Protection System
ML19031C723
Person / Time
Site: Salem  PSEG icon.png
Issue date: 10/28/1977
From: Schneider F
Public Service Electric & Gas Co
To: Grier B
NRC/IE, NRC Region 1
References
IEB-77-003
Download: ML19031C723 (2)


Text

rederick W. Schneider ce President Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 201/622-7000 oduction October 28, 1977 Mr. Boyce H. Grier, Director U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

NRC IE BULLETIN NO. 77-03 "ON-LINE-TESTING OF THE WESTINGHOUSE (W)-SOLID STATE PROTECTION SYSTEM (SSPS)"

NO. l AND 2 UNITS SALEM NUCLEAR GENERATING STATION In response to your letter of September 12, 1977 transmitting NRC IE Bulletin No. 77-03, we have investigated this matter with respect to applicability. to Salem No. 1 and 2 Uni ts. *

  • The.. following_ summari*zes -the results* *of our investigation.
1. ' The testing provisions for_,_ the-Salem-SSRS--d-id not-include~

testing-;e:f*:the reset *.tirrii-ng circuitry. __.

2.

To -assure _periodicc tes.ting **of-~.the--safety.:i,.-nj ection reset timing* -circuit, Performance *Depar_tment Procedure Number PD-18.1.001;-*"sSPS Periodic Test", ha_s been revised to*

incorporate the scheme-specified by the W~stinghouse Technical Bulletin NSD-TB-77-11.

3.

The above action applies to Salem No. 1 and 2 Units.

/

Mr. B.H. Grier 2 -

.. I 10 77 If you require additional information, we will be pleased to discuss it with you.

~

truly yours,