a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
/1111 Test Date: _1_12-'0/_20_1_4 ____ -'-'1/?t{tq Reviewed By: Allen Cottingham
~
Review Date: 1/27/2014 1-*>*tll Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (In)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
As-Tested Unit Weight, (pcf)
Loading Rate (lb/sec)
Test Duration to Failure, (min)_
Uniaxial Compressive Strength, (psi)
Type of Break Young's Modulus, (psi)
Poisson's Ratio
- 10,000 I
- 9,000
- 8,000
-7,000
- 6,000
\\
\\
I
\\
.e:
vi
- 5,000 l=
Ill
'ii
-4,000
~
I I
l I
- 3,000
- 2,000
-1,000 I
/
l /
- l.
l(
Sample No.: L7-3 BH Boring No.: MP-203 Run. No.: N/A Sample Depth {ft): 121.7-122.7 Page 1 of 2 (See boring log)
Laboratory Air-Dry 2.40 5.39 2.2 Noltl 46&.7-I ~3 l}d_ ~
130 v
6.7 9,190 Complete Break 2,620,000 0.14
/
/
/~
1/
./
I
-- Average Adjusted Axial 1-Strain (in/in)
I
--i -- Average Adjusted I
L~ teral Strain (infon)
I 0
0.0020 0.0010 0.0000
.0.0010
-0.0020 Axial Strain [ -J, (lnnn)
- 0.0030 Lateral Strain [+), (In/in)
Comments:
Young's Modulus and Poisson's Ratio determined using linear teast-sguares of stress-strain data from 40% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical
<*I Specimen did not meet End Perpendicularity and End Flatness requirements of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-40 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
~~~
Test Date: 1/20/2014 J h1pL(
Reviewed By: Allen Cottingham
- r (fli':rt:
Review Date: 1/27/2014 1-1 IY
~~~~----------
Comments:
Specimen Prior to Testing
("MP-203 l7-3 BH before testjpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-41 of 91 Sample No.: L7-3 BH Boring No.: MP-203 Run. No.: N/A Sample Depth (ft): 121.7-122.7 Page 2 of 2 Specimen After Testing
("MP-203 L7-3 BH after test.jpg"):
(\\:od) ~:vrr G,q~g-f~-/0~
Mf-~03 Ll- ~- B,H 1~1.7'- ~~-7'
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton Test Date: 1/27/2014 Reviewed By: Allen Cottingham Review Date:...:1.:.;/3:..:0::../2::c0:...1c..:4'-------
Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (in)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
As-Tested Unit Weight, (pcf)
Loading Rate {lb/sec)
Test Duration to Failure, (min)
Uniaxial Compressive Strength, (psi)
Type of Break Young's Modulus, (psi)
Poisson's Ratio
-7,000
-6,000 I
\\ \\
I
-5,000
-4,000
'i Eo I
Sample No.: L3-32 BH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft): 72.7-73.5 Page 1 of 2 (See boring log)
Laboratorv Air-Drv 1.77 3.96 2.2 No 111
~ ({..1 (/tJ-90 7
5.3 6,890 Columnar/Complete Break 2,370,000 0.09 7
7
/
~
-3,000
~
-2,000 7 '
I 1/
l
-1,000 --
0 0.0020 Comments:
I I
0.0010 0.0000 Lateral Strain [ + ), (In/In)
~
I I
-0.0010 I
! --*~" ""'"' "'"'j Strain (in/in)
[--Average Adjusted Lateral Strain (in/in) r
-0.0020 Axial Strain ( - ], (lnlln)
-0.0030 Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 40% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical ill Specimen did not meet Side Straightness requirements of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-42 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton m1f Test Date: 1/27/2014 tf31{1Lf Reviewed By: Allen Cottingham 11'\\At Review Date: --'1;,:/3'-'0"-'/2'-'0--'1--'4 _______ l-1\\*1"\\
Comments:
Specimen Prior to Testing
("MP-205 L3-32-BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.243 of 91 Sample No.: L3-32 BH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft): 72.7-73.5 Page 2 of 2 Specimen After Testing
("MP-205 L3-32-BH after test (2).jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton IJtiJ Test Date: -..:1:..::/2:.:;6/:..::2.:..01:...c4:...._ ___
_l/~
h1/M Reviewed By: Allen Cottingham
~\\()((..
Review Date: 1/30/2014 1-1H~
Rock Type Moisture Condition Specimen Diameter, (in}
Specimen Length, (in)
Length/Diameter Ratio Sample No.: L3*36 BCH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft}: 162.6-163.4 Page 1 of 2 (See boring log}
Laboratory Air-Dry 1.76 3.86 2.2 Specimen Conforms with Dimensional Requirements?
No 111 As-Tested Unit Weight, (pcf}
1-6&:4-c tD8 AD :t Loading Rate (lb/sec}
90
{/
Test Duration to Failure, (min) 4 Uniaxial Compressive Strength, (psi) 7,130 Type of Break Columnar (Slight Shear}
Young's Modulus, (psi}
4,650,000 Poisson's Ratio 0.20
-8.000
- 7,000
- 6.000
- 5.000
.. s..
-4,000
.b
~
-3,000
-2,000
-1,000 I
I
~
\\ I Ll I
---r i v t
I I
I I
I I
I I
--Average Adjusted Axial Strain {infln) 1-
/
I
~ - Ave rageAdjus ted J Lateral Strain {infln) 0 0.0020 0.0010 0.0000
-0.0010
-0.0020 Axial Strain[ *], (In/In]
-0.0030 Lateral Strain I+J, (In/In]
Comments:
Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 40% to 60%
or the uniaxial compressive strength {data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is posilive.
Load direction wilh respect to lithology: Vertical PI Specimen did not meet End Flatness requirements of ASTM 0 4543-08. Authorization to proceed with tesl received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-44 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton mif Test Date:...:1:..::/2:..:.6/:..::2:..:.01.:...4:.__ ___ ---'14-bqt/!.!
Reviewed By: Allen Cottingham 1"\\M Review Date: 1/30/2014 l *"">b**~
Comments:
Specimen Prior to Testing
("MP-205 L3-36 BCH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-45 of 91 Sample No.: L3-36 BCH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft): 162.6-163.4 Page 2 of 2 Specimen After Testing
("MP-205 L3-36 BCH after test.jpg"):
a me El astic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton llt-11 Test Date: 1/26/2014 1/1lf~
Reviewed By: Allen Cottingham
,n11<
Review Date: 1/30/2014 1*~1.1~
Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (in)
Length/Diameter Ratio Sample No.: L3-37 BH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft): 208.5-209.0 Page 1 of 2 (See boring log)
Laboratory Air-Dry 1.75 4.10 2.3 Specimen Conforms with Dimensional Requirements?
No 111 As-Tested Unit Weight, (pcf)
-%&.+ '"2'; 1M, Loading Rate (lb/sec) 90 1/
Test Duration to Failure, (min) 6.7 Uniaxial Compressive Strength, (psi) 15,310 Type of Break Shear with Columnar Young's Modulus, (psi) 9,530,000 Poisson's Ratio 0.28
-16.000,.....---------------:--------:----------------.,
-14,000 1-------+-----1---+-------+----/-----t---
- 12,000
-4,000 1--------\\------
-2,000 1-------+-------~-~-J'-------+---------; +--I
--Average Adjusted Axial Strain (in/in)
--Average Adjusted Lateral Strain (In/in) o L-----------------~--------------~~======~
0.0020 0.0010 Lateral Strain ( + ], (lnlln)
Comments:
0.0000
- 0.0010
-0.0020 Axial Strain ( *], (In/In)
-0.0030 Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 35% to 55%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical PI Specimen did not meet End Flatness requirements of ASTM D4543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-46 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
!>>If Test Date:..:.1:..::/2:.::.6/:..::2:.::.01.:...4:.__ ____
!../..//..qJI//I{
Reviewed By: Allen Cottingham (ffrt.
Review Date: 1/30/2014 I J7t>
- f~
Comments:
Specimen Prior to Testing
("MP-205 L3-37 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-47 of 91 Sample No.: L3-37 BH Boring No.: MP-205 Run. No.: N/A Sample Depth (ft): 208.5-209.0 Page 2 of 2 Specimen After Testing
("MP-205 L3-37 BH after test.jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton Tfl,{t Test Date: _1_/2_0/_2_01_4 ____ ----'-PI/31/Ilf Reviewed By: Allen Cottingham 1"4t Review Date: 1/27/2014 1-)-lll Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (in)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
Sample No.: L7-6 BH Boring No.: MP-207 Run. No.: N/A Sample Depth (ft): 70.7-71.7 Page 1 of 2 (See boring log)
Laboratory Air-Dry 2.36 5.34 2.3 Not*t As-Tested Unit Weight, (pcf)
~
I '-1 /JeJ- ~-
Loading Rate (lb/sec) 130 v
Test Duration to Failure, (min) 4.7 Uniaxial Compressive Strength, (psi) 5,970 Type of Break Columnar with slight shear Young's Modulus, (psi) 4,040,000 Poisson's Ratio 0.18
-4,000
-3,500
-3,000
-2,500
-;;.e,
-2,000 b
~
-1,500
-1,000 I
I I
I I
I
/_
I I
I I
I I I
~*-
t--
I I
--Average Adjusted Axial !
I Strain (In/In)
-500 ------
0 0.0020 Comments:
I 0 0010 Latorol Stroln ( * ), (lnnn)
I 0.0000
.{).0010
-- Average Adjusted Lateral Strain (infln)
.{).0020 Axial Strain ( - ), (In/In)
Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 40% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Laleral Strain is positive.
Load direction with respect to lithology: Vertical 1'1 Specimen did not meet End Perpendicularity and end natness requirements of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-48 of 91 r-
-0.0030
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
~ #
Test Date: 1/20/2014 If~'/ lq Reviewed By: Allen Cottingham f<'~
Review Date: 1127/2014
\\ - <../ -H Comments:
Specimen Prior to Testing
("MP-207 L7-6 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.249 of 91 Sample No.: L7-6 BH Boring No.: MP-207 Run. No.: N/A Sample Depth (ft): 70.7-71.7 Page 2 of 2 Specimen After Testing
("MP-207 L7-6 BH after test.jpg"):