ML18347A657

From kanterella
Jump to navigation Jump to search
5/4/1976 Letter, Providing Information Relating to Testing of Iodine Adsorbers (Activated Charcoal), as Requested
ML18347A657
Person / Time
Site: Palisades 
Issue date: 06/18/1976
From: Bixel D
Consumers Power Co
To: Schwencer A
Office of Nuclear Reactor Regulation
References
Download: ML18347A657 (1)


Text

(~uJatq_rj' consumers Power company General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201

  • Area Code 517 788-0550 June 18, 1976 Director of Nuclear Reactor RegUlation Att:

Mr Albert Schwencer, Chief Operating Reactor Branch No 1 US Nuclear RegUlatory Commission Washington, DC 20555 DOCKET 50-255, LICENSE DPR PALISADES PLANT, IODINE ADSORBER PERFORMAN' Your letter dated May 4, 1976 req_uested information relating to iodine adsorbers (activated charcoal).

The' followi,ng is our response information req_uested:

1.

Two samples of cb'.arcoal were obtained on May 26, 1976 by removing canisters from the' system.

2.

The charcoal had been* installed* in the system for 153 days and the system was in operation for 117 days.*

3.

The laboratory that performed the radioactive test was Nuclear Containment Systems., Inc, Columbus,* Ohio.

We U.nder&tand that they used the services of Environment al Engineering and Testing, Richland, W ashiilgt on *

4.

The testing agent was methyl iodide.

5.

The* test* was performed using RDT M16.;..1T

  • procedures. and the followi.ng condi-tions:*

Temperature 25°C Pressure

- Ambient Relative Kumidi.ty. -

70%

Linear Flow Rate * - ll.;..13 Meters/M:j.nute

6.

Two canisters were tested.

The removal efficiency obtained was a13 follows:

Sample 645 - 98. 46%

Sample 646. - 99... 09~&'

7.

There were no operating conditions w:hich. we considered unusual.*

Assistant Nuclear Licensing Administrator CC:

JGKeppler, USNRC