L-18-244, Response to Request for Additional Information Related to 10 CFR 50.55a Request PR-2
| ML18290A461 | |
| Person / Time | |
|---|---|
| Site: | Perry (NPF-058) |
| Issue date: | 10/16/2018 |
| From: | Hamilton D FirstEnergy Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| EPID L-2018-LLR-0093, L-18-244 | |
| Download: ML18290A461 (3) | |
Text
~
FirstEnergy Nuclear Operating Company David B. Hamilton Vice President October 16, 2018 L-18-244 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Perry Nuclear Power Plant Docket No. 50-440, License No. NPF-58 Perry Nuclear Power Plant PO Box 97 10 Center Road Perry, Ohio 44081 440-280-5382 10 CFR 50.55a Response to Request for Additional Information Related to 10 CFR 50.55a Request PR-2 (EPID L-2018-LLR-0093)
By correspondence dated June 21, 2018 (Accession No. ML18172A068), FirstEnergy Nuclear Operating Company (FENOC) requested five separate alternatives to certain requirements associated with the fourth ten-year in-service testing program interval for the Perry Nuclear Power Plant.
By electronic mail dated October 2, 2018, the Nuclear Regulatory Commission (NRC) provided a request for additional information (RAI) to complete its review of alternative request PR-2. FENOC's response to the RAI is provided in Attachment 1.
There are no regulatory commitments contained in this submittal. If there are any questions or if additional information is required, please contact Mr. Phil H. Lashley, Acting Manager - FENOC Nuclear Licensing & Regulatory Affairs, at (330) 315-6808.
Sincerely, David B. Hamilton : Response to October 2, 2018 Request for Additional Information
Perry Nuclear Power Plant L-18-244 Page 2 of 2 cc:
NRC Region Ill Administrator NRC Resident Inspector NRC Project Manager Branch Chief, Ohio Emergency Management Agency, State of Ohio (NRC Liaison)
Utility Radiological Safety Board L-18-244 Response to October 2, 2018 Request for Additional Information Page 1 of 1 The Nuclear Regulatory Commission's request for additional information is provided in bold type below, followed by the FENOC response.
RAI 1
Clarify whether the Group A test Required Action Range high values will be changed from >1.10 times reference value to >1.06 times reference value to satisfy the condition in RG [Regulatory Guide] 1.192, Revision 2, or provide justification for not adjusting the Required Action Range high values.
Response
The Group A test Required Action Range high values will remain at >1.06 times the reference value to satisfy the condition in RG 1.192, Revision 2 in the transition from the third 10-Year In-Service Testing interval to the fourth 10-Year In-Service Testing interval.