10 CFR 50.46 Annual Report
ML18222A253
Person / Time
Site: Peach Bottom  
(DPR-044, DPR-056)
Issue date: 08/10/2018
From: David Gudger
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML18222A253 (9)


Text

200 Exelon Way Exelon Generation ~

Kennett Square. PA 19348 August 10, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 www.exeloncorp com Peach Bottom Atomic Power Station, Units 2 and 3 Renewed Facility Operating License Nos. DPR-44 and DPR-56 NRG Docket Nos. 50-277 and 50-278

Subject:

1 O CFR 50.46 Annual Report 10 CFR 50.46

Reference:

Letter from David T. Gudger (Exelon Generation Company, LLC) to the U.S.

Nuclear Regulatory Commission, "10 CFR 50.46 Annual Report," dated August 1 O, 2017 The purpose of this letter is to transmit the 1 O CFR 50.46 reporting information for Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3. The previous 50.46 report for PBAPS, Units 2 and 3, (Reference) provided the cumulative Peak Cladding Temperature (PCT) errors for the most recent fuel designs through August 10, 2017.

No new 10 CFR 50.46 notifications were received from the fuel vendor since the last 2017 annual report (Reference) submitted to NRG. Therefore, the total PCT value of 1925°F reported in the last annual report (Reference) is unchanged for this report.

There are no regulatory commitments in this letter.

U.S. NRG Regulatory Commission Peach Bottom Atomic Power Station, Units 2 and 3 10 CFR 50.46 Report August 10, 2018 Page 2 If you have any questions concerning this letter, please contact Richard Gropp at 610-765-5557.

Respectfully, 1'1~:J I..4---Jri---

David T. Gudger Manager, Licensing and Regulatory Affairs Exelon Generation Company, LLC Attachments:

1. Peach Bottom Unit 2 I SAFER/PRIME I GNF2 Fuel 10 CFR 50.46 Report
2. Peach Bottom Unit 3 I SAFER/PRIME I GNF2 Fuel 10 CFR 50.46 Report
3. Assessment Notes cc:

w/ Attachments USNRC Region I, Regional Administrator USNRC Senior Resident Inspector, PBAPS USNRC Project Manager, PBAPS R. R. Janati, Pennsylvania Bureau of Radiation Protection D. A. Tancabel, State of Maryland

ATTACHMENT 1 Peach Bottom Unit 2 I SAFER/PRIME I GNF2 Fuel 10 CFR 50.46 Report

Peach Bottom Unit 2 I SAFER/PRIME I GNF2 Fuel 10 CFR 50.46 Report PLANT NAME:

ECCS EVALUATION MODEL:

EVALUATION MODEL VENDOR:

REPORT REVISION DATE:

CURRENT OPERATING CYCLE:

Peach Bottom Unit 2 SAFER/PRIME GNF/GEH August 10, 2018 22 ANALYSIS OF RECORD CALCULATIONS Page 1of1

1. Project Task Report, Exelon Generation Company LLC, Peach Bottom Atomic Power Station, Units 2 & 3 MELLLA+ Task T0407: ECCS-LOCA Performance, 0000-0162-2354-RO, Revision 0, (PLM OOON0296 Revision 0), December 2013.

Fuels Analyzed in Calculations and in Operation:

Limiting Fuel Type:

Limiting Single Failure:

Limiting Break Location:

Limiting Break Size:

Reference Peak Cladding Temperature (PCT) for GNF2 Fuel:

MARGIN ALLOCATION A. PRIOR LOCA ASSESSMENTS (Note 1 ):

1 O CFR 50.46 Report dated August 15, 2014 (Note 1.1) 1 O CFR 50.46 Report dated August 1 O, 2016 (Note 1.2) 1 O CFR 50.46 Report dated August 1 o, 2017 (Note 1.3)

Net PCT B. CURRENT LOCA ASSESSMENTS (Note 2):

Total PCT Change from Current Assessments (Note 2)

Cumulative PCT Change from Current Assessments Net PCT GNF2 GNF2 Battery Failure Recirculation Discharge Line 0.05 ft2 (Small Break) 1920° F GNF2: ~PCT= +5°F GNF2: ~PCT= 0°F GNF2: ~PCT= 0°F GNF2: 1925°F GNF2: I~PCT = 0°F GNF2: Il~PCTI = 0°F GNF2: 1925°F

ATTACHMENT 2 Peach Bottom Unit 3 I SAFER/PRIME I GNF2 Fuel 10 CFR 50.46 Report

Peach Bottom Unit 3 I SAFER/PRIME I GNF2 Fuel 1 O CFR 50.46 Report PLANT NAME:

ECCS EVALUATION MODEL:

EVALUATION MODEL VENDOR:

REPORT REVISION DATE:

CURRENT OPERATING CYCLE:

Peach Bottom Unit 3 SAFER/PRIME GNF/GEH August10,2018 22 ANALYSIS OF RECORD CALCULATIONS Page 1 of 1

1. Project Task Report, Exelon Generation Company LLC, Peach Bottom Atomic Power Station, Units 2 & 3 MELLLA+ Task T0407: ECCS-LOCA Performance, 0000-0162-2354-RO, Revision 0, (PLM OOON0296 Revision 0), December 2013.

Fuels Analyzed in Calculations and in Operation:

Limiting Fuel Type:

Limiting Single Failure:

Limiting Break Location:

Limiting Break Size:

Reference Peak Cladding Temperature (PCT) for GNF2 Fuel:

MARGIN ALLOCATION A. PRIOR LOCA ASSESSMENTS (Note 1 ):

1 O CFR 50.46 Report dated August 15, 2014 (Note 1.1) 10 CFR 50.46 Report dated August 10, 2016 (Note 1.2) 1 o CFR 50.46 Report dated August 1 o, 2017 (Note 1.3)

Net PCT B. CURRENT LOCA ASSESSMENTS (Note 2):

Total PCT Change from Current Assessments (Note 2)

Cumulative PCT Change from Current Assessments Net PCT GNF2 GNF2 Battery Failure Recirculation Discharge Line 0.05 ft2 (Small Break) 1920 °F GNF2: ~PCT= +5°F GNF2: ~PCT= 0°F GNF2: ~PCT= 0°F GNF2: 1925°F GNF2: I~PCT = 0°F GNF2: Il~PCTI = 0°F GNF2: 1925°F

ATTACHMENT 3 Assessment Notes 10 CFR 50.46 Report

Assessment Notes 1 O CFR 50.46 Report

1. Prior LOCA Assessment Assessment Notes Page 1 of 2 The last 1 O CFR 50.46 annual report submitted to NRC was in August 10, 2017 (Reference 1 ). This report documents a Net PCT of 1925°F: a licensing basis PCT of 1920° F from the analysis of record report, and a total PCT adder of +5°F for Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3.

[Reference 1: Letter from David T. Gudger (Exelon Generation Company, LLC) to U.S.

Nuclear Regulatory Commission, "10 CFR 50.46 Annual Report," dated August 10, 2017.]

1.1.

Prior LOCA Assessment - 2014 The referenced letter reported four vendor notifications that were received.

1. The first notification addressed several accumulated updates to the SAFER04A model. The code maintenance changes had an individually and collectively insignificant effect on calculated peak cladding temperature.
2. The second notification was for a correction to a logic error that was isolated, occurring with an indication that the expected systems mass diverged from the calculated actual system mass. This error affected the Emergency Core Cooling System (ECCS) flow credited as reaching the core. Correction of this error resulted in a +10°F Peak Cladding Temperature (PCT} change for GNF2 fuel.
3. The third notification addressed an error with the imposed minimum Pressure Differential (Llp} for droplet flow above a two-phase level in the core. This error could have offered an inappropriate steam cooling benefit above the core two phase level. To correct this error an explicit core pressure drop calculation was applied without regard to droplet condition resulting in a PCT of -10°F for GNF2 fuel.
4. The forth notification addressed an incorrect pressure head representation when defining the Counter Current Flow Limitation (CCFL). Correction of this error resulted in a +5°F PCT change for GNF2 fuel.

Note that the 1 O CFR 50.46 notifications discussed in the referenced report are applicable to the Unit 2 and Unit 3 MELLLA+ LOCA analysis and the net effect of these notifications is +5°F

[

Reference:

Letter from James Barstow (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "10 CFR 50.46 Annual Report," dated August 15, 2014.]

Assessment Notes 10 CFR 50.46 Report 1.2.

Prior LOCA Assessment - 2016 Page 2 of 2 The referenced letter reported that PBAPS, Units 2 and 3, implemented Maximum Extended Load Line Limit Analysis Plus (MELLLA+) for which a new LOCA analysis was performed. PBAPS, Units 2 and 3, transitioned to MELLLA+

operation mid-cycle in April 2016 and May 2016, respectively. The error notifications reported in Assessment Note 1 are applicable to the PBAPS, Units 2 and 3, MELLLA+ LOCA analysis. The notifications were issued subsequent to the performance of the MELLLA+ LOCA analysis, but prior to its implementation.

[

Reference:

Letter from James Barstow (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "10 CFR 50.46 Annual Report," dated August 1 O, 2016.]

1.3.

Prior LOCA Assessment - 2017 The referenced letter reported two (2) vendor notifications regarding Emergency Core Cooling System (ECCS) modeling changes/errors applicable to PBAPS (Notifications 2017-01 and 2017-02). These notifications described issues related to the improper modelling of lower tie plate leakage for the GNF2 fuel design and changes to modeling of the fuel rod plenum for 1 Ox1 O fuel.

Correction of these errors each resulted in a 0°F PCT change for GNF2 fuel.

The referenced letter reported a change in the Level 3 setpoint. The impact of this change on the Loss of Coolant Accident (LOCA) analysis was assessed in GNF Report 003N4534-RO, "Peach Bottom Level 3 Analytical Limit Reduction,"

dated May 25, 2016, which concluded that there is no impact on the licensing basis PCT for PBAPS.

[

Reference:

Letter from David T. Gudger (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "10 CFR 50.46 Annual Report," dated August 1 O, 2017.]

2. Current LOCA Assessment No new 50.46 notifications were received from the fuel vendor since issuance of the last annual report (Reference 1 in Note 1 ). Therefore, the total PCT value of 1925°F reported in the last annual report is unchanged for this report.