Effects of Sunlight Exposure on PVC Pipe and Conduit
ML18207A448
Person / Time
Issue date: 01/31/2009
From: William Burton
NRC/NRR/DMLR/MRPB
To:
Burton W, NRR-DMLR 415-6332
References
Download: ML18207A448 (2)


Text

Page 1 of 2 TECHNICAL BULLETIN Building essentials for a better tomorrow THE EFFECTS OF SUNLIGHT EXPOSURE ON PVC PIPE AND CONDUIT INTRODUCTION The sun emits visible and non-visible radiation. One component of non-visible radiation is ultraviolet (UV) light. Like many other substances, PVC plastics are affected by exposure to UV radiation. This bulletin will provide information on the effects sunlight exposure has on PVC, what the resulting consequences are for PVC pipe and conduit, and what can be done to pre vent the effects of UV radiation.

THE EFFECTS OF SUNLIGHT EXPOSURE The exposure of PVC to the UV component of sunlight results in PVC molecules in the first.001 to.002 of exposed surface becoming permanently converted to a complex structure typified by polyene formations. The result is a brownish discoloration, often termed UV Discoloration, UV Degradation, or simply Sunburn.

This discoloration varies depending on the original color of the pipe. White pipe will turn yellow to brown in color. Blue, green, or purple pipe will sun bleach. Grey pipe will have brown or black streaks. UV discoloration does not occur where PVC is not exposed to sunlight, and ceases when exposure ends.

The discoloration process is time dependent, and can be slowed with the addition of UV absorbers in the PVC compound. The most common additive used for this purpose is titanium dioxide, which also functions as a pigment. Titanium dioxide imparts a beige to bright white color to PVC compounds, depending upon the type used.

THE CONSEQUENCES OF SUNLIGHT EXPOSURE FOR PVC PIPE AND CONDUIT Research has been done to determine the effectsof long-term (two year) sunlight exposure on PVC pipe (See UNI-TR-5: The Effects of Ultraviolet Aging on PVC Pipe, by the Uni-Bell PVC Pipe Association). Other than the visible discoloration, the following summarizes the results on pipe physical properties:

The research indicates that the sole performance char acteristic adversely affected by sunlight exposure is impact resistance. Depending upon the type of pipe, additional care may be required during pipe handling and installation to avoid potential breakage. Once installed, however, there will be no effect on the pipes pressure capacity and external load capacity.

JANUARY 2009 PHYSICAL PROPERTY PERFORMANCE CHARACTERISTIC EFFECT OF SUNLIGHT EXPOSURE Impact Strength Impact Resistance Decreased Tensile Strength Pressure Capacity No effect Modulus Pipe Stiffness No effect

Page 2 of 2 Building essentials for a better tomorrow The degree to which impact strength is afected by sun light depends upon a number of variables, including:

time of exposure, climatic conditions, diameter of pipe, wall thickness of pipe, and type of PVC compound used. Because of these variables, it is impossible to state how long it will take before the effects of sunlight exposure become noticeable. In general, pipes of smaller diameter and thinner wall will exhibit more effect from sunlight exposure than larger, thicker-walled pipe. The effect of sunlight exposure on thickwalled pressure pipes such as those made to AWWA C900 and C905 is almost unnoticeable, other than the sur face discoloration.

The tapping of UV-discolored pressure pipes has been a topic of concern. However, the PVC pipe industry has found no evidence of tapping failures due to UV discoloration.

JM Eagles Schedule 40 and Schedule 80 NSF listed electrical conduit has been tested for sunlight resis tance according to UL 651 requirements and is listed for continuous outdoor exposed use. The test is based on izod impact testing, not color retention.

PREVENTION OF UV DISCOLORATION For permanent above-ground PVC pipe installations, it is recommended that the pipe be protected from sun light exposure. This can be accomplished by wrapping the pipe with an opaque material, or more commonly, by painting it. If the pipe is to be painted, a water-based latex paint formulated for exterior use is recommended.

Oil or solvent-based paints may damage the pipe and/

or not adhere well. In order to minimize heat build-up, white or light-colored latex paints are best.

Pipe that is going to be stored for a long period of time (one to two years or more) may be protected from the sun with light colored tarps. The tarps should be placed so as to allow for adequate ventilation to prevent heat build-up.

GASKETS PVC pipe gaskets are formulated to withstand UV exposure under common storage practices for PVC pipe. PVC pipe and gaskets can be used after pro longed storage above ground under normal conditions and it is not necessary to replace the gaskets unless there are signs of degradation such as cracking.

As a standard practice, the installer should inspect the pipe and gaskets for any signs of deformation, crack ing, or physical damage prior to assembly. Such pipe should not be installed.