Forwards Mods to Two ERDS Points for Total High Head Safety Injection Cold Leg Flow to Resolve Recent Emergency Response Facility Problem Repts Detailed in Data Point Library Ref Sheets Contained in Attachment 1
ML18153D085
Person / Time
Site: Surry  
Issue date: 08/06/1992
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
92-492, NUDOCS 9208110271
Download: ML18153D085 (11)


Text


-- -_ -- -- ~-

e e

VIRGINIA ELECTRIC AND "POWER -COMPANY RICHMOND, VIRGINIA -23261 August 6, 1992 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY

-SURRY POWER STATION UNITS 1 AND 2 EMERGENCY RESPONSE DATA SYSTEM DATA BASE UPDATES Serial No.*

NL&P/CGL Docket Nos.

License Nos.92-492 RO 50-280 50-281 DPR-32 DPR-37 Modifications were recently made to two Emergency Response Data System (EADS) points for total high head safety injection cold leg flow for Surry Units 1 and 2. The changes, which were made to resolve recent Emergency Response Facility problem reports, are detailed in the Data Point Library (DPL) reference file sheets contained in. Attachment 2 provides revision summaries (change reports) for the affected points. The updated data base files, documented in Attachments 1 and 2, are also provided in the dBase IV format on Attachment 3.

If you have questions regarding this information, please contact us.

Very truly yours,

  • , t\\ ("~/

'.\\

\\."\\1-*yt_{v~:~

  • W. L. Stewart

$enior Vice President - Nuclear Attachments:

1. Updated Data Point Library Reference File Sheets
2.
  • Revision Summaries
3. Updated DPL Data Base Files in dBase IV Format 9208110271 920806 PDR ADOCK 05000280 F

PDR

e cc:

U~ S. Nuclear Regulatory Commission - Attachments 1 and 2 Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. M. W. Branch - Attachments 1 and 2 NRC*Senior Resident Inspector Surry Power Station NUS Corporation I El Division - Attachments 1, 2, and 3 P. 0. Box 59736 Idaho Falls, Idaho 83405 Attention: Mr. Tony LaRosa


=

e e

  • ATTACHMENT 1 UPDATED DATA POINT LIBRARY REFERENCE FILE SHEETS

DATE:

REACTOR UN IT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HO\\./ PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

e STATION: Surry UNIT: 1 e

P\\./R DATA,POINT LIBRARY REFERENCE FILE 07/14/92 SU1 N/A' HP SI FLO\\./

  • F1SI001C TOT COLD LEG HHS! FLO\\./

HIGH PRESSURE SI FLO\\./

A GPM N/A 0

1800 N/A N/A p

  • 3 SUM - SEE SYSTEM DESCRIPTION CHRGING PMP DISCH UPSTRM OF COLD LEG VARIABLE NI DETECTOR PO\\./ER SUPPLY CUT-OFF PO\\./ER LEVEL:

N/A NI DETECTOR PO\\./ER SUPPLY TURN-ON PO\\./ER LEVEL:

N/A INSTRUMENT FAILURE MODE:

N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

N/A Provides flow indication on the SI headers from the HHS!

pumps to the cold leg of each loop.

The 3 loop high head SI flows are totaled for this value.

If any one of the loop SI values is invalid, this point will be marked invalid.

PRINTED 07/14/92

DATE:

REACTOR UN IT:

DATA FEEDER:

NRC EROS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR,UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

e 07/14/92 SU2 N/A HP SI FLOW F2SI001C STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE TOT COLD LEG HHS! FLOW HIGH PRESSURE SI FLOW A

GPM N/A 0

1800 N/A N/A p

3 SUM* SEE SYSTEM DESCRIPTION CHRGING PMP DISCH UPSTRM OF COLD LEG VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC:

Provides flow indic.ation on the SI headers from the HHS!

pumps to the cold leg of each loop.

The 3 loop high head SI flows are totaled for this value.

If any one of the loop SI values is invalid, this point will' marked invalid.

PRINTED 07/14/92

ATTACHMENT 2 REVISION SUMMARIES

STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT -

e ADDED.POINT F1Sl001C AT 09:44 ON 07/14/92 AS FOLLOWS:

DATE:

REACTOR UN IT:

DATA FEEDER:

NRC EROS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL.:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

  • NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY

  • cuT-OFF _POWER LEVEL:

07/14/92 SU1 N/A HP SI FLOW F1Sl001C TOT, COLO LEG HHSI FLOW HIGH PRESSURE SI FLOW A

GPM N/A 0

1800 N/A N/A p

3 SUM - SEE SYSTEM DESCRIPTION CHRGING PMP DISCH UPSTRM OF COLD LEG VARIABLE N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

N/A TEMPERATURE COMPENSAr'ION FOR DP TRANSMITTERS:

LEVEL REFERENCE*LEG:

UNIQUE SYSTEM DESC:

N/A Provides flow ir,dication on the SI headers from the HHSI punps to the' cold leg of each loop.

The 3 loop high head SI flows are totaled for this value.

If any one of the loop SI values is invalid, this point will be marked invalid.

PRINTED 07/14/92

STATION: Surry*

UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT DELETED POINT F1RC005C AT 09:45 ON 07/14/92.

FIELDS WERE AS FOLLOWS:

DATE:

05/20/91 REACTOR UNIT:

SU1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

-HP SI FLOW POINT ID:

F1RC005C PLANT SPEC PO~NT DESC:

TOT COLD LEG HHS! FLOW GEN~RIC/COND DESC:

HIGH PRESSURE SI FLOW ANALOG/DIGITAL:

. A ENGR UNITS/DIG STATES:

GPM ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

0.0 MAXIMUM INSTR RANGE:

1800.0_

ZERO POINT

REFERENCE:

N/A REFERENCE. POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

3 HOW PROCESSED:

SUM **SEE SYSTEM DESCRIPTION SENSOR LOCATIONS:

CHRGING PMP DISCH UPSTRM OF COLD LEG.

ALARM/TRIP SETPOINTS:

VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT.fAI LURE MODE:

N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A e

UNIQUE SYSTEM DESC:

Provides flow indication on the SI headers from the *HHSI pull>S to the cold Leg of each Loop.* The 3 Loop high head SI flows are totaled for this value.

If any_ one of the loop SI values is invalid, this point wi LL be marked invalid.

PRINTED

  • 07 /14/92

I STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT ADDED POINT F2SI001C AT 09:49 ON 07/14/92 AS FOLLOWS:

DATE:

REACTOR UN IT: -

DATA FEEDER:

NRC EROS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIG IT AL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARH/TRIP*SETPQINTS:

07/14/92 SU2 N/A HP SI FLOIJ F2SI001C TOT COLD LEG HHS! FLOW HiGH PRESSURE SI FLOW A

GPH N/A 0

1800.

N/A N/A p

3 SUH* SEE SYSTEM DESCRIPTION CHRGING PHP DISCH UPSTRH OF COLD LEG VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MOOE:

N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A e

UNIQUE SYSTEM DESC:

Provides flow indication on the SI headers from the HHS!

~s to *the cold leg of each loop.

The 3 loop high head SI flows are totaled for this value: If any one of the loop SI values is invalid, this point will marked invalid.

PRINTED 07/14/92

e STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT DELETED POINT F2Rcposc AT 09:49 ON 07/14/92 *. FIELDS WERE AS FOLLOWS:

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

_GENERIC/COND DESC:

ANALOG/DIG IT AL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF *SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

05/20/91 SU2

_N/A HP SI FLOW F2RCOOSC TOT COLD LEG HHSI FLOW HIGH PRESSURE SI FLOW A

GPM N/A o.o 1800.0 N/A

_NIA p

3 SUM~- SEE SYSTEM DESCRIPTION CHRGING PMP DISCH UPSTRM OF COLD LEG VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:-

N/A INSTRUMENT FAILURE MOOE:

N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A.

e UNIQUE SYSTEM DESC:

Provides flow indication on the SI headers from the HHS!

punps to the cold leg of each loop.

The 3 loop.high head SI flows are totaled for this value.

If any one of the loop SI values is invalid, this point will be marked invalid.

PRINTED 07/14/92