I I

e e

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 April 20, 1990 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT 1 Serial No.

89-8288 NO/ETSREV1 Docket Nos.

50-280 License Nos.

DPR-32 CLARIFICATION TO TYPE C TESTING EXEMPTION REQUEST On January 8, 1990, Virginia Electric and Power Company requested an exemption from 1 O CFR 50, Appendix J, Type G testing requirements. This exemption, coupled with one-time Technical Specification changes for snubber and check valve testing, will avoid a shutdown of Surry Unit 1 prior to its scheduled refueling outage (October 1990) solely to perform routine testing. In a telephone conference call with Mr. B. C. Buckley and other members of the NRC staff, it was requested that a projected 'As-found' total leakage be provided for the valves for which the exemption is being requested. The calculation to develop the projected leakage total uses a conservative estimate for each penetration. Therefore, this projection should provide reasonable assurance that the valves' leaktightness should not degrade to a point where the Type C leakage acceptance criterion (0.6 La) would be exceeded by December 31, 1990. provides the 'As-found' leakage projection for the valves included in the exemption, as well as a projected 'As-found' leakage total for Type C testing during the 1990 refueling outage. provides a summary of the subject valves leakage performance.

Should you have any further questions please contact us.

Very truly yours,

\\SJ~

W. L. Stewart Senior Vice President - Nuclear Attachments

  • 90050101 71 9004-20 l LPD~

ADOCK 05000280

\\P -

PDC

e cc:

U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station

ATTACHMENT 1 Surry Power Station Previous Tests and Projected Leakage Totals For Type C Testing For Valves/Penetrations Included In Exemption Request

L The following presents the 1986 and 1988 Type C leakage for the valves included in the exemption request. A projection of the 1990 Type C test results based on the 1986 and 1988 test results and the maintenance history of the valves has been completed.

1986 Type C Test Results (Exemption Request Valves)

'As-found' Total: 910.117 SCFH Major contributors were: TV-DA-1 OOA/B; 1-RM-3; 1-IA-939; TV-SS-102A; TV-SS-101 A, with 300 SCFH directly attributable to TV-DA-1 OOA/B. These valves were repaired and retested satisfactorily as demonstrated by the test results in.

1988 Type C Test Results (Exemption Request Valves)

'As-found' Total: 253.334 SCFH Major contributors were: 1-RM-3; 1-RC-160; FCV-1160; 1-IA-446; TV-SS-102A; TV-CV-150A, with 107.94 SCFH directly attributable to FCV-1160. FCV-1160 is water filled and not considered a credible leakage path.

1990 Projected Type C Test Results (Exemption Request Valves)

'As-found' Total: 59.874 SCFH The projected value is based on 70 valves. Six Steam Generator Recirculation and Transfer valves are Type C tested, but are in a closed system and not a contributor to the overall Type C leakage total (RT valve test results are included in ). For each valve a projected leakage calculation was performed and then the projected leakage for the 70 valves was totalled. If a valve had a negative leakage trend the most recent 'As-found' leakage value was used.

For valves that were overhauled or replaced, a leakage calculation was not used.

Instead the most recent post-maintenance 'As-found' leakage value was used. If the 'As-found' leakage was not available then the 'As-left' leakage value was used.

Valves in eight penetrations were replaced or overhauled. These valves were the major leakage contributor in the 1988 Type C test and include the following:

FCV - 1160 1 - RM - 3 TV-IA-100 TV-SS-102A 1 - VP - 12 TV - CV-150A HGV - CV - 100 TV - SS - 101 B valve overhauled valve replaced flange gasket replaced.no valve leakage valve replaced valve replaced valve overhauled valve overhauled valve replaced

1990 Projected Total Type c Test Results If a projected value is determined for the remaining 46 valves which were not included in the exemption request, and added to the projected value for the 70 valves for which an exemption is being requested, the following leakage projection is obtained.

'As-found' Total: 134.404 SCFH This projected total provides a reasonable margin to the allowable 0.6 La value of 180 SCFH.

Projected Leakage Calculation Methodology If:

Test 1 = 1986 'As-found' test results Test 2 = 1988 'As-found' test results LRTM = Leakage Rate Trend Month 24 months = elapsed time between 1986 and 1988 tests 30 months = time between 1988 test and December 31, 1990 PVLI = Projected Valve Leakage Increase then:

(Test 2 - Test 1) + by 24 months= LRTM LRTM x 30 months = PVLI Test 2 + PVLI = Projected 1990 Leakage for that valve 62 I

(Test 2 + PVLI) + Leakage total for the 8 overhauled and replaced valves 1

= Projected 1990 Leakage for valves included in the exemption request

ATTACHMENT 2 Surry Power Station Leakage Results For Penetrations/Valves Included In Type C Exemption Request

e SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 015 1-CH-0309 05/16/86

.000.

015 1-CH-0309 06/23/88

.147 015 1-CH-0309 06/23/88

.147 015 MOV-CH-1289A 05/16/86

.124 015 MOV-CH-1289A 06/30/86

.120 015 MOV-CH-1289A 06/23/88 3.190 015 MOV-CH-1289A 06/23/88

.000 015 MOV-CH-1289A 04/10/89

.000 015 MOV-CH-1289A

  • 06/20/89

.000 024 MOV-RH-0100 05/16/86 4.200 024 MOV-RH-0100 06/07/86

.240 024 MOV-RH-0100 06/23/88

.647 024 MOV-RH-0100 06/23/88

.522 032 TV-GW-0106 05/15/86

.000 032 TV-GW-0106 06/23/88

.000 032 TV-GW-0106 06/23/88

.000 032 TV-GW-0107 05/15/86

.000 032 TV-GW-0107 06/23/88

.000 032 TV-GW-0107 06/23/88

.000 033 TV-DG-01 OBA 05/19/86 3.730 033 TV-DG-01 OBA 06/18/86

.460 033 TV-DG-01 OBA 06/23/88 4.160 033 TV-DG-01 OBA 06/23/88

.050 033 TV-DG-01088 05/19/86 35.000 033 TV-DG-01088 06/18/86

.070 033 TV-DG-01088 06/23/88

.000 033 TV-DG-01088 06/23/88

.000 033 TV-DG-01088 04/10/89

.000 033 TV-DG-01088

  • 04/10/89

.000

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 038 TV-DA-01 OOA 01/27/86

.600 038 TV-DA-01 OOA 05/22/86 300.000 038 TV-DA-01 OOA 06/21 /86

.000 038 TV-DA-01 OOA 07/09/86

.900 038 TV-DA-01 OOA 09/11 /86 255.000 038 TV-DA-01 OOA 09/11 /86 4.900 038 TV-DA-01 OOA 09/22/86

.000 038 TV-DA-01 OOA 12/12/86

.320 038 TV-DA-01 OOA 01/13/87

.000 038 TV-DA-01 OOA 05/19/87 305.000 038 TV-DA-01 OOA 05/21 /87

.000 038 TV-DA-01 OOA 06/23/88

.109 038 TV-DA-01 OOA 06/23/88

.000 038 TV-DA-01 OOB 01/27/86 22.200 038 TV-DA-01 OOB 02/02/86 3.600 038 TV-DA-01 OOB 05/22/86 300.000 038 TV-DA-01 OOB 06/21/86

.000 038 TV-DA-01 OOB 09/11 /86 255.000 038 TV-DA-01 OOB 09/11 /86 4.900 038 TV-DA-01 OOB 12/12/86 31.430 038 TV-DA-01 OOB 01/13/87

.000 038 TV-DA-01 OOB 05/19/87

.000 038 TV-DA-01 OOB 06/23/88 4.990 038 TV-DA-01 OOB 06/23/88

.000 042 1-SA-0060 06/24/86

.190 042 1-SA-0060 06/23/88

.000 042 1-SA-0060 06/23/88

.000 042 1-SA-0062 06/24/86

.076 042 1-SA-0062 06/23/88

.000 042 1-SA-0062 06/23/88

.000 043 1-RM-0003 05/29/86 28.400 043 1-RM-0003 06/23/86

.000 043 1-RM-0003 01/02/87 15.710 043 1-RM-0003 06/23/88 15.000 043 1-RM-0003 06/23/88

.000

e SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 043 TV-RM-01 DOA 05/29/86 2.320 043 TV-RM-01 DOA 06/23/86

.330 043 TV-RM-01 DOA 06/23/88

.539 044 TV-RM-01008 05/21 /86

.067 044 TV-RM-01008 06/23/88

.106 044 TV-RM-01008 06/23/88

.106 044 TV-RM-01 OOC 05/21/86

.000 044 TV-RM-01 DOC 06/23/88

.055 044 TV-RM-01 OOC 06/23/88

.055 045 1-RC-0160 05/17/86 2.420 045 1-RC-0160 06/16/86 3.280 045 1-RC-0160 06/23/88 9.900 045 1-RC-0160 06/23/88 9.900 045 TV-RC-1519A 05/17/86

.000 045 TV-RC-1519A 06/16/86

.000 045 TV-RC-1519A 06/23/88

.000 045 TV-RC-1519A 06/23/88

.000 045 TV-RC-1519A 04/10/89

.000 045 TV-RC-1519A 04/10/89

.000 045 TV-RC-1519A

  • 06/20/89

.000 046 FCV-CH-1160 05/14/86 4.910 046 FCV-CH-1160 06/07/86

.112 046 FCV-CH-1160 01/06/87

.000 046 FCV-CH-1160 01/12/87

.000 046 FCV-CH-1160 05/19/87

.740 046 FCV-CH-1160 05/25/87

.050 046 FCV-CH-1160 09/22/87 51.550 046 FCV-CH-1160 09/27/87

.834 046 FCV-CH-11 60 06/23/88 107.500 046 FCV-CH-1160 06/23/88

.000

~-~ -------~~

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 047 1-IA-0446 05/17/86

.000 047 1-IA-0446 06/23/88 18.760 047 1-IA-0446 06/23/88

.000 047 1-IA-0939 05/17/86 101.000 047 1-IA-0939 05/27/86

.000 047 1-IA-0939 06/23/88 14.500 047 1-IA-0939 06/23/88

.160 047 TV-IA-0100 05/17/86

.000 047 TV-IA-0100 06/23/88 18.760 047 TV-IA-0100 06/23/88

.000 048 TV-VG-0109A 05/20/86

.187 048 TV-VG-0109A 06/23/88 1.340 048 TV-VG-0109A 06/23/88

.025 048 TV-VG-0109B 05/20/86

.000 048 TV-VG-0109B 06/23/88

.000 048 TV-VG-0109B 06/23/88

.000 048 TV-VG-01098 06/20/89

.000 048 TV-VG-0109B

  • 06/20/89

.000 050 TV-Sl-0101 A 05/15/86 6.400 050 TV-Sl-0101 A 05/28/86

.042 050 TV-Sl-0101 A 06/23/88 1.730 050 TV-Sl-0101 A 06/23/88

.220 050 TV-Sl-0101 A 04/10/89

.000 050 TV-Sl-0101 A

  • 04/10/89

.000 050 TV-Sl-0101 B 05/15/86

.260 050 TV-Sl-0101 B 06/23/88

.000 050 TV-Sl-0101 B 06/23/88

.000

e SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 051 1-SW-0206 05/14/86

.661 051 1-SW-0206 06/30/86 1.100 051 1-SW-0206 01/02/87

.670 051 1-SW-0206 01/16/87

.400 051 1-SW-0206 06/23/88

.308 051 1-SW-0206 06/23/88

.308 051 1-SW-0208 05/14/86

.510 051 1-SW-0208 06/30/86 1.600 051 1-SW-0208 01/02/87

.130 051 1-SW-0208 01/16/87

.110 051 1-SW-0208 06/23/88

.000 051 1-SW-0208 06/23/88

.000 053 1-Sl-0234 05/14/86

.612 053 1-Sl-0234 06/23/88 1.500 053 1-Sl-0234 06/23/88

.047 053 TV-Sl-0100 05/14/86

.125 053 TV-Sl-0100 06/23/88

.000 053 TV-Sl-0100 06/23/88

.000 054 1-VA-0001 05/21 /86

.340 054 1-VA-0001 06/23/88

.225 054 1-VA-0001 06/23/88

.225 054 1-VA-0006 05/21 /86

.310 054 1-VA-0006 06/23/88

.760 054 1-VA-0006 06/23/88

.760 055A TV-LM-01 OOG 05/12/86

.000 055A TV-LM-01 OOG 06/23/88

.000 055A TV-LM-01 OOG 06/23/88

.000 055A TV-LM-01 OOH 05/12/86

.000 055A TV-LM-01 OOH 06/23/88

.000 055A TV-LM-01 OOH 06/23/88

.000

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 056A TV-SS-01 OOA 05/22/86

.000 056A TV-SS-01 OOA 06/17/86

.000 056A TV-SS-01 OOA 12/16/86

.000 056A TV-SS-01 OOA 01/09/87

.000 056A TV-SS-01 OOA 06/23/88

.000 056A TV-SS-01 OOA 06/23/88

.000 056A TV-SS-01008 05/22/86

.547 056A TV-SS-01008 06/17/86

.420 056A TV-SS-01008 06/23/88

.000 056A TV-SS-01008 06/23/88

.000 056A TV-SS-01008 06/20/89

.090 056A TV-SS-01008

  • 06/20/89

.000 0568 TV-SS-0102A 05/22/86 260.000 0568 TV-SS-0102A 06/10/86

.000 0568 TV-SS-0102A 09/23/87

.000 0568 TV-SS-0102A 09/27/87

.000 0568 TV-SS-0102A 06/23/88 13.500 0568 TV-SS-0102A 06/23/88

.000 0568 TV-SS-01028 05/22/86 5.700 0568 TV-SS-01028 06/10/86

.023 0568 TV-SS-01028 09/23/87 300.000 0568 TV-SS-01028 09/27/87

.000 0568 TV-SS-01028 06/23/88 13.500 0568 TV-SS-01028 06/23/88

.000 056D TV-SS-0106A 05/29/86 8.550 056D TV-SS-0106A 06/15/86

.000 056D TV-SS-0106A 06/23/88

.000 056D TV-SS-0106A 06/23/88

.000 056D TV-SS-01068 05/29/86 9.160 056D TV-SS-01068 06/15/86

.110 056D TV-SS-01068 06/23/88

.000 056D TV-SS-01068 06.23/88

.000

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 057A TV-LM-01 OOE 05/12/86

.000 057A TV-LM-01 OOE 06/23/88

.000 057A TV-LM-01 OOE 06/23/88

.000 057A TV-LM-01 OOF 05/12/86

.000 057A TV-LM-01 OOF 06/23/88

.000 057A TV-LM-01 OOF 06/23/88

.000 057B TV-SS-0104A 05/18/86

.012 057B TV-SS-0104A 06/14/86

.119 057B TV-SS-0104A 12/16/86

.100 057B TV-SS-0104A 01/09/87

.000 057B TV-SS-0104A 06/23/88

.000 057B TV-SS-0104A 06/23/88

.000 057B TV-SS-0104B 05/18/86

.020 057B TV-SS-0104B 06/23/88

.000 057B TV-SS-0104B 06/23/88

.000 057C TV-SS-0101 A 05/22/86 180.000 057C TV-SS-0101 A 07/01/86

.000 057C TV-SS-0101 A 07/08/86

.000 057C TV-SS-0101 A 12/16/86

.000 057C TV-SS-0101 A 01/09/87

.000 057C TV-SS-0101 A 06/23/88

.000 057C TV-SS-0101 A 06/23/88

.000 o.57C TV-SS-0101 B 05/22/86

.229 057C TV-SS-0101 B 06/23/88 8.140 057C TV-SS-0101 B 06/23/88

.000 057D TV-DA-0103A 05/15/86

.000 057D TV-DA-0103A 01/13/87

.110 057D TV-DA-0103A 06/23/88

.180 057D TV-DA-01 03A 06/23/88

.180 I

L

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 0570 TV-OA-01038 05/15/86

.000 0570 TV-OA-01038 01/13/87

.255 0570 TV-OA-01038 06/23/88

.235 0570 TV-OA-01038 06/23/88

.235 058 1-IA-0938 05/12/86

.000 058 1-IA-0938 06/23/88

.000 058 1-IA-0938 06/23/88

.000 058 2-IA-0446 05/17/86

.000 058 2-IA-0446 06/23/88

.450 058 2-IA-0446 06/23/88

.203 070 1-RS-0011 05/30/86

.053 070 1-RS-0011 06/23/88 3.500 070 1-RS-0011 06/23/88

.740 070 MOV-RS-01568 05/30/86 2.090 070 MOV-RS-01568 06/27/86

.120 070 MOV-RS-01568 06/23/88 3.250 070 MOV-RS-01568 06/23/88 1.524 070 MOV-RS-01568 06/20/89

.650 070 MOV-RS-0156B

  • 06/20/89 1.050 071 1-RS-0017 05/29/86

.134 071 1-RS-0017 06/23/88

.000 071 1-RS-0017 06/23/88

.660 071 MOV-RS-0156A 05/29/86

.213 071 MOV-RS-0156A 06/27/86

.000 071 MOV-RS-0156A 06/23/88

.450 071 MOV-RS-0156A 06/23/88

.664 071 MOV-RS-0156A 06/20/89 1.400 071 MOV-RS-0156A

  • 06/20/89

.1450 L

(

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 089 1-VP-0012 05/20/86

.200 089 1-VP-0012 06/23/88 4.400 089 1-VP-0012 06/23/88

.730 089 TV-SV-0102A 05/20/86 1.310 089 TV-SV-0102A 05/20/86 1.080 089 TV-SV-0102A 06/23/88

.000 089 TV-SV-0102A 06/23/88

.000 092 TV-CV-0150C 05/21/86 9.000 092 TV-CV-0150C 06/09/86

.270 092 TV-CV-0150C 06/23/88

.185 092 TV-CV-01 50C 06/23/88

.185 092 TV-CV-0150D 05/21/86

.870 092 TV-CV-0150D 06/09/86

.190 092 TV-CV-0150D 06/23/88

.771 092 TV-CV-0150D 06/23/88

.191 092 TV-GW-0100 05/21/86

.660 092 TV-GW-0100 06/09/86

.025 092 TV-GW-0100 06/23/88

.000 092 TV-GW-0100 06/23/88

.000 092 TV-GW-0101 05/21 /86

.220 092 TV-GW-0101 06/09/86

.000 092 TV-GW-0101 06/23/88

.000 092 TV-GW-0101 06/23/88

.000 093 TV-CV-0150A 05/15/86

.660 093 TV-CV-0150A 05/26/86

.000 093 TV-CV-0150A 06/23/88 49.500 093 TV-CV-0150A 06/23/88

.000 093 TV-CV-0150B 05/15/86 2.820 093 TV-CV-0150B 05/26/86

.180 093 TV-CV-0150B 06/23/88

.160 093 TV-CV-0150B 06/23/88

.160

~

r, I..

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 093 TV-GW-0104 05/15/86

.660 093 TV-GW-0104 05/26/86

.020 093 TV-GW-0104 06/23/88

.000 093 TV-GW-0104 06/23/88

.000 093 TV-GW-0105 05/15/86

.660 093 TV-GW-0105 05/26/86

.000 093 TV-GW-0105 06/23/88

.000 093 TV-GW-0105 06/23/88

.000 094 1-CV-0002 05/26/86

.000 094 1-CV-0002 06/23/88

.838 094 1-CV-0002 06/23/88

.000 094 HCV-CV-0100 05/26/86

.300 094 HCV-CV-0100 06/23/88 3.250 094 HCV-CV-0100 06/23/88

.470 0978 TV-SS-0103A 05/23/86

.076 0978 TV-SS-0103A 06/23/88

.000 0978 TV-SS-0103A 06/23/88

.000 0978 TV-SS-01038 05/23/86

.071 0978 TV-SS-01038 06/23/88

.000 0978 TV-SS-01038 06/23/88

.000 097C TV-LM-01 OOA 05/12/86

.000 097C TV-LM-01 OOA 06/23/88

.000 097C TV-LM-01 OOA 06/23/88

.000 097C TV-LM-01008 05/12/86

.000 097C TV-LM-01008 06/23/88

.000 097C TV-LM-01008 06/23/88

.000

I...

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 TEST MEASUREMENT PEN NO VALVE NO TEST DATE (SCFH) 100 TV-GW-0102 05/16/86

.000 100 TV-GW-0102 06/23/88

.000 100 TV-GW-0102 06/23/88

.000 100 TV-GW-0103 05/16/86

.000 100 TV-GW-0103 06/23/88

.000 100 TV-GW-0103 06/23/88

.000 100 TV-GW-0103

  • 06/24/89

.000 101 1-FP-0151 05/31 /86

.110 101 1-FP-0151 06/23/88

.000 101 1-FP-0151 06/23/88

.000 101 1-FP-0152 05/31 /86

.000 101 1-FP-0152 06/23/88

.000 101 1-FP-0152 06/23/88

.000 105C TV-GW-0111 A 05/16/86

.000 105C TV-GW-0111 A 06/23/88

.000 105C TV-GW-0111 A 06/23/88

.000 105C TV-GW-0111 B 05/16/86

.000 105C TV-GW-0111 B 06/23/88

.000 105C TV-GW-0111 B 06/23/88

.000 105D TV-LM-01 OOC 05/12/86

.000 105D TV-LM-01 OOC 06/23/88

.000 105D TV-LM-01 OOC 06/23/88

.000 105D TV-LM-01 OOD 05/12/86

.000 105D TV-LM-01 OOD 06/23/88

.000 105D TV-LM-01 OOD 06/23/88

.000

SURRY UNIT ONE TYPE C HISTORY FOR PENETRATIONS NOT FULLY TESTED SINCE JUNE 1988 PEN NO VALVE NO TEST DATE 112 TV-IA-0101 A 05/20/86 112 TV-IA-0101 A 06/23/88 112 TV-IA-0101 A 06/23/88 112 TV-IA-0101 B 05/20/86 112 TV-IA-0101 B 06/23/88 112 TV-IA-0101 B 06/23/88

STEAM GENERATOR RECIRCULATION AND TRANSFER PENETRATIONS 022 1-RT-0021 06/23/88 022 1-RT-0021 06/23/88 022 1-RT-0025 06/23/88 022 1-RT-0025 06/23/88 096 1-RT-0002 06/23/88 096 1-RT-0002 06/23/88 096 1-RT-0006 06/23/88 096 1-RT-0006 06/23/88 096 1-RT-0006 06/20/89 096 1-RT-0006 06/20/89 114 1-RT-0040 06/23/88 114 1-RT-0040 06/23/88 114 1-RT-0044 06/23/88 114 1-RT-0044 06/23/88 NOTE: RT-0044 - COMPLETELY OVERHAULED TEST MEASUREMENT (SCFH)

.157

.760

.000

.120 4.470

.000

.000

.000

.000

.000

.000

.060

.080

.080

.000

.000

.000

.000 128.960

.454