Text

,_.

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 March 8, 1990 United States Nuclear Regulatory Commission Serial No.90-098 Attention: Document Control Desk NO/ETS:vlh Washington, D. C. 20555 Docket Nos. 50-280 50-281 License Nos. DPR-32 DPR-37 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS I AND 2 PROPOSED TECHNICAL SPECIFICATION CHANGE SENSITIZED STAINLESS STEEL PIPING FLUSHING Pursuant to 10 CFR 50.90, the Virginia Electric and Power Company requests amendments, in the form of changes to the Technical Specifications, to Operating Licenses DPR-32 and DPR-37 for Surry Power Station Units 1 and 2, respectively. The change (Attachment 1) will eliminate the monthly flush requirements for the sensitized stainless steel piping installed in primary and safety systems. The sensitized stainless steel will be flushed on an as-necessary basis whenever chlorides and/or fluorides exceed 0.15 ppm in the refueling water storage tank and as a minimum each refueling outage in conjunction with safety system flow testing. The normal operating range for chlorides and fluorides in the refueling water storage tank is 20-25 ppb chlorides and 1-2 ppb fluorides.

This change has been reviewed by the Station Nuclear Safety and Operating Committee. It has been determined that the change does not involve an unreviewed safety question as defined in 10 CFR 50.59 or a significant hazards consideration as defined in 10 CFR 50.92. Our basis for determining that no significant hazards consideration exists is contained in Attachment 2.

Very truly yours,

\JtS~

W. L. Stewart Senior Vice President - Nuclear Attachments

1. Proposed Technical Specifications Change
2. Discussion of Proposed Change r

9003100012 PDR ADOCK O 9ggg8! 80 PNU p

I I

L_

cc: U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station Commissioner Department of Health Room 400 109 Governor Street Richmond, Virginia 23219

e e COMMONWEALTH OF VIRGINIA )

)

COUNlY OF HENRICO )

The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by W. L. Stewart who is Senior Vice President - Nuclear, of Virginia Electric and Power Company. He is duly authorized to execute and file the foregoing document in behalf of that Company, and the statements in the document are true to the best of his knowledge and belief.

Acknowledged before me this 8 !JI day of~~ 199l>.

My Commission Expires: ~ 3/ , 19~.

___$Cb_:_X._fluli Notary Public (SEAL) ; i