e e

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 July 28, 1989 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 Serial No.

NO/ETS Docket Nos.

License Nos.

88-275C 50-280 50-281 DPR-32 DPR-37 NRC BULLETIN 88-04: POTENTIAL SAFETY-RELATED PUMP LOSS SUPPLEMENTAL INFORMATION On August 8, 1988, Virginia Electric and Power Company provided our response to NRC Bulletin 88-04, "Potential Safety-Related Pump Loss."

This letter provides supplemental information to detail our actions taken with regard to Low Head Safety Injection (LHSI) pump operation.

In the*-original submittal, we committed to evaluate accident scenarios on the simulator to ensure the emergency procedures adequately addressed, and therefore, minimized parallel operation of the LHSI pumps during low flow conditions. The evaluation was completed, and it was determined that an emergency procedure revision. is necessary to ensure, that one LHSI pump will be secured within 30 minutes when operating in parallel with low flow conditions. The emergency procedure has been revised to secure one LHSI pump during recirculation only flow conditions. A timing validation on the simulator has indicated that one pump can be secured within 30 minutes.

The information contained herein is true and accurate to the best of my knowledge. If you have any questions, please contact me.

Very truly yours, Jt~

W. L. Stewart Senior Vice President - Power R908070082 890728

~b~ ADOCK 05000280 Q

PDC

\\

e cc:

U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station e

e COMMONWEAL TH OF VIRGINIA )

)

COUNTY OF HENRICO

)

The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by W. L. Stewart who is Senior Vice President - Power, of Virginia Electric and Power Company.

He is duly authorized to execute and file the foregoing document in behalf of that Company, and the statements in the document are true to the best of his knowledge and belief.

Acknowledged before me this --2.8.._ day of _....,.9.,..u."""~...,_ __, 19tt_.

My Commission Expires: Ji.~ ZS.

, 19j'.t_.