Forwards Response to NRC Bulletin 88-010, Nonconforming Molded-Case Circuit Breakers. Subj Breakers Will Be Replaced
ML18153B675
Person / Time
Site: Surry  
Issue date: 04/03/1989
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
88-788B, IEB-88-010, IEB-88-10, NUDOCS 8904120410
Download: ML18153B675 (5)


Text

e*

e VIRGINIA ELECTRIC AND POWER COMPANY

. RICHMOND,.VIRGINIA 23261

.-***:.:~:J~~t::z::::\\-:-._:,... *'.:~: *,. :.".:::_:_~-::-::*:.** ;:: :~.{:.:*.*:, :* \\\\*.,.'.*~e~i,'.. ~~f,-~:~*a_~_.:':.::.._/:**.-i*:_:.:***.. :,\\;:'.

. :.**:. :': * :* ::. '.,., ~*.,:* *:,.,.*~':,:.r*.::~.* * *},*;

NUCLEAR U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 RESPONSE TO NRC BULLETIN No. 88-10 Serial No.

NO/HWB:vlh Docket Nos.

License Nos.

88-788B Rev 4 50-280 50-281 DPR-32 DPR-37 As requested by NRC Compliance Bulletin No. 88-10, Nonconforming Molded-Case Circuit Breakers, a summary of the total number, manufacturer, model number, and to the extent possible, the procurement chain, has been identified for those molded-case circuit breakers (MCCBs) in our station stores which were purchased before August 1, 1988 and which could not be traced to a circuit breaker manufacturer (CBM).

This summary is provided in Attachment 1.

We are proceeding with the removal of these non-traceable molded-case circuit breakers from our station stores to preclude use in safety-related systems.

As delineated in the February 17, 1989 NRC letter from Mr. F. J. Miraglia to Mr. W.

H. Rasin of NUMARC regarding clarification of NRC Bulletin 88-10, we have opted to proceed directly with the information collection for the molded-case circuit breakers installed in safety-related systems between August 1, 1983 and August 1, 1988 in lieu of testing. However, due to the resource requirements to support the outages at Surry Power Station, we are still in the process of collecting this information. It is our intention to replace any non-traceable molded-case circuit

  • breakers installed in our safety-related systems.

410 890403 990412000cK 05000:zso PDR

  • A

.. F'DC Q

\\

In addition to these ongoing efforts, we have evaluated our procurement

_*.:. proced_µres. an.d practice~ to, determi_n~ -.any-f~.ther., acti9ns, that should b~.. take~ Jo.,... _

. -*. ~-*enis-ii.re'"tJ:i.af 6:nl y **qualif1ed ::rriolded~case-- circuit" breaker's :are"* being main tairi-e"d as* :.'. -* ;. ':.

stored spares for future use in safety-related applications. To accomplish this, in the future we will only purchase circuit breakers for use in safety-related systems directly from an approved circuit breaker manufacturer or from an approved distributor that can certify direct traceability to a circuit breaker manufacturer. To provide an additional level of assurance, we will verify this traceability by audit or by other appropriate means.

Prior to restart, we will provide an updated summary of our non-traceable molded case circuit breakers and a schedule for the replacement of the non-traceable installed circuit breakers.

We anticipate establishing traceability for several molded-case circuit breakers currently identified as non-traceable at that time.

These completion dates identified in this letter have been discussed with Mr. B. C.

Buckley of your staff. The information contained herein is true and accurate to the best of my knowledge. Should you have any questions concerning this response please contact us.

cc:

  • U.S. Nuclear Regulatory Commission 101 Marietta Street, N.W.

Suite 2900 Atlanta, GA 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station

COMMONWEALTH OF VIRGINIA)

)

COUNTY OF HENRICO

)

The foregoing document was acknowledged before me, in and for the County and Commonwealth* aforesaid, today by W.

R. Cartwright who is Vice President -

Nuclear, of Virginia Electric and Power Company.

He is duly authorized to execute and file the foregoing document in beha 1 f of that Company, and the statements in the document are true to the best of his knowledge and belief.

this _3__ day of _

....... ( 4/1~%"'-"""""le""'-----' 19 1tl_.

-'-"""""~~-e~k~~"""/~-2-=-5~. _, 19 _1g__.

Acknowledged before me My Commission expires:

Notary Public (SEAL)

.. : *:.,::. -~... *.. -~.. :.. '.

'-'.... *.'. :_.. _:_ -~.. *... *.*** *.

ACTION PLAN RESPONSE TO NRC BULLETIN No. 88-10 NORTH ANNA POWER STATION 88-788B

1. STATION STORES Remove all non-traceable molded-case circuit breakers for use in safety-related systems from station stores by May 1, 1989.
2. PROCUREMENT ENGINEERING Revise appropriate procedures by May 8, 1989 to ensure circuit breakers for use in safety related systems are only purchased from an approved circuit breaker manufacturer or from an approved distributor that can certify direct traceability to a circuit breaker manufacturer.
3. CORPORATE QUALITY ASSURANCE Verify traceability of circuit breakers for use in safety-related systems by audit or by other *appropriate means.
4. PROCUREMENT ENGINEERING Provide an updated summary.of non-traceable molded case circuit breakers by May 8, 1989.
6. STATION LICENSING Provide a schedule for the replacement of and JCO for the non-traceable installed circuit breakers by May 8, 1989.

.\\

MOLDED-CASE -EAKER

. -C ATTACHMENT 1 LISTING; ~ON-TRACEABLE ATION STORES

  • r SURRY POWER STATION April 3. 1989 P.O... Number I.tern.

. Manufac.turer Vendor..,.*

.. Model Number Number.*

I unknown Square D 008260 4

SY 07636 Westinghouse Jarrett Electric JA3125W SY 014231 03 Westinghouse Electrical Suppliers(ES)

FB3125 0

SY 014231 07 Westinghouse ES & East Coast Pnl Board FB3015 9

SY 14386 07 Heineman Gammametrics 000222001 2

SY 123663 17 Westinghouse Electrical Suppliers EB3060 4

SY 137588 01 Square D ECK A18260 1

SY 137588 02 Square D ECK A1850AMP 1

SY 014231/018002 05/01 Westinghouse Electrical Suppliers FB3100 4

Tot~I Number ~