Informs of Mod Made to Instrument Range for RVLIS Dynamic Head Points to Expand Range in Order to Prevent Spurious Alarms Which Resolves North Anna Emergency Response Facility Problem Rept
ML18153B363
Person / Time
Site: Surry, North Anna  
Issue date: 11/02/1993
From: Bowling M
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
93-675, NUDOCS 9311120020
Download: ML18153B363 (15)


Text

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 November 2, 1993 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 NORTH ANNA POWER STATION UNITS 1 AND 2 EMERGENCY RESPONSE DATA SYSTEM DATA BASE UPDATES Serial No.

NL&P/CGL Docket Nos.

License Nos.93-675 RO 50-280 50-281 50-338 50-339 DPR-32 DPR-37 NFP-4 NFP-7 Modifications were recently made to the instrument range for the Reactor Vessel Level Instrumentation System (RVLIS) dynamic head points. The upper instrument limits were modified slightly to expand the range in order to prevent spurious alarms. The changes were made to resolve a recent North Anna Emergency Response Facility problem report. Since the potential for this problem also exists at Surry, the changes were made at both stations and are detailed in the Data Point Library (DPL) revision summaries (change reports) contained in Attachments 1 and 2 for Surry Units 1 and 2 and North Anna Units 1 and 2, respectively. Attachments 3 and 4 provide revision summaries (change reports) for the affected points for Surry Units 1 and 2 and North Anna Units 1 and 2, respectively. The updated data base files are also provided in the dBase IV format on Attachment 5.

If you have questions regarding this information, please contact us.

Very truly yours, fi;J~

M. L. Bowling, Manager Nuciear Licensing & Programs Attachments:

1. Updated DPL Forms for Surry Units 1 and 2
2. Updated DPL Forms for North Anna Units 1 and 2
3. DPL Revision Summaries for Surry Units 1 and 2
4. DPL Revision Summaries for North Anna Units 1 and 2
5. Updated DPL Data Base Files for Surry and North Anna in dBase IV Format 9311120020 931102 PDR ADOCK 05000280 F

PDR

cc:

U. S. Nuclear Regulatory Commission - Attachments 1 - 4 Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. M. W. Branch - Attachments 1 - 4 NRC Senior Resident Inspector Surry Power Station Mr. R. D. McWhorter - Attachments 1 - 4 NRC Senior Resident Inspector North Anna Power Station NUS Corporation/ El Division - Attachments 1 - 5 P. 0. Box 59736 Idaho Falls, Idaho 83405 Attention: Mr. Tony LaRosa

e ATTACHMENT 1 UPDATED DPL FORMS FOR SURRY UNITS 1 AND 2

DATE:

REACTOR UNIT:

DATA FEEDER:

NRG ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

'j'"

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

10/20/93 SUl N/A REAC VES LEV L1RC003C STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE RVLIS DYNAMIC HEAD LEVEL REACTOR VESSEL WATER LEVEL A

PCT N/A 0.0 122.0 TNKBOT N/A p

5 AVERAGE - SEE SYSTEM DESCRIPTION HEAD VENT (TOP) & BOTTOM OF VESSEL VARIABLE N/A N/A N/A WET The 2 reactor dynamic head level signals are used in conjunction with the reactor coolant pump motor currents to calculate this value.

The dynamic head readings are invalid if no RCP's are running; therefore, this process value will be set invalid if no RCP motor current is greater than 5% of it's full load value.

If none of the RCP's are running, the average of the valid dynamic head level signals is used to calculate this point.

PRINTED 10/20/93

I-'

I N

DATE:

REACTOR UNIT:

DATA FEEDER:

NRG ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

10/20/93 SU2 N/A REAC VES LEV L2RC003C STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE RVLIS DYNAMIC HEAD LEVEL REACTOR VESSEL WATER LEVEL A

PCT N/A 0.0 122.0 TNKBOT N/A p

5 AVERAGE -

SEE SYSTEM DESCRIPTION HEAD VENT (TOP) & BOTTOM OF VESSEL VARIABLE N/A N/A N/A WET The 2 reactor dynamic head level signals are used in conjunction with the reactor coolant pump motor currents to calculate this value.

The dynamic head readings are invalid if no RCP's are running; therefore, this process value will be set invalid if no RCP motor current is greater than 5% of it's full load value.

If none of the RCP's are running, the average of the valid dynamic head level signals is used to calculate this point.

PRINTED 10/20/93

ATTACHMENT 2 UPDATED DPL FORMS FOR NORTH ANNA UNITS 1 AND 2

N I

I-'

DATE:

REACTOR UNIT:

DATA FEEDER:

NRG ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

10/20/93 NAl N/A REAC VES LEV LlRC003C STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE RVLIS DYNAMIC HEAD LEVEL REACTOR VESSEL WATER LEVEL A

PCT N/A 0.0 122.0 TNKBOT N/A p

5 AVERAGE - SEE SYSTEM DESCRIPTION HEAD VENT (TOP) & BOTTOM OF VESSEL VARIABLE N/A N/A N/A WET The 2 DYNAMIC HEAD level signals are used in conjunction with the reactor coolant pump (RCP) breaker statuses to calculate this value.

The dynamic head readings are invalid if no RCP's are running; therefore, this point will be set invalid if no RCP breakers are closed.

If any of the RCP breakers are closed, the average of the valid dynamic head level signals is used to calculate this point.

PRINTED 10/20/93

DATE:

REACTOR UNIT:

DATA FEEDER:

NRG ERDS PARAMETER:

POINT ID:

PIANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

AI.ARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N NI DETECTOR POWER SUPPLY r!..,

TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

10/20/93 NA2 N/A REAC VES LEV L2RC003C STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE RVLIS DYNAMIC HEAD LEVEL REACTOR VESSEL WATER LEVEL A

PCT N/A 0.0 122.0 TNKBOT N/A p

5 AVERAGE - SEE SYSTEM DESCRIPTION HEAD VENT (TOP) & BOTTOM OF VESSEL VARIABLE N/A N/A N/A WET The 2 DYNAMIC HEAD level signals are used in conjunction with the reactor coolant pump (RCP) breaker statuses to calculate this value.

The dynamic head readings are invalid if no RCP's are running; therefore, this point will be set invalid if no RCP breakers are closed.

If any of the RCP breakers are closed, the average of the valid dynamic head level signals is used to calculate this point.

PRINTED 10/20/93

e ATTACHMENT 3 DPL REVISION SUMMARIES FOR SURRY UNITS 1 AND 2

w I.....

STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT LlRG003C AT 08:21 ON 10/20/93.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 05/20/91 IS: 10/20/93 WAS: 120.0 IS: 122.0 PRINTED 10/20/93

w I

N STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L2RC003C AT 08:22 ON 10/20/93.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 05/20/91 IS: 10/20/93 WAS: 120.0 IS: 122.0 PRINTED 10/20/93

ATTACHMENT 4 DPL REVISION SUMMARIES FOR NORTH ANNA UNITS 1 AND 2

STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L1RG003G AT 08:20 ON 10/20/93.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 03/21/91 IS: 10/20/93 WAS: 120.0 IS: 122.0 PRINTED 10/20/93

-Po I

N STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE.

CHANGE REPORT CHANGED POINT L2RC003C AT 08:21 ON 10/20/93.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 03/21/91 IS: 10/20/93 WAS: 120.0 IS: 122.0 PRINTED 10/20/93

e ATTACHMENT 5 UPDATED DPL DATA BASE FILES FOR SURRY AND NORTH ANNA IN dBASE IV FORMAT (Diskette to NUS Corporation / El Division)