ACCELERATEa DOCUMENT DISTRDWTION SYSTEM REGULATO,., INFORMATION DISTRIBUTION~~TEM (RIDS)

ACCESSION~1R:9407050194 DOC.DATE: 94/06/24 NOTARIZED: NO FACIL:SQ~281 Surry Power Station, Unit 2, Virginia Electric & Powe AUTH.NAME AUTHOR AFFILIATION BOWLING,M.L.

Virgin~a Power (Virginia Electric & Power Co.)

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Forwards emergency response data sys & data base updates.

Updated data base files provided in dBase IV format on also.

DOCKET#

05000281 DISTRIBUTION GODE: A026D COPIES RECEIVED:LTR '

ENCL 1 TITLE: Emergency Response Data System (ERDS)

SIZE: ---+-/..... 0~-

R I

D s

NOTES:lcy NMSS/STSB/PM.

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL AEOD/IRB 01 2

2 NRR/PD3-2 1

1 BUCKLEY,B 1

1 INTERNAL: ACRS 1

1 AEOD 1

1 AEOD/DOA/IRB 1

1 NRR;!J~S10:PEPB 1

1 OC/LFDCB 1

0 RGN2 ERC 1

1

'RE FIL;ILE 1

1 EXTERNAL: NRC PDR 1

1 NOTES:

1 1

NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 504-2065) TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 14 ENCL 13 05000281 /

A D

D s

R I

D s

I A

D D

s

e VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 June 29, 1994 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SUJRRY POWER STATION UNIT 2 EMERGENCY RESPONSE DATA SYSTEM DATA BASE UPDATES Serial No.

NL&P/CGL Docket Nos.

License Nos.

94-195A RO 50-281 DPR-37 Modifications were recently made to the instrument range for the auxiliary feedwater flow points for Surry Unit 2. As part of the outage-related design change package associated with the Control Room Design Review modifications, the auxiliary feedwater flow range has been expanded from O - 350 gpm to O - 400 gpm. These modifications are identical to the Unit 1 changes you were advised of by an April 12, 1994 letter (Serial No.94-195). The changes are detailed in the Data Point Library (DPL) reference file forms contained in Attachment 1. Attachment 2 provides revision summaries (change reports) for the affected points for Surry Unit 2.

  • The updated data base files are also provided in the dBase IV format on Attachment 3.

If you have questions regarding this information, please contact us.

Very truly yours,

//Al/2~

M. L. Bowling, Manager Nuclear Licensing & Programs Attachments:

1. Updated DPL Forms for Surry Unit 2
2. DPL Revision Summaries for Surry Unit 2
3. Updated DPL Data Base Files for Surry Unit 2 in dBase IV Format

,-..-.,~

l ;_; \\.,:.~ :.(~

9407050194 940629 PDR ADOCK 05000281 P

cc:

U. S. Nuclear Regulatory Commission - Attachments 1 and 2 Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. M. W. Branch - Attachments 1 and 2 NRC Senior Resident Inspector Surry Power Station NUS Corporation I El Division - Attachments 1 - 3 P. 0. Box 59736 Idaho Falls, Idaho 83405 Attention: Mr. Tony LaRosa

ATTACHMENT 1 UPDATED DPL FORMS FOR SURRY UNIT 2

PRINTED 06/16/94 DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 06/16/94 SU2 N/A AX FD FL 1/A F2FW001A SG A AFW FLOW (RD)

STM GEN A AUX FEEDWATER FLOW A

GPM 0 -

515" H20 0.0 400.0 N/A N/A s

N/A N/A - THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN A VARIABLE N/A N/A N/A N/A Senses auxiliary feedwater flow to steam generator A.

e

I-'

I N

PRINTED 06/16/94 DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 06/16/94 SU2 N/A AX FD FL 2/B F2FW002A SG B AFW FLOW (WT)

STM GEN B AUX FEEDWATER FLOW A

GPM 0 -

515" H20 0.0 400.0 N/A N/A s

N/A N/A -

THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN B VARIABLE N/A N/A N/A N/A Senses auxiliary feedwater flow to steam generator B.

PRINTED 06/16/94 DATE:

REACTOR UNI'l;':

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 06/16/94 SU2 N/A AX FD FL 3/C F2FW003A SG C AFW FLOW (BL)

STM GEN C AUX FEEDWATER FLOW A

GPM 0 -

515" H20 0.0 400.0 N/A N/A s

N/A N/A - THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN C VARIABLE N/A N/A N/A N/A Senses auxiliary feedwater flow to steam generator C.

ATTACHMENT 2 DPL REVISION SUMMARIES FOR SURRY UNIT 2

N I......

STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW001A AT 10:46 ON 06/16/94.

CHANGES WERE AS FOLLOWS:

DATE:

WAS: 03/29/94 IS: 06/16/94 ENGR UNITS CONVERSION:

WAS: 0 -

394" H20 IS: 0 - 515 II H20 MAXIMUM INSTR RANGE:

WAS: 350.0 IS: 400.0 PRINTED 06./16/94

N I

N STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW002A AT 10:46 ON 06/16/94.

CHANGES WERE AS FOLLOWS:

DATE:

WAS: 03/29/94 IS: 06/16/94 ENGR UNITS CONVERSION:

WAS: 0 -

394" H20 IS: 0 -

515" H20 MAXIMUM INSTR RANGE:

WAS: 350.0 IS: 400.0 PRINTED 06/16/94

.I

N I w STATION: Surry UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW003A AT 10:47 ON 06/16/94.

CHANGES WERE AS FOLLOWS:

DATE:

WAS: 03/29/94 IS: 06/16/94 ENGR UNITS CONVERSION:

WAS:

0 -

394" H20 IS: 0 -

515" H20 MAXIMUM INSTR RANGE:

WAS: 350.0 IS: 400.0 PRINTED 06/16/94 r

'.~

..