ML18153A403

From kanterella
Jump to navigation Jump to search
Submits Mods to ERDS Points,Necessary as Result of Plant Design Change.Updated Data Base Files,Documented in Attachments 1 & 2,also Provided in Dbase IV Format as Attachment 3
ML18153A403
Person / Time
Site: Surry  Dominion icon.png
Issue date: 05/01/1997
From: Sarver S
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
97-275, NUDOCS 9705090111
Download: ML18153A403 (14)


Text

_,...:.. ---*

VIRGINIA ELECTRIC AND PowER COMPANY RICHMOND, VIRGINIA 23261 May 1, 1997 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Gentlemen:

. Docket No.

50-280 50-281 License No. DPR-32 DPR-37 In accordance. with 10 CFR 50 Appendix E, Section Vl.3.a, we are. submitting modifications to five Emergency Response Data System (EROS) points which were

. necessary as a result of a Surry design change. The instrument ranges for five Unit 1 radiation monitor points were modified. The changes are detailed in the Data Point Library (DPL) reference file forms in Attachment 1. Attachment 2 provides the revision summary (change report) for the affected points.

The updated data base files, documented in Attachments 1 and 2, are also provided in the dBase IV format as.

Should you require additional information, please contact us.

Very truly yours,

. S. P. Sarver, Acting Manager Nuclear Licensing and Operations Support Attachments

1.

1 Surry Updated Data Point Library Reference File Sheet

2. Revision Summary
3. Updated DPL Data Base Files in dBase Format (NUS copy only)

- - ------~---- ---------- ----~--------

9705090111 970501 PDR ADOCK 05000280 F

  • PDR 000055 111111111111111111111111111 {11111m tf,r-I

cc:

US Nuclear Regulatory Commission (Attachments 1 and 2)

Region II Atlanta Federal Center 61 Forsyth St., SE, Suite 23T85 Atlanta, GA 30303 Mr. A. A. Musser (Attachments 1 and 2)

NRC Senior Resident Inspector Surry Power Station NUS Corporation/ El Division (Attachments 1, 2, and 3)

P. 0. Box59736 Idaho Falls, Idaho 83405 Attention: Mr. Tony LaRosa

ATTACHMENT 1 COMMON UPDATED DATA POINT LIBRARY REFERENCE FILE SHEETS

. SORRY POWER STATION UNITS t AND 2

DP.TE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGB:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

  • SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 04/22/97 SUl N/A RCS LTDN RAD RlRM201C RCS LETDOWN LR (119)

RAD LEVEL OF RCS LETDOWN LINE A

CPM N/A 10.0 l.OE7 N/A N/A p

1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT AUX BLDG, 27' LVL OUTSIDE WALL-SAMPLE RM VARIABLE N/A N/A N/A N/A PRINTED 04/22/97

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT-DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

.MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOw PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY

. TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

STATION: su:c:ry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE ' :

  • 04/22/97.

SUl N/A RCS LTDN, RAD RlRM202C*

RCS LETDOWN HR (118)

RAD LEVEL OF RCS LETDOWN LINE A

CPM N/A 10.0 l.OE7 N/A N/A p

1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT AUX BLDG*, 27' LVL OUTSIDE WALL-SAMPLE RM VARIABLE N/A N/A N/A N/A

),*..

PRINTED 04/22/97

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:.

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL R~FERENCE LEG:

UNIQUE 3YSTEM DESC:

STATION: Surry,,_

UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE_

04/22/97 SUl N/A SG BD RAD lA R1RM215C SG BLOW DOWN (112)

STM GEN A-SLOWDOWN RAD LEVEL A

CPM N/A 10.0 1.0E7 N/A N/A p

1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURBINE BLDG BASEMENT BY EMERG SWG ROOM VARIABLE N/A N/A N/A N/A

-PRINTED 04/22/97

DATE:

REACTOR UNIT:

DATA FEEDER:

  • NRC EROS PARAMETER:

POINT ID:

PLA..'IT SPEC POINT DESC:

GENERIC/COND DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER S~PLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITl'ERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 04/22/97 SUl N/A SG DB RAD lA RlRM216C SG BLOW DOWN (113)

STM GEN A BLOWDOWN RAD LEVEL A

CPM N/A 10.0 l.OE7 N/A N/A p

1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURBINE ~LDG BASEMENT BY EMERG SWG ROOM VARIABLE N/A N/A N/A N/A 04/22/97

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

  • PLANT SPEC POINT DESC:

GENERIC/COND DESC:

  • ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SETPOINTS:

NI DETECTOR POWER SUPPLY CUT~OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER.LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UN~QUE SYSTEM DESC:

04/22/97 SUl N/A COND A/E RAD R1RM217C STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CONDENSER AE (111)

COND AIR EJECTOR RADIOACTIVITY A

CPM N/A 1.0El l.OE7 N/A N/A p

1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURBINE BLDG MEZZANINE OVERHEAD BY AE VARIABLE N/A N/A N/A N/A PRINTED 04/22/97

I I

ATTACHMENT 2 REVISION

SUMMARY

SURRY POWER STATION UNITS 1 AND 2 I

Page No.

1 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM201C AT 14:40 ON 04/22/97.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 05/20/91 IS: 04/22/97 WAS: 1.0E6 IS: l.OE7 PRINTED 04/22/97

Page No.

2 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM202C AT 14:40 ON 04/22/97.

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR R.;.NGE:

WAS: 05/20/91 IS: 04/22/97 WAS: l.OE6 IS: l.OE7 PRINTED 04/22/97

Page No.

3 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM215C AT 14: 40 ON 04/22/97..

CHANGES WERE AS FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 05/20/91 IS: 04/22/97 WAS: 1.0E6 IS: 1.0E7 PRINTED 04/22/97 I

Page NJ.

4 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R1RM216C AT 14:41 ON 04/22/97.

CHANGES WERE AS. FOLLOWS:

DATE:

MAXIMUM INSTR RANGE:

WAS: 05/20/91 IS: 04/22/97 WAS: 1.0E6 IS: 1. OE7 PRINTED 04/22/97

Page No.

5 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM217C AT 14:41 ON 04/22/97.

CHANGES WERE AS FOLLOWS:

DATE:

WAS: 11/25/92 IS: 04/22/97 MINIMUM INSTR RANGE:

WAS: 3.162 IS: l.OEl MAXIMUM INSTR RANGE:

WAS: 1.0E6 IS: l.OE7

~.

PRINTED 04/22/97