ML18152B784

From kanterella
Jump to navigation Jump to search
Forwards Valve Info,Where Available,In Response to 980529 RAI Re Resolution of GSI 165, Spring-Actuated Safety & Relief Valve Reliability
ML18152B784
Person / Time
Site: Surry  Dominion icon.png
Issue date: 08/03/1998
From: Mccarthy J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-GTECI-*****, REF-GTECI-NI, TASK-*****, TASK-OR 98-343, NUDOCS 9808100245
Download: ML18152B784 (4)


Text

e e

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 August 3, 1998 Document Control Desk United States Nuclear Regulatory Commission Washington, D. C. 20555

. Serial No.

NLOS/GDM Docket Nos.98-343 R2 50-280 50-281 License Nos. DPR-32 DPR-37 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 GENERIC SAFETY ISSUE (GSI) 165-SPRING-ACTUATED SAFETY AND RELIEF VALVE RELIABILITY REQUEST FOR ADDITIONAL INFORMATION In a May 29, 1998 letter, the NRC requested Virginia Electric and Power Company to provide data for certain valves located in the Low Head Safety Injection System and the Emergency Diesel Generator air supply system. The information is required to support the NRC's resolution of GSl-165 which addresses whether failures of spring-actuated relief valves in safety-related support systems have the potential to cause substantial increases in plant core damage frequency. The requested valve information, where available, is provided in the attachment.

If you have any questions regarding this information, please contact us.

Very truly yours, Attachment Commitments made by this letter: None

cc:

U.S. Nuclear Regulatory Commission

  • Region II Atlanta Federal Center 61 Forsyth Street, SW Suite 23T85 Atlanta, Georgia 30303 Mr. R. A. Musser NRC Senior Resident Inspector Surry Power Station

e ATTACHMENT RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION GENERIC SAFETY ISSUE 165 Virginia Electric and Power Company Surry Power Station Units 1 and 2

Item Drawing Valve ID LPI pump 11448-CMB-1-SI RV-discharge 089A-3 sh 2/3 1845A SRVs LPI pump 11448-CMB-1-SI RV-discharge 089A-3 sh 2/3 1845B SRVs LPI pump 11448-CMB-1-SI RV-discharge 089A-3 sh 2/3 1845C SRVs I

EOG air tank 11448-FB-046A 1-EG RV-12 SRVs sh,1/3 EOG air tank 11448-FB-046A 1-EG-3**

isolation valve sh:1/3 Orifice size or rated flow at rated pressure.

    • This is a manual ball valve.
      • Supplier Relief Valve Information Manufacturer Model Orifice Set Size*

Pressure Crosby JRAKSPEC B 1.8 GPM 242 PSIG 0.75" X 1.0" DWG H-50909 Crosby JRAKSPEC B 1.8 GPM 242 PSIG 0.75" X 1.0" DWG H-50909 Crosby JRAKSPEC B 1.8 GPM 242 PSIG 0.75" X 1.0" DWG H-50909 Dresser Industrial 15430-XMYI 464 CFM 225 PSIG Valve Engine Systems, 8409024

~1.5in N/A Inc.***

e