e e VIRGINIA ELECTRIC AND PowER COMPANY RICHMOND, VIRGINIA 23261 June 6, 1991 United States Nuclear Regulatory Commission Serial No.90-681 C Attention: Document Control Desk NO/RBP RO Washington, D. C. 20555 Docket Nos. 50-280 50-281 50-338 50-339 License Nos. DPR-32 DPR-37 NPF-4 NPF-7 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 NORTH ANNA POWER STATION UNITS 1 AND 2 EMERGENCY RESPONSE DATA SYSTEM NRC letter dated October 25, 1990 contained a survey requesting detailed hardware, communications, data point, and administrative information to assist the NRC's contractor in designing Emergency Response Data System (EROS) interfaces. In our letter dated April 11, 1991, Virginia Electric and Power Company submitted this requested information for North Anna Power Station and a partial listing of this information for Surry Power Station. Corrections have been made to some of the North Anna data base records that were previously transmitted in the April submittal.

These corrections include some typographical errors and some corrections made as a result of discussions with the NRC's EROS contractor. This letter forwards the remaining survey information and data point library for Surry Power Station as well as corrected North Anna data point library information as summarized in Attachment A.

Attachment B contains the detailed information.

t If you have any questions concerning this matter, please contact us.

Very truly yo s, V,J. L. S t e ~

Senior Vice President - Nuclear Attachments A. Emergency Response Data System Implementation Survey Responses

8. Detailed information of Attachment A *

(-~,;;;;-;-.-:-:-:-.-=c=-

*~~ 10612027:"=: 910606 -:,\

~DR ADOCJ<: 050002:::0 PDR

e cc: U. S. Nuclear Regulatory Commission Attachment A only Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. M. Branch Attachment A only NRC Senior Resident Inspector Surry Power Station Mr. M. S. Lesser Attachment A only NRC Senior Resident Inspector North Anna Power Station NUS Corporation / El Division P.O. Box 50736 Idaho Falls, Idaho 83405 Attention : Mr. Tony LaRosa

50-280/281/338/339 SURRY & NORTH ANNA VEPCO EMERGENCY RESPONSE DATA SYSTEM REC'D W/LTR DTD 06/06/91. ... 9106120273

~NOTICE-THE ATTACHED FILES ARE OFFICIAL

- RECORDS OF THE INFORMATION &

REPORTS MANAGEMENT BRANCH.

THEY HAVE BEEN CHARGED TO YOU FOR A LIMITED TIME PERIOD AND -

MUST BE RETURNED TO THE RE-CORDS & ARCHIVES SERVICES SEC-TION P1-22 WHITE FLINT. PLEASE DO NOT SEND DOCUMENTS CHARGED OUT THROUGH THE MAIL. REMOVAL OF ANY PAGE(S) FROM DOCUMENT FOR REPRODUCTION MUST BE RE-FERRED TO FILE PERSONNEL.

-NOTICE-

ATTACHMENT A

ATIACHMENT A NORTH ANNA ANP SURRY POWER STATION EMERGENCY RESPONSE DATA SYSTEM IMPLEMENTATION NRC SURVEY RESPONSES Attachment B contains the following information:

1. Completed Data Point Library (DPL} forms indicating the characteristics of the process loop values we intend to transmit for Surry Unit 1.
2. _ Completed DPL forms indicating the characteristics of the process loop values we intend to transmit for Surry Unit 2.
3. Updated DPL forms indicating the characteristics of the process loop values we intend to transmit for North Anna Unit 1.
4. Updated DPL forms indicating the characteristics of the process loop values we intend to transmit for North Anna Unit 2.
5. Revision history detailing the changes made to the North Anna DPL's
6. A 1.44 megabyte - 3.5 inch floppy diskette containing the data base files for the DPL's addressed in Attachments 1 - 4 above.

--* The dBase IV files contained on this diskette are as follows:

File Name SU1_ERDS.DBF Description Surry Unit 1 DPL dBase file.

SU1_ERDS.D8T Surry Unit 1 dBase memo file for DPL unique system description field.

  • SU2 ERDS.DBF Surry Unit 2 DPL dBase file SU2 EROS.DST Surry Unit 2 dBase memo file for DPL unique system description field.

. NA1_ERDS;D8F North Anna Unit 1 DPL dBase file NA1_ERDS.DBT North Anna Unit 1 dBase memo file for DPL unique

  • system description field.

NA2_ERDS.DBF North Anna Unit 2 DPL dBase file.

NA2_ERDS.D8T North Anna Unit 2 dBase memo file for DPL unique system description field .

ATTACHMENT B

  • ATTACHMENT 1 SURRY DATA UNIT 1 POINT LI_BRARY LISTINGS

Page No. STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: RCS CHG/MU POINT ID: F1CH003A PLANT SPEC POINT DESC: CHARGING LOOP FLOW (BL)

GENERIC/COND DESC: PRIM SYS CHARGING OR MAKEUP FLOW ANALOG/DI GIT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0

  • 393.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 150.0 ZERO P91NT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER.OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHARGING LINE UPSTRM OF REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Flow transmitter FT-1122 transmits a signal to a controller Located in the control cabinets, and to a flow indicator in the ma.in control room. The control Ler operates the charging water flow control valve CFCV-1122) to maintain a preset charging flow in conjunction with a signal from the pressurizer Level instrumentation. The two signals maintain pressurizer Level within the proscribed band and Limit the minimum and maximum charging flow rates

  • Page No. 2 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: RCS LTDN RAD POiNT ID: F1CH004A PLANT SPEC POINT DESC: LOW PRESSURE LETDOWN FLOW CWT)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 400" H20 MINIMUM INST~ RANGE: 0.0 MAXIMUM INSTR RANGE: 150.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LETDOWN LINE DWNSTRM OF NON-REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides indication of letdown stream flow rate in the Control Room

  • Page No. 3 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: BWST LEVEL POINT ID: L1CS001C PLANT SPEC POINT DESC: RWST LEVEL GENERIC/COND DESC: BORATED WATER STORAGE TANK LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 3997 GALLONS MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 13500 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: MINUMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RWST ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: DRY UNIQUE SYSTEM DESC: Indicates the level in the RWST. The lowest valid signal is used. If none of the 4 signals is val id, this point is marked invalid

  • Page No. 4 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT SMP WR POINT ID: L1DA001C PLANT SPEC POINT DESC: CONTAINMENT WR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP WR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION: 1 FT= 58343 GALLONS MINIMUM INSTR RANGE: 0.43 MAXIMUM INSTR RANGE: 9.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RECIRC SPRAY SUMP-SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI PETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid wide range signals are averaged (2 signals if all are valid). _If neither signal is valid, this point is marked invalid

  • Page No. 5 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT SMP NR POINT ID: L1DA002C PLANT SPEC POINT DESC: CONTAINMENT NR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP NR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: INCH ENGR UNITS CONVERSION: 1 IN= 2369 GALLONS MINIMUM INSTR RANGE: 4.5 MAXIMUM INSTR RANGE: 26.5 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 280 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CONTAINMENT SUMP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment sump Level and provides a high Level alarm. The largest valid narrow range signal is used for this point. If all signals are valid, 2 signals are considered. If both signals are invalid, this point is marked invalid .

Page No. 6 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 1/A POINT ID: F1FW001A PLANT SPEC POINT DESC: SG A AFW FLOW (RD)<>

GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 394 11 H20 MINIMUM INSTR RANGE: a.a MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR PO\JER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator A.

Page No. 7 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 2/B POINT ID: F1FW002A PLANT SPEC POINT DESC: SG B AFW FLOW (WT)<>

GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/0 I GIT AL: A ENGR UNITS/DIG *sTATES: GPM ENGR UNITS CONVERSION: 0 - 394 11 H20 MINIMUM INSTR RANGE: 0.0

  • MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED_: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator B.

Page No. 8 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 3/C POINT ID: F1FW003A PLANT SPEC POINT DESC: SG C AFW FLOW (BL) <>

GENERIC/COND DESC: STM GEN C AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 394 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator C.

Page No. 9 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 1/A POINT ID: F1FW005C PLANT SPEC POINT DESC: SG A MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN A MAIN FEEDWATER FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0 - 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator A.

.The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used

  • Page No. 10 STATION: Surry 05/21/91 UNIT: 1 PWR OATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: MN FD FL 2/B POINT ID: F1FW006C PLANT SPEC POINT DESC: SG B MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN B MAIN FEEDWATER FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0 - 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator B.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used .

Page No. 11 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 3/C POINT ID: F1FW007C PLANT SPEC POINT DESC: SG C MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN C MAIN FEEDWATER FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0 - 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2.

HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater Line to steam generator C.

The average of the valid feed flow signals is used for this point . .If all signals are valid, 2 signals will be used .

Page No. 12 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 1/A POINT ID: L1FW004A PLANT SPEC POINT DESC: SG A WR LEVEL CWT)<>

GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1A.

Page No. 13 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 2/B POINT ID: L1FW008A PLANT SPEC POINT DESC: , SG B WR LEVEL (BL) <>

GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1B.

Page No. 14 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 3/C POINT ID: L1FW012A PLANT SPEC POINT DESC: SG C WR LEVEL (YW) <>

GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PQ\,/ER SUPPLY CUT-OFF PQ\,/ER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water Level in steam generator 1C .

Page No. 15 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 1/A POINT ID: L1FW001C PLANT SPEC POINT DESC: STEAM GENERATOR A LEVEL GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828 11 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1A. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid

  • Page No. 16 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 2/B POINT ID: L1FW002C PLANT SPEC POINT DESC: STEAM GENERATOR B LEVEL GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828 11 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1B. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 17 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L1FW003C PLANT SPEC POINT DESC: STEAM GENERATOR C LEVEL GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828 11 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1C. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 18 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: H2 CONC POINT ID: A1GW001C PLANT SPEC POINT DESC: CNTMT H2 CONCENTRATION GENERIC/COND DESC: CONTAINMENT HYDROGEN CONC ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: AUX BLDG 13' LVL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR. POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Takes a sample of containment atmosphere and measures the hydrogen concentration in the sample. The valid signals are averaged (2 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 19 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT PRESS POINT ID: P1LM001C PLANT SPEC POINT DESC: CONTAINMENT PRESSURE GENERIC/COND DESC: CONTAINMENT PRESSURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PSIA ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CABLE PENETRATION AREA IN AUX BLDG ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses reactor containment pressure. The valid intermediate range signals (4 signals if all are valid) are averaged. If no intermediate range signals are valid, the average of the wide range signals is used (2 signals if all are valid). If no signals are valid, this point is marked invalid .

Page No. 20 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT TEMP POINT ID: T1LM001C PLANT SPEC POINT DESC: CONTAINMENT TEMPERATURE GENERIC/COND DESC: CONTAINMENT TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: so.a MAXIMUM INSTR RANGE: 300.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: REACTOR CONTAINMENT ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses reactor contairvnent temperature. The valid signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

Page No. 21 STATION: Surry 05/21/91 -

UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 1/A POINT ID: P1MS001C PLANT SPEC POINT DESC: SG A PRESSURE GENERIC/COND DESC: STEAM GENERATOR A PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator 1A to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is-marked invalid .

Page No. 22 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 2/8 POINT ID: P1MS002C PLANT SPEC POINT DESC: SG B PRESSURE GENERIC/COND DESC: STEAM GENERATOR B PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: o.o MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION

. SENSOR LOCATIONS: OUTPUT OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator 18 to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid

  • Page No. 23 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS 3/C POINT ID: P1MS003C PLANT SPEC POINT DESC: SG C PRESSURE GENERIC/COND DESC: STEAM GENERATOR C PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION:* N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator 1C to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 24 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: NI SOURC RNG POINT ID: M1NM001C PLANT SPEC POINT DESC: SOURCE LEVEL POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, SOURCE RNG ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPS ENGR UNITS CONVERSION: Approximately 1e*9 - 1e-3 % Power MINIMUM INSTR RANGE: 1.0EO MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMIM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: 1e-10 AMPS .IR

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

<1e-10 AMPS IR N/A N/A UNIQUE SYSTEM DESC: NI cut_off requires the listed reading on either of the intermediate range instruments and NI cut_on requires the listed reading on both of the intermediate range instruments CIR is on the intermediate range power scale). The highest valid source range signal is used for this point. 2 source range signals are available for use. If neither of the source range signals is valid, this point is marked invalid.

The source range inputs are logrithmic in nature.

Therefore, the highest valid source range signal is exponentiated to yield the value for this point .

Page No. 25 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: NI INTER RNG POINT ID: M1NM003C PLANT SPEC POINT DESC: INTERMEDIATE RANGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, INT RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: AMPS ENGR UNITS CONVERSION: Approximately 3e 120 % Power MINIMUM INSTR RANGE: 1 . OE-11 MAXIMUM INSTR RANGE: 1.0E-3 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOY PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION.

SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POYER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The highest valid intermediate range signal is used for this point. 2 intermediate range signals are available for use.

If neither of the intermediate range signals is valid, this point is marked invalid. The intermediate range inputs are logrithmic in nature. Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point

  • Page No. 26 STATION: Surry 05/21 /91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: NI POWER RNG POINT ID: M1NMOOSC PLANT SPEC POINT DESC: POWER RANGE AVERAGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, POWER RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid power range signals are averaged for this point.

4 power range signals are available for use. If none of the power range signals is valid, this point is marked invalid .

Page No. 27 STATION: Surry 05/21/91 UNIT: '1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CORE FLOW POINT ID: F1RC004C PLANT SPEC POINT DESC: AVERAGE RCS LOOP FLOW GENERIC/COND DESC: TOTAL REACTOR FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 460 11 H20 MINIMUM INSTR RANGE: o:o MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 9 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN DISCHARGE UPSTRM OF RCP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the flow of coolant from the steam generator to the reactor coolant pump. The average of the 3 loop calculated average flows is used for this point. The 3 loop average values are calculated by taking the average of the valid flow signals for each loop. If all loop flow signals are valid, 3 flow readings will be used for each loop

  • Page No. 28 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F1RC005C PLANT SPEC POINT DESC: TOT COLD LEG HHS! FLOW GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1800.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: SUM* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CHRGING PMP DISCH UPSTRM OF COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHS!

pu11ps to the cold leg of each loop. The 3 loop high head SI flows are totaled for this value. If any one of the loop SI values is invalid, this point will be marked invalid

  • Page No. 29 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: REAC VES LEV POINT ID: L1RC001C PLANT SPEC POINT DESC: REAC VSL FULL RANGE LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT-

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: The 2 reactor full range level signals are used in conjunction with the reactor coolant pump motor currents to calculate this value. The full range readings are invalid if any RCP is running; therefore, this process value will be set invalid if any RCP motor current is greater than 5% of it's full Coad value. If none of the RCP's are running, the average of the valid full range level signals is used to calculate this point.

Page No. 30 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: PRZR LEVEL POINT ID: L1RC002C PLANT SPEC POINT DESC: PRESSURIZER LEVEL GENERIC/COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 3.60 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: PRESSURIZER-HP LOCATED 30.0 1 ABOVE LP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI .DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses pressurizer level and provides alarm and control function inputs when the plant is operating normally. The valid signals are averaged (3 signals if all are valid). If none of the signals are valid, this point is marked invalid .

Page No. 31 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: REAC VES LEV POINT ID: L1RC003C PLANT SPEC POINT DESC: RVLIS DYNAMIC HEAD LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE-COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: The 2 reactor dynamic head level signals are used in conjunction with the reactor coolant pump motor currents to calculate this value. The dynamic head readings are invalid if no RCP 1 s are running; therefore, this process value will be set invalid if no RCP motor current is greater than 5% of it's full load value. If none of the RCP's are running, the average of the valid dynamic head level signals is used to calculate this point

  • Page No. 32 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: RCS PRESSURE POINT ID: P1RC001C PLANT SPEC POINT DESC: RCS AVERAGE PRESSURE GENERIC/COND DESC: REACTOR COOLANT SYSTEM PRESSURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 3000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI .DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: PT-1455, PT-1456, and PT-1457 all measure pressurizer pressure (narrow range) and are used for pressurizer pressure protection. The valid narrow range signals are averaged (3 signals if all are valid). If none of the narrow range signals valid, the average of the valid wide range signals is used (2 signals if all are valid). If none of the narrow or wide range signals is valid, this point is marked invalid

  • Page No. 33 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 1/A POINT ID: T1RC004A PLANT SPEC POINT DESC: LOOP A WR T COLD (RD)<>

GENERIC/COND DESC: STM GEN A OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR-RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses loop A cold leg temperature.

I**

I

Page No. 34 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: HL TEMP 1/A POINT ID: T1RC005A PLANT SPEC POINT DESC: LOOP A WR HOT LEG TEMP (RD)<>

GENERIC/COND DESC: STM GEN A INLET TEMPERATURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED:

  • N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A
  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses loop A hot leg temperature .

Page No. 35 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 2/8 POINT ID: T1RCD08A PLANT SPEC POINT DESC: LOOP B WR T COLD CWT)<>

GENERIC/COND DESC: STM GEN B OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: D.D MAXIMUM INSTR RANGE: 700.D ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI .DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses loop B cold leg temperature.

Page No. 36 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: HL TEMP 2/B POINT ID: T1RC009A

  • PLANT SPEC POINT DESC: LOOP B WR HOT LEG TEMP (WT)<>

GENERIC/COND DESC: STM GEN B INLET. TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI .DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses loop B hot leg temperature.

Page No. 37 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 3/C POINT ID: T1RC012A PLANT SPEC POINT DESC: LOOP C WR T COLD (BL)<>

GENERIC/COND DESC: STM GEN C OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A
  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM-DESC: Senses loop C cold leg temperature.

Page No. 38 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: HL TEMP 3/C POINT ID: T1RC013A PLANT SPEC POINT DESC: LOOP C WR HOT LEG TEMP (BL)<>

GENERIC/COND DESC: STM GEN C INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW.PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop C hot leg temperature.

Page No. 39 STATION: Surry 05/21/91 UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: TEMP CORE EX POINT ID: T1RC001C PLANT SPEC POINT DESC: PEAK CORE EXIT TEMP GENERIC/COND DESC: HIGHEST TEMPERATURE AT CORE EXIT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 2400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 50 HOIJ PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: EXIT OF SELECTED FUEL ASSEMBLIES IN-CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POIJER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the reactor coolant exit temperature. The highest valid incore thermocouple is used. If none of the thermocouples is valid, this point is marked invalid .

Page No. 40 STATION: Surry 05/21/91 UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SUB MARGIN POINT ID: T1RC020C PLANT SPEC POINT DESC: CORE EXIT TSAT MARGIN GENERIC/COND DESC: SATURATION TEMP* HIGHEST CET ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -35.000 MAXIMUM INSTR RANGE: 200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOIJ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: TSAT

  • CONTAINMENT CET - REACTOR CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid saturation margin inputs from the RVLIS system are averaged (2 signals if all are valid). If none of the signals are valid, this point is marked invalid .

Page No. 41 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: R1RM201C PLANT SPEC POINT DESC: RCS LETDOWN LR (119)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 27' LVL OUTSIDE WALL-SAMPLE RM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the RCS letdown line - LOW RANGE.

1./

Page No. 42 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: R1RM202C PLANT SPEC POINT DESC: RCS LETDOWN HR (118)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: .1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 27' LVL OUTSIDE WALL-SAMPLE RM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the RCS letdown line - HIGH RANGE

  • Page No. 43 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R1RM203C PLANT SPEC POINT DESC: AFPT EXHAUST (129)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR _UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, OUTSIDE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the unit 1 turbine-driven auxiliary feed pump exhaust ("Terry" turbine) .

  • Page No. 44 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: MAIN SL 1/A POINT ID: R1RM204C PLANT SPEC POINT DESC: A MS HIGH RANGE (124)

GENERIC/COND DESC: STM GEN A STEAM LINE RAD LEVEL ANALOG/DIGITAL: A

  • ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1. DE-2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in main steam line A*

Page No. 45 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 2/B POINT ID: R1RM205C PLANT SPEC POINT DESC: B MS HIGH RANGE (125)

GENERIC/COND DESC: STM GEN B STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI- DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in main steam line B.

Page No. 46 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: MAIN SL 3/C POINT ID: R1RM206C PLANT SPEC POINT DESC: CMS HIGH RANGE (126)

GENERIC/COND DESC: STM GEN C STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E*2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in main steam line C.

Page No. 47 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM207C PLANT SPEC POINT DESC: CNTMT AIR GASEOUS (160)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE *POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 45 1 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation Level of air taken from the reactor containment

  • Page No. 48 STATION: Surry 05/21 /91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R1RM208C PLANT SPEC POINT DESC: CNTMT AIR PART (159)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 45 1 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of particles in the air taken out of the reactor containment .

Page No. 49 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM209C PLANT SPEC POINT DESC: CNTMT AREA (163)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-1 MAXIMUM INSTR RANGE: 1.0E?

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: . N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level within the reactor containment .

Page No. 50 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM210C PLANT SPEC POINT DESC: CNTMT PER HATCH (161)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-1 MAXIMUM INSTR RANGE: 1 .OE?

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, OUTSIDE PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the Personnel Hatch area.

Page No. 51 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R1RM213C PLANT SPEC POINT DESC: CONTAINMENT HR AREA (127)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-1 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the reactor containment -

HIGH RANGE .

Page No. 52 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM214C PLANT SPEC POINT DESC: CONTAINMENT HR AREA (128)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG ITAL : A ENGR UNiTS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: 'N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL 47' LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the reactor containment -

HIGH RANGE .

Page No. 53 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG BD RAD 1A POINT ID: R1RM215C PLANT SPEC POINT DESC: SG BLOIJ DOWN (112)

GENERIC/COND DESC: STM GEN A BLOIIDOIJN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT BY EMERG SWG ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
  • N/A INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION

.FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the blowdown of steam generator. Although this parameter is identified as the steam generator A blow down radiation monitor, this monitor can actually be aligned to any one of the three steam generators

  • Page No. 54 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91' REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG DB RAD 1A POINT ID: R1RM216C PLANT SPEC POINT DESC: SG BLOW DOWN (113)

GENERIC/COND DESC: STM GEN A SLOWDOWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT BY EMERG SWG ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation Level of the blowdown of steam generator. Although this parameter is identified as the steam generator A blow down radiation monitor, this monitor can actually be aligned to any one of the three,steam generators .

Page No. 55 *sTATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: COND A/E RAD POINT ID: R1RM217C PLANT SPEC POINT DESC: CONDENSER AE (111)

GENERIC/COMO DESC: COND AIR EJECTOR RADIOACTIVITY ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG MEZZANINE OVERHEAD BY AE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the gaseous effluent from the condenser air ejectors. On high radiation any radioactive air is diverted into the reactor containment .

Page No. 56 STATION: Surry 05/21/91 UNIT: 1

  • PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R1RM218C PLANT SPEC POINT DESC: CW DISCHARGE TUNNEL (120)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 .

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: DISCHARGE CANAL, OUTLET OF DISCH TUNNEL ALARM/TRIP SETPOINTS: VARIABLE NI* DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the circulating water discharge tunnel .

Page No. 57 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F1SI002A PLANT SPEC POINT DESC: LHSI PMP A DISCH HOR FLOW (NL)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 628 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 5000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LHSI PMP A DISCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A.

UNIQUE SYSTEM DESC: Senses discharge of LHSI punp A.

I

Page No. 58 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F1SI003A PLANT SPEC POINT DESC: LHSI PMP B DISCH HOR FLOW (NL)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 62811 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 5000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LHSI PMP B DISCH ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses discharge of LHSI pump B.

Page No. 59 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F1SI008A PLANT SPEC POINT DESC: HHS! HOT LEGS TOTAL FLOW (YW)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:

  • GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRG PMPS A,B,C DISCH UPSTRM OF HOT LEGS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses total discharge of charging pumps A, B, & C to RCS hot legs .

  • Page No.

DATE:

60 REACTOR UN IT :

05/20/91 SU1 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F1SI009A PLANT SPEC POINT DESC: HHS! COLD LEGS TOTAL FLOW (RD)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRG PMPS A,B,C DISCH UPSTRM OF CLO LEGS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses total discharge of charging pumps A, B, & C to RCS cold legs .

Page No. 61 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: D5/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM001A PLANT SPEC POINT DESC: WIND SPEED LOWER (RCDR*1) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35 1 ON PRIMARY TOWER&30 1 ON BACKUP TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures wind speed at 35 feet.

  • Page No.

DATE:

62 REACTOR UN IT:

05/20/91 SU1 STATION: Surry UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED POINT ID: M3MM002A PLANT SPEC POINT DESC: WIND SPEED UPPER CRCDR-2) (NL)

GENERIC/COND DESC: WIND SPEED AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150° ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Measures wind speed at 150 feet.

Page No. 63 STATION: Surry 05/21/91 UNIT: 1 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: YIND DIR POINT ID: M3MM004A PLANT SPEC POINT DESC: YIND DIR LOYER (RCDR-4) (NL)

GENERIC/COND DESC: YIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 360.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOY PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35 1 ON PRIMARY TOYER&30' ON BACKUP TOYER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A NI DETECTOR POYER SUPPLY TURN-ON POYER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses wind direction at 35 feet.

Page No. 64 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM005A PLANT SPEC POINT DESC: WIND DIR UPPER (RCDR-5) (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 360.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses wind direction at 150 feet.

Page No. 65 STATION: Surry 05/21 /91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM006A PLANT SPEC POINT DESC: SIGMA THETA (RCDR-6) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: PRIMARY TOWER TRAILER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: The output sigma theta signal is the standard deviation around the average direction .

Page No. 66 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM008A PLANT SPEC POINT DESC: DELTA T (RCDR-9) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -5.0 MAXIMUM INSTR RANGE: 15.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 2 RTDs AT 35 1 & 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Delta Tis Lower temperature minus upper temperature.

Page No. 67 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: T3MM001A PLANT SPEC POINT DESC: AMB TEMPERATURE (RCDR-7) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -25.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: RTD AT 35 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures air temperature at 35 1 elevation on the primary tower

  • Page No. 68 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM203C PLANT SPEC POINT DESC: PROCESS VENT GAS (102)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS:

HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45 1 10" LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of. air taken from the process vent .

Page No. 69 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91

. REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM204C PLANT SPEC POINT DESC: PV HIGH RANGE (130-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1 ;OE-3 MAXIMUM INSTR RANGE: 1.0ES ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - HIGH RANGE

  • Page No. 70 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM205C PLANT SPEC POINT DESC: PV HIGH RANGE (130-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E4 MAXIMUM INSTR RANGE: 1. OE12 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI.DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER. LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - HIGH RANGE .

Page No. 71 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM206C PLANT SPEC POINT DESC: PV NORMAL (130*1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-8 MAXIMUM INSTR RANGE: 1.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBE~ OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation Level in the process vent - NORMAL RANGE

  • I I

Page No. 72 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: . N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM207C PLANT SPEC POINT DESC: PV NORMAL (130-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MIN_IMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0EB ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - NORMAL RANGE .

Page No. 73 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: DS/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM208C PLANT SPEC POINT DESC: PV PARTICULATE (101)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45' 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of particles in the air taken out of the process vent .

Page No. 74 STATION: Surry 05,'21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM209C PLANT SPEC POINT DESC: LW DISPOSAL (108)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 13 1 LVL ACROSS FROM CHRG PMPS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP.TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the liquid waste system.

Page No. 75 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM218C PLANT SPEC POINT DESC: SW FROM CC HX A RM (107A)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM-INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger A*

Page No. 76 STATION: Surry 05/21/91 UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE, DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM219C PLANT SPEC POINT DESC: VENT VENT GASEOUS (110)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45 1 10 11 LEVEL EAST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POIJER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of air taken from ventilation vent stack #2 .

Page No. 77 STATION: Surry 05/21/91 UNIT: 1*

PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM220C PLANT SPEC POINT DESC: VV PARTICULATE (109)

GENERIC/COND DESC: RADIOACTIVITY OF* RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45 1 1011 LEVEL EAST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of particles in the air taken from ventilation vent stack #2

  • Page No. 78 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: . R3RM221C PLANT SPEC POINT DESC: VV 1 GAS RAD MON (104)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: UNIT 2 SWITCHGEAR ROOM (NORTH WALL)

ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of air taken from the ventilation vent .

Page No, 79 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM223C PLANT SPEC POINT DESC: VV HIGH RANGE (131-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-3 MAXIMUM INSTR RANGE: 1.0E5 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI QETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

HIGH RANGE .

Page No. 80 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM224C PLANT SPEC POINT DESC: VV HIGH RANGE (131-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E4 MAXIMUM INSTR RANGE: 1.0E12 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

HIGH RANGE .

Page No. 81 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM225C PLANT SPEC POINT DESC: VV NORMAL RANGE (131-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-8 MAXIMUM INSTR RANGE: 1.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF *LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

NORMAL RANGE .

Page No. 82 STATION: Surry 05/21/91 UNIT: 1 P\.IR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM226C PLANT SPEC POINT DESC: VV NORMAL RANGE (131-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/0 I GITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0E8 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE N1. DETECTOR PO\.IER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

NORMAL RANGE .

Page No. 83 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT *10: R3RM227C PLANT SPEC POINT DESC: SW FROM CC HX BRM (107B)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI PETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger B*

Page No. 84 STATION: Surry 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF LIQ RAD POINT ID: R3RM228C PLANT SPEC POINT DESC: SW FROM CC HX C RM (107C)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger C.

I

  • ATTACHMENT 2 SURRY DATA UNIT 2 POINT LIBRARY LISTINGS

Page No. STATION: Surry 05/21/91 UNIT: 2 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA. FEEDER: N/A NRC EROS PARAMETER: RCS CHG/MU POINT ID: F2CH003A PLANT SPEC POINT DESC: CHARGING LOOP FLOIJ (BL)

GENERIC/COND DESC: PRIM SYS CHARGING OR MAKEUP FLOIJ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 393.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 150.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOIJ PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHARGING LINE UPSTRM OF REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Flow transmitter FT-2122 transmits a signal to a controller located in the control cabinets, and to a flow indicator in the main control room. The controller operates the charging water flow control valve (FCV-2122) to maintain a preset charging flow in conjunction with a signal from the pressurizer level instrumentation. The two signals maintain pressurizer level within the proscribed band and limit the minimum and maximum charging flow rates

  • Page No. 2 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: RCS LTDN RAD POINT ID: F2CH004A PLANT SPEC POINT DESC: LOW PRESSURE LETDOWN FLOW (WT)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 400" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 150.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LETDOWN LINE DWNSTRM OF NON-REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides indication of letdown stream flow rate in the Control Room .

Page No. 3 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: BWST LEVEL POINT ID: L2CS001C PLANT SPEC POINT DESC: RWST LEVEL GENERIC/COND DESC: BORATED WATER STORAGE TANK LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 3997 GALLONS MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 13500 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED.: MINUMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RWST ALARM/TRIP SETPOINTS: VARIABLE NI ~ETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: DRY UNIQUE SYSTEM DESC: Indicates the level in the RWST. The lowest valid signal is used. If none of the 4 signals is valid, this point is marked invalid .

Page No. 4 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT SMP WR POINT ID: L2DA001C PLANT SPEC POINT DESC: CONTAINMENT WR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP WR LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION: 1 FT= 58343 GALLONS MINIMUM INSTR RANGE: 0.43 MAXIMUM INSTR RANGE: 9.0 ZERO POINT

REFERENCE:

TNKBOT REFE~ENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RECIRC SPRAY SUMP-SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid wide range signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

Page No. 5 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT SMP NR POINT ID: L2DA002C PLANT SPEC POINT DESC: CONTAINMENT NR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP NR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: INCH ENGR UNITS CONVERSION: 1 IN= 2369 GALLONS MINIMUM INSTR RANGE: 4.5 MAXIMUM INSTR RANGE: 26.5 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 280 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CONTAINMENT SUMP ALARM/TRIP*SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment sump level and provides a high level alarm. The largest valid narrow range signal is used for this point. If all signals are valid, 2 signals are considered. If both signals are invalid, this point is marked invalid .

Page No. 6 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 1/A POINT ID: F2FW001A PLANT SPEC POINT DESC: SG A AFW FLOW (RD)<>

GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0

  • 394 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOI.I PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POI.IER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POI.IER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator A.

Page No. 7 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 2/B POINT ID: F2FW002A PLANT SPEC POINT DESC: SG B AFW FLOW CWT) <>

GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0

  • 394 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POYER LEVEL: N/A NI DETECTOR POYER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator B.

Page No. 8 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 3/C POINT ID: F2FW003A PLANT SPEC POINT DESC: SG C AFW FLOW (BL) <>

GENERIC/COND DESC: STM GEN C AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 394 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 350.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER. OF SENSORS: N/A HOW .PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feedwater flow to steam generator C.

Page No. 9 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: MN FD FL 1/A POINT ID: F2FW005C PLANT SPEC POINT DESC: SG A MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN A MAIN FEEDWATER,FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0

  • 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator A.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used

  • Page No. 10 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: MN FD FL 2/B POINT ID: F2FW006C PLANT SPEC POINT OESC: SG B MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN B MAIN FEEDWATER FLOW ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0 - 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A -

UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator B.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used .

Page No. 11 STATION: Surry 05/21/91

. UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: MN FD FL 3/C POINT ID: F2FW007C PLANT SPEC POINT DESC: SG C MAIN FEEDWATER FLO\,I GENERIC/COND DESC: STM GEN C MAIN FEEDWATER FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0 - 286.2 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4.4 ZERO POINT

REFERENCE:

N/A

'REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HQ\,I PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HTR DISCH UPSTRM OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE.

NI DETECTOR PQ\,IER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator C.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used .

Page No. 12 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 1/A POINT ID: L2FW004A PLANT SPEC POINT DESC: SG A WR LEVEL (WT)<>

GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: o.o MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HO\.J PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 2A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\.JER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR PO\.JER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2A.

Page No. 13 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 2/B POINT ID: L2FW008A PLANT SPEC POINT DESC: SG B WR LEVEL (BL) <>

GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 2B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water Level in steam generator 2B .

Page No. 14 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L2FW012A PLANT SPEC POINT DESC: SG C WR LEVEL (YW) <>

GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 564 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR* LOCATIONS: STEAM GENERATOR 2C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2C.

Page No. 15 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 1/A POINT ID: L2FW001C PLANT SPEC POINT DESC: STEAM GENERATOR A LEVEL GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828" ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2A. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid

  • Page No. 16 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE
  • DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 2/B POINT ID: L2FW002C PLANT SPEC POINT DESC: STEAM GENERATOR B LEVEL GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT
  • ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828 11 ALARM/TRIP SETPOINTS: VARIABLE NI.DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2B. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 17 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L2FIJ003C PLANT SPEC POINT DESC: STEAM GENERATOR C LEVEL GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOIJ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 684 11 & TOP AT 828 11 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF PO\JER LEVEL: N/A NI DETECTOR PO\JER SUPPLY TURN-ON PO\.IER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: \JET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2C. *The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 18 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: H2 CONC POINT ID: A2GW001C PLANT SPEC POINT DESC: CNTMT H2 CONCENTRATION GENERIC/COND DESC: CONTAINMENT HYDROGEN CONC ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: AUX BLDG 13 1 LVL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Takes a sample of containment atmosphere and measures the hydrogen concentration in the sample. The valid signals are averaged (2 signals if all are valid). If none of the signals is valid, this point is marked invalid

  • Page No. 19 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: -cTMNT PRESS POINT ID: P2LM001C PLANT SPEC POINT DESC: CONTAINMENT PRESSURE GENERIC/COND DESC: CONTAINMENT PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIA ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CABLE PENETRATION AREA IN AUX BLDG ALARM/TRIP SETPOINTS: VARIABLE NI PETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment pressure. The valid intermediate range signals (4 signals if all are valid) are averaged. If no intermediate range signals are valid, the average of the wide range signals is used (2 signals if all are valid). If no signals are valid, this point is marked invalid

  • Page No. 20 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT TEMP POINT ID: T2LM001C PLANT SPEC POINT DESC: CONTAINMENT TEMPERATURE GENERIC/COND DESC: CONTAINMENT TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 50.0 MAXIMUM INSTR RANGE: 300.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR.SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: REACTOR CONTAINMENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor contairvnent temperature. The valid signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

Page No. 21 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS 1/A POINT ID: P2MS001C PLANT SPEC POINT DESC: SG A PRESSURE GENERIC/COND DESC: STEAM GENERATOR A PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HO\I PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR PO\IER SUPPLY TURN-ON PO\IER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DES~: Provides pressure of the steam which is on route from steam generator 2A to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid

  • Page No. 22 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 2/B POINT ID: P2MS002C PLANT SPEC POINT DESC: SG B PRESSURE GENERIC/COND DESC: STEAM GENERATOR B PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF PO\.IER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON PO\.IER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator 2B to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 23 STATION: Surry 05/21/91 UNIT: 2 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91

. REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 3/C POINT ID: P2MS003C PLANT SPEC POINT DESC: SG C PRESSURE GENERIC/COND DESC: STEAM GENERATOR C PRESSURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROCOR SENS: p NUMBER OF SENSORS: 3 HOY PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN C ALARM/TRIP SETPOINTS: VARIABLE NI.DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A

  • NI DETECTOR POYER SUPPLY TURN-ON POYER LEVEL:

iNSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator 2C to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 24. STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: NI SOURC RNG POINT ID: M2NM001C PLANT SPEC POINT DESC: SOURCE LEVEL POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, SOURCE RNG ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPS ENGR UNITS CONVERSION: Approximately 1e 1e-3 % Power MINIMUM INSTR RANGE: 1.0EO MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: 1e-10 AMPS IR

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP. TRANSMITTERS:

LEVEL REFERENCE LEG:

<1e-10 AMPS IR N/A N/A UNIQUE SYSTEM DESC: NI cut_off requires the listed reading on either of the intermediate range instruments and NI cut_on requires the listed reading on both of the intermediate range instruments CIR is on the intermediate range power scale). The highest valid source range signal is used for this point. 2 source range si.gnals are available for use. If* neither of the source range signals is valid, this point is marked invalid.

The source range inputs are logrithmic in nature.

Therefore, the highest valid source range signal is exponentiated to yield the value for this poin~ .

Page No. 25 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: NI INTER RNG POINT ID: M2NM003C PLANT SPEC POINT DESC: INTERMEDIATE RANGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, INT RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: AMPS ENGR UNITS CONVERSION: Approximately 3e 120 % Power MINIMUM INSTR RANGE: 1.0E-11 MAXIMUM INSTR RANGE: 1.0E-3 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The highest valid intermediate range signal is used for this point. 2 intermediate range signals are available for use.

If neither of the intermediate range signals is valid, this point is marked invalid. The intermediate range inputs are logrithmic in nature. Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point .

Page No. 26 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: NI POWER RNG POINT ID: M2NM005C PLANT SPEC POINT DESC: POWER RANGE AVERAGE POWER

  • GENERIC/COND DESC: NUCLEAR INSTRUMENTS, POWER RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: The valid power range signals are averaged for this point.

4 power range signa.ls are available for use. If none of the power range signals is valid, this point is marked invalid .

Page No. 27 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CORE FLOW POINT ID: F2RC004C PLANT SPEC POINT DESC: AVERAGE RCS LOOP FLOW GENERIC/COND DESC: TOTAL REACTOR FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0 - 460 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 9 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN DISCHARGE UPSTRM OF RCP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the flow of coolant from the steam generator to the reactor coolant pump. The average of the 3 loop calculated average flows is used for this point. The 3 loop average values are calculated by taking the average of the valid flow signals for each loop. If all loop flow signals are valid, 3 fl~w readings will be used for each loop

  • Page No. 28 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F2RC005C PLANT SPEC POINT DESC: TOT COLD LEG HHS! FLOW GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/0 I GITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1800.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: SUM* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CHRGING PMP .DISCH UPSTRM OF COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHS!

punps to the cold leg of each loop. The .3 loop high head SI flows are totaled for this value. If any one of the loop SI values is invalid, this point will be marked -invalid

  • Page No. 29 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 .

REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: REAC VES LEV POINT ID: L2RC001C PLANT SPEC POINT DESC: REAC VSL FULL RANGE LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY

-CUT-OFF POWER LEVEL: . N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: The 2 reactor full range level signals are used in conjunction with the reactor coolant pump motor currents to calculate this value. The full range readings are invalid if any RCP is running; therefore, this process value will be set invalid if any RCP motor current .is greater than 5% of it's full load value. If none of the RCP's are running, the average of the valid full range level signals is used to calculate this point .

Page No. 30 STATION: Surry 05/21/91 UNIT: 2 PWR OATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: PRZR LEVEL POINT ID: L2RC002C PLANT SPEC POINT DESC: PRESSURIZER LEVEL GENERIC/COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1 % = 3.60 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: PRESSURIZER-HP LOCATED 32.0 1 ABOVE LP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses pressurizer level and provides alarm and control function inputs when the plant is operating normally. The valid signals are averaged (3 signals if all are valid). If none of the signals are valid, this point is marked invalid .

Page No. 31 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: REAC VES LEV POINT ID: L2RC003C PLANT SPEC POINT DESC: RVLIS DYNAMIC HEAD LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A EN~R UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: The 2 reactor dynamic head level signals are used in conjunction with the reactor coolant~ motor currents to calculate this value. The dynamic head readings are invalid if no RCP's are ~unning; therefore, this process value will be set invalid if no RCP motor current is greater than 5% of it's full load value. If none of the RCP's are running, the average of the valid dynamic head level signals is used to calculate this point

  • Page No. 32 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS PRESSURE POINT ID: P2RC001C PLANT SPEC POINT DESC: RCS AVERAGE PRESSURE GENERIC/COND DESC: REACTOR COOLANT SYSTEM PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 3000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: PT-2455, PT-2456, and PT-2457 all measure pressurizer pressure (narrow range) and are used for pressurizer pressure protection. The valid narrow range signals are averaged (3 signals if all are valid). If none of the narrow range signals valid, the average of the valid wide range signals is used (2 signals if all are valid). If none of the narrow or wide range signals is valid, this point is marked invalid .

Page No. 33 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 1/A POINT ID: T2RC004A PLANT SPEC POINT DESC: LOOP A WR T COLD (RD)<>

GENERIC/COND DESC: STM GEN A OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE:- 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: S NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI.DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A cold leg temperature.

Page No. 34 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: HL TEMP 1/A POINT ID: T2RC005A PLANT SPEC POINT DESC: LOOP A WR HOT LEG TEMP (RD)<>

GENERIC/CONO OESC: STM GEN A INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A hot leg temperature.

Page No. 35 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 2/B POINT ID: T2RC008A PLANT SPEC POINT DESC: LOOP B WR T COLD CWT)<>

GENERIC/COND DESC: STM GEN B OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: o.o MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B COLD LEG ALARM/TR.IP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION I

FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses loop B cold leg temperature.

Page No. 36 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: HL TEMP 2/B POINT ID: T2RC009A PLANT SPEC POINT DESC: LOOP B WR HOT LEG TEMP (WT)<>

GENERIC/COND DESC: STM GEN B INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A
  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop B hot leg temperature.

Page No. 37 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 3/C POINT ID: T2RC012A PLANT SPEC POINT DESC: LOOP C WR T COLD (BL)<>

GENERIC/COND DESC: STM* GEN C OUTLET-TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop C cold leg temperature.

Page No. 38 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: HL TEMP 3/C POINT ID: T2RC013A PLANT SPEC POINT DESC: LCX)P C WR HOT LEG TEMP (BL)<>

GENERIC/COND DESC: STM GEN C INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LCX)P C HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A
  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop C hot leg temperature.

Page No. 39 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: TEMP CORE EX POINT ID: T2RC001C PLANT SPEC POINT DESC: PEAK CORE EXIT TEMP GENERIC/COND DESC: HIGHEST TEMPERATURE AT CORE EXIT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 2400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 50 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: EXIT OF SELECTED FUEL ASSEMBLIES IN-CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the reactor coolant exit temperature. The highest valid incore thermocouple is used. If none of the thermocouples is val id, this point is marked inval.id .

Page No. 40 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SUB MARGIN POINT ID: T2RC020C PLANT SPEC POINT DESC: CORE EXIT TSAT MARGIN GENERIC/COND DESC: SATURATION TEMP - HIGHEST CET ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -35.000 MAXIMUM INSTR RANGE: 200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: TSAT - CONTAINMENT CET - REACTOR CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid saturation margin inputs from the RVLIS system are averaged (2 signals if all are valid). If none of the signals are valid, this point is marked invalid .

Page No. 41 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: R2RM201C PLANT SPEC POINT DESC: RCS LETDOWN HR (218)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 27 1 LVL OUTSIDE WALL-SAMPLE RM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the RCS letdown line - HIGH RANGE

  • Page No. 42 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: R2RM202C PLANT SPEC POINT DESC: RCS LETDOWN LR (219)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 27 1 LVL OUTSIDE WALL-SAMPLE RM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the RCS letdown line - LOW RANGE .

Page No. 43 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R2RM203C PLANT SPEC POINT DESC: TD AFW PUMP EXHAUST (229)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: .1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, OUTSIDE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the unit 2 turbine-driven auxiliary feed ~ exhaust ("Terry" turbine) .

Page No. 44 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: MAIN SL 1/A POINT ID: R2RM204C PLANT SPEC POINT DESC: A MS HIGH RANGE (224)

GENERIC/COND DESC: STM GEN A STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E7

  • ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47' LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • . NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in ma.in steam line A.

Page No. 45 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 2/B POINT ID: R2RM205C PLANT SPEC POINT DESC: B MS HIGH RANGE (225)

GENERIC/COND DESC: STM GEN B STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E*2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HO\.I PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47' LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\.IER SUPPLY CUT*OFF PO\.IER LEVEL: N/A

  • NI DETECTOR PO\.IER SUPPLY TURN-ON PO\.IER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in main steam line B.

Page No. 46 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 3/C POINT ID: R2RM206C PLANT SPEC POINT DESC: CMS HIGH RANGE (226)

GENERIC/COND DESC: STM GEN C STEAM LINE RAD LEVEL ANALOG/DIGITAL: A.

ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SAFEGUARDS AREA, 47' LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in main steam line C.

Page No. 47 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM207C PLANT SPEC POINT DESC: CNTMT AIR GASEOUS (260)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 45 1 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF PO\.IER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/,A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of air taken from the reactor containment .

Page No. 48 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM208C PLANT SPEC POINT DESC: CNTMT AIR PART (259)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, 45 1 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of particles in the air taken out of the reactor containment .

Page No. 49 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R2RM209C PLANT SPEC POINT DESC: CNTMT AREA (263)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DI GIT AL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-1 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:* N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level within the reactor containment.

Page No. 50 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R2RM210C PLANT SPEC POINT DESC: CNTMT PER HATCH (261)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-1 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG, OUTSIDE PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the Personnel Hatch area.

Page No. 51 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM213C PLANT SPEC POINT DESC: CONTAINMENT HR AREA (227)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E*1 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the reactor containment -

HIGH RANGE .

Page No. 52 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM214C PLANT SPEC POINT DESC: CONTAINMENT HR AREA (228)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CONTAINMENT, INSIDE CRANE WALL 47 1 LEVEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the reactor containment -

HIGH RANGE .

Page No. 53 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG BD RAD 1A POINT ID: R2RM215C PLANT SPEC POINT DESC: SG BLOW DOWN (212)

GENERIC/COND DESC: STM GEN A BLOWDOWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERE,NCE POI NT NOTES: N/A PROC OR SENS: p

  • NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT BY EMERG SWG ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT.FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the blowdown of steam generator. Although this parameter is identified as the

  • Page No. 54 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: SG BD RAD 1A POINT ID: R2RM216C PLANT SPEC POINT DESC: SG BLOW DOWN (213)

GENERIC/COND DESC: STM GEN A SLOWDOWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT BY EMERG SWG ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the blowdown of steam generator. Although this parameter is identified as the steam generator A blow down radiation monitor, this monitor can actually be aligned to any one of the three steam generators .

Page No. 55 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: COND A/E RAD POINT ID: R2RM217C PLANT SPEC POINT DESC: CONDENSER AE (211)

GENERIC/COND DESC: COND AIR EJECTOR RADIOACTIVITY ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARIT~MIC INPUT SENSOR LOCATIONS: TURBINE BLDG MEZZANINE OVERHEAD BY AE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the gaseous effluent from the condenser air ejectors. On high radiation any radioactive air is diverted into the reactor containment

  • I

Page No. 56 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R2RM218C PLANT SPEC POINT DESC: CW DISCHARGE TUNNEL (220)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG MEZZANINE OVERHEAD BY AE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the gaseous effluent from the condenser air ejectors. On high radiation any radioactive air is diverted into the reactor containment .

Page No. 57 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F2SI002A PLANT SPEC POINT DESC: LHSI PMP A DISCH HDR FLOW (NL)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 628 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 5000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LHSI PMP A DISCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses discharge of LHSI pump A.

Page No. 58 STATION: Surry 05/21/91 UNIT: 2 P'olR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLO'ol POINT ID: F2Sl003A PLANT SPEC POINT DESC: LHSI PMP B DISCH HDR.FLO'ol (NL)

GENERIC/COND DESC: HIGH PRESSURE SI FLO'ol ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 628 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 5000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HO'ol PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LHSI PMP B DISCH ALARM/TRIP SETPOINTS: VARIABLE NJ.DETECTOR PO'olER SUPPLY CUT-OFF PO'olER LEVEL: N/A NI DETECTOR PO'olER SUPPLY TURN-ON PO'olER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: . Senses dfscharge of LHSI pump B.

Page No. 59 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F2SI008A PLANT SPEC POINT DESC: HHS! HOT LEGS TOTAL FLOW CYW)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1100.00 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRG PMPS A,B,C DISCH UPSTRM OF HOT LEGS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses total discharge of charging pumps A, B, & C to RCS hot legs

  • Page No. 60 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F2Sl009A PLANT SPEC POINT DESC: HHS! COLD LEGS TOTAL FLO\J (RD)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1100.00

  • ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRG PMPS A,B,C DISCH UPSTRM OF CLD LEGS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A
  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses total discharge of charging pumps A, B, & C to RCS cold legs .

Page No. 61 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: STAB CLASS POINT ID: M3MM001A PLANT SPEC POINT DESC: WIND SPEED LOWER (RCDR-1) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION:_ N/A MINIMUM INSTR RANGE: 0.0

. MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35 1 ON PRIMARY TOWER&30 1 ON BACKUP TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures wind speed at 35 feet

  • Page No. 62 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED POINT ID: M3MM002A PLANT SPEC POINT DESC: WIND SPEED UPPER (RCDR-2) (NL)

GENERIC/COND DESC: WIND SPEED AT THE REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI-DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A

  • N/A N/A UNIQUE SYSTEM DESC: Measures wind speed at 150 feet.

Page No. 63 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM004A PLANT SPEC POINT DESC: WIND DIR LOWER (RCDR-4) (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INST.R RANGE: 0.0 MAXIMUM INSTR RANGE: 360.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35 1 ON PRIMARY TOWER&30 1 ON BACKUP TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses wind direction at 35 feet.

Page No. 64 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM005A PLANT SPEC POINT DESC: WIND DIR UPPER (RCDR-5) (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 360.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150' ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses wind direction at 150 feet.

Page No. 65 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: STAB CLASS POINT ID: M3MM006A PLANT SPEC POINT DESC: SIGMA THETA (RCDR-6) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HO\I PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: PRIMARY TOWER TRAILER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\IER SUPPLY CUT-OFF PO\IER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: The output sigma theta signal is the standard deviation around the average direction .

Page No. 66 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: STAB CLASS POINT ID: M3MM008A PLANT SPEC POINT DESC: DELTA T (RCDR-9) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL:. A ENGR UNITS/DIG STATES: DEGC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -5.0 MAXIMUM INSTR RANGE: 15.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 2 RTDs AT 35 1 & 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI*DETECTOR POYER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Delta Tis lower temperature minus upper temperature.

Page No. 67 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: T3MM001A PLANT SPEC POINT DESC: AMB TEMPERATURE (RCDR-7) (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -25.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: RTD AT 35 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures air temperature at 35 1 elevation on the primary tower .

Page No. 68 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM203C PLANT SPEC POINT DESC: PROCESS VENT GAS (102)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45' 10" LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation Level of air taken from the process vent .

Page No. 69 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM204C PLANT SPEC POINT DESC: PV HIGH RANGE (130*2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1. OE-3 MAXIMUM INSTR RANGE: 1.0ES ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - HIGH RANGE

  • Page No. 70 STATION: Surry 05/21/91 UNIT: 2 PWR OATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAO POINT ID: R3RM205C PLANT SPEC POINT DESC: PV HIGH RANGE (130*2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E4 MAXIMUM INSTR RANGE: 1. OE12 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - HIGH RANGE

  • Page No. 71 STAT ION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM206C PLANT SPEC POINT DESC: PV NORMAL (130-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1. OE-8 MAXIMUM INSTR RANGE: 1.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - NORMAL RANGE

  • Page No. 72 STATION: Surry 05/21/91 UNIT: 2 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM207C PLANT SPEC POINT DESC: PV NORMAL (130-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0E8 ZERO POINT

REFERENCE:

N/A

.REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT*

SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the process vent - NORMAL RANGE .

Page No. 73 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: D5/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A N~C ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM208C PLANT SPEC POINT DESC: PV PARTICULATE (101)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45' 10 11 LEVEL WEST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of particles in the air taken out of the process vent .

- ------ --- ----=-=---=::-:=-::::=-

Page No. 74 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM209C PLANT SPEC POINT DESC: LW DISPOSAL (108)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 13 1 LVL ACROSS FROM CHRG PMPS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FQR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the liquid waste system.

Page No. 75 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM218C PLANT SPEC POINT DESC: SW FROM CC HX A RM (107A)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger A*

Page No. 76 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM219C PLANT SPEC POINT DESC: VENT VENT GASEOUS (110)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

  • N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG 45 1 10 11 LEVEL EAST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of air taken from ventilation vent stack #2

  • Page No. n STATION: Surry 05/~1/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM220C PLANT SPEC POINT DESC: VV PARTICULATE (109)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A

- PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC- INPUT SENSOR LOCATIONS: AUX BLDG 45' 10" LEVEL EAST END ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiat.ion level of particles in the air taken from ventilation vent stack #2

  • Page No. 78 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM221C PLANT SPEC POINT DESC: VV 1 GAS RAD MON (104)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: .N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: UNIT 2 SWITCHGEAR ROOM (NORTH WALL)

ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF Pm/ER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of air taken from the ventilation vent .

Page No. 79 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM223C PLANT SPEC POINT DESC: VV HIGH RANGE (131-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-3 MAXIMUM INSTR RANGE: 1.0E5 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation Level of ventilation vent stack #2 -

HIGH RANGE .

Page No. 80 STATION: Surry 05/21/91 UNIT: 2 P~R DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UNIT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM224C PLANT SPEC POINT DESC: VV HIGH RANGE (131-2)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: UC!/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E4 MAXIMUM INSTR RANGE: 1.0E12 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 H~ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR P~ER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR P~ER SUPPLY TURN-ON P~ER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

HIGH RANGE .

Page No. 81 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM225C PLANT SPEC POINT DESC: VV NORMAL RANGE (131-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-8 MAXIMUM INSTR RANGE: 1.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF PO~ER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

NORMAL RANGE .

Page No. 82 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM226C PLANT SPEC POINT DESC: VV NORMAL RANGE (131-1)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS_CONVERSION: N/A MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1.0E8 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HO\,/ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: CABLE SPREADING ROOM ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\,/ER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of ventilation vent stack #2 -

NORMAL RANGE .

Page No. 83 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/20/91 REACTOR UN IT : SU2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM227C PLANT SPEC POINT DESC: SW FROM CC HX BRM (107B)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger B.

- l Page No. 84 STATION: Surry 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: DS/20/91 REACTOR UN IT: SU2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF LIQ RAD POINT ID: R3RM228C PLANT SPEC POINT DESC: SW FROM CC HX C RM (107C)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 10.0 MAXIMUM INSTR RANGE: 1.0E7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS:* p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE BLDG BASEMENT CC HEAT EXCHANGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REfERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level in the service water effluent of component cooling heat exchanger C.

ATTACHMENT 3 NORTH ANNA UNIT 1 DATA POINT LIBRARY LISTINGS

  • Page No.

DATE:

REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS CHG/MU POINT ID: F1CH003A PLANT SPEC POINT DESC: CHARGING LOOP FLOW (NL)

GENERIC/COND DESC: PRIM SYS CHARGING OR MAKEUP FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-648 11 H20 MINIMUM-INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHARGING LINE UPSTREAM OF REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Flow transmitter FT-1122 transmits a signal to a controller located in the control cabinets, and to a flow indicator in the main control room. The controller operates the charging water flow control valve (FCV-1122) to maintain a preset charging fl_ow in conjunction with a signal from the pressurizer level instrumentation. The two signals maintain pressurizer level within the proscribed band and limit the maximum and minimum charging flow rates .

Page No. 2 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: F1CH004A PLANT SPEC POINT DESC: LOW PRESSURE LETDOWN FLOW (NL)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-560 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LETDOWN LINE DWNSTRM OF NON-REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides indication of letdown stream flow rate in the Control Room *

  • Page No.

DATE:

3 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: BWST LEVEL POINT ID: L1CS001C PLANT SPEC POINT DESC: RWST LEVEL GENERIC/COND DESC: BORATED WATER STORAGE TANK LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 4700 GALLONS MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 16970 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: MINUMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RWST ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: DRY UNIQUE SYSTEM DESC: Indicates the level in the RWST. The lowest valid signal is used. If none of the 4 signals is valid, this point is marked invalid.

  • Page No.

DATE:

4 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT SMP WR POINT ID: L1DA001C PLANT SPEC POINT DESC: CONTAINMENT WR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP WR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 11.33 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RECIRC SPRAY SUMP-SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Two transmitters (LT-RS-151A-2 & B-2) monitor recirc spray sunp level in the sump itself (0-6 1 811 ) and an two additional transmitters (LT-RS-151A-1 & B-1) monitor the level above the sump itself (6 1 811 -11 1 411 ) . The valid wide range signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

  • Page No.

DATE:

5 REACTOR UN IT :

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT SMP NR POINT ID: L1DA002C PLANT SPEC POINT DESC: CONTAINMENT NR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP NR LEVEL ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 0.12 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CONTAINMENT SUMP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment sump level. The largest valid narrow range signal is used for this point. If all signals are valid, 2 signals are considered. If both signals are invalid, this point is marked invalid *

  • Page No.

DATE:

6 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 1/A POINT ID: F1FW001A PLANT SPEC POINT DESC: AFW FLOW TO SG A (Bl)<>

GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-600 11 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITITERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed pump discharge to steam generator A.

  • Page No.

DATE:

REACTOR UNIT:

7 03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 2/B POINT ID: F1FW002A PLANT SPEC POINT DESC: AFW FLOW TO SG B (YW) <>

GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-600 11 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed pump discharge to steam generator B.

  • Page No.

DATE:

8 REACTOR UN IT :

03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA1 DATA FEEDER: N/A NRC EROS PARAMETER: AX FD FL 3/C POINT ID: F1FW003A PLANT SPEC*POINT DESC: AFW FLOW TO SG C CWT)<>

GENERIC/COND DESC: STM GEN C AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-600 11 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 1C ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed pump discharge to steam generator C.

Page No. 9 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 1/A POINT ID: F1FW005C PLANT SPEC POINT DESC: SG A MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN A. MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0-796.92 11 H20 MINIMUM INSTR RANGE: -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HEATR DISCH UPSTRM OF STM GEN 1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1A.

The average of the valid feed flow signals is used for this point. If all signals are vaUd, 2 s i gnats will be used *

  • Page No.

DATE:

10 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEOER: N/A NRC ERDS PARAMETER: MN FOFL 2/B POINT ID: F1FW006C PLANT SPEC POINT DESC: SG B MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN B MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0-796.92 11 H20 MINIMUM INSTR RANGE: -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE

  • SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HEATR DISCH UPSTRM OF STM GEN 1B ALARM/TRIP SETPOINTS: . VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR OP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1B.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used *

  • Page No.

DATE:

11 03/21/91 STATION: North Anna UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 3/C POINT ID: F1FIJ007C PLANT SPEC POINT DESC: SG C MAIN FEEDIJATER FLOW GENERIC/COND DESC: STM GEN C MAIN FEEDIJATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0*796.92 11 H20 MINIMUM INSTR RANGE:* -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDIJTR HEATR DISCH UPSTRM OF STM GEN 1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1C.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used *

  • Page No.

DATE:

12 REACTOR UN IT :

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 1/A POINT ID: L1FW004A PLANT SPEC POINT DESC: SG A WR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1-RC-E-1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1-RC-E-1A.

Page No. 13 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 2/B POINT ID: L1FW008A PLANT SPEC POINT DESC: SG B WR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1-RC-E-1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1-RC-E-1B.

  • Page No.

DATE:

14 REACTOR UNIT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L1FW012A PLANT SPEC POINT DESC: SG C WR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 1-RC-E-1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1-RC-E-1C.

Page No. 15 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 1/A POINT ID: L1FW001C PLANT SPEC POINT DESC: STEAM GENERATOR A LEVEL GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.4411 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 533 11 & TOP AT 677" ALARM/TRIP SETPOINTS: VARIABLE Nl DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1A. The valid

  • narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid *
  • Page No.

DATE:

16 05/17/91 STATION:.North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 2/B POINT ID: L1FW002C PLANT SPEC POINT DESC: STEAM GENERATOR B LEVEL GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO. POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 533 11 & TOP AT 67711 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1B. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

  • Page No.

DATE:

17 05/17/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC_ERDS PARAMETER: SG LEVEL 3/C POINT ID: L1FW003C PLANT SPEC _POINT DESC: STEAM GENERATOR C LEVEL GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 533 11 & TOP AT 67711 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1C. The valid narrow range signals are averaged (3 signals if all are val id). If none of the signals is val id, this point is marked invalid *

  • Page No.

DATE:

18 REACTOR UNIT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: H2 CONC POINT ID: A1GW001C PLANT SPEC POINT DESC: CNTMT H2 CONCENTRATION GENERIC/COND DESC: CONTAINMENT HYDROGEN CONC ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: . N/A MINIMUM INSTR RANGE: -1.5 MAXIMUM INSTR RANGE: 10.0

. . ZERO POI NT

REFERENCE:

N/A

**~: . - .

REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: AUX BLDG ELEV 259 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Takes a sample of contairvnent atmosphere and measures the hydrogen concentration in the sample.

The valid signals are averaged (2 signals if all are valid).

  • 1f none of the signals is val id, this point is marked invalid
  • Page No. 19 STATION: North Anna 05/21/91 UNIT: 1 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT PRESS POINT ID: P1LM001C PLANT SPEC POINT DESC: CONTAINMENT PRESSURE GENERIC/COND DESC: CONTAINMENT PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIA ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CABLE PENETRATION AREA IN AUX BLDG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POYER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment pressure. The valid intermediate range signals (4 signals if all are valid) are averaged. If no intermediate range signals are valid, the average of the wide range signals is used (2 signals if all are valid). If no signals are valid, this point is marked invalid .

Page No. 20 STATION: North Anna 05/21/91 UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT TEMP POINT ID: T1LM001C PLANT SPEC POINT DESC: CONTAINMENT TEMPERATURE GENERIC/COND DESC: CONTAINMENT TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOIJ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: REACTOR CONTAINMENT ELEV 270 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON PO'wER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment temperature. The valid signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

  • Page No.

DATE:

21 REACTOR UN IT :

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 1/A POINT ID: P1MS001C PLANT SPEC POINT DESC: SG A PRESSURE GENERIC/COND DESC: STEAM GENERATOR A PRESSURE ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -14.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HO\./ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 1-RC-E-1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\.IER SUPPLY CUT-OFF PO\.IER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON PO\.IER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator A to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

  • Page No.

DATE:

22 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS 2/B POINT ID: P1MS002C PLANT SPEC POINT DESC: SG B PRESSURE GENERIC/COND DESC: STEAM GENERATOR B PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION:* N/A MINIMUM INSTR RANGE: -14.0

.MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 1-RC-E-1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator B to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid *

  • Page No.

DATE:

23 03/21/91

, STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS 3/C POINT ID: P1MS003C PLANT SPEC POINT DESC: SG C PRESSURE GENERIC/COND DESC: STEAM GENERATOR C PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -14.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 1-RC-E-1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator C to the main steam manifold. The val id wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid *

  • Page No.

DATE:

24 REACTOR UNIT:

05/17/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: NI SOURC RNG POINT ID: M1NM001C PLANT SPEC POINT DESC: SOURCE LEVEL POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, SOURCE RNG ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPS ENGR UNITS CONVERSION: 1e 1e-3% Power MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1000000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: 10e-10 AMPS IR NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: <10e-10 AMPS IR INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: NI cut off requires the listed reading on either of the intermediate range instr1.111ents and NI cut on requires the listed reading on both of the intermediate range instr1.111ents CIR is on the intermediate range power scale). The highest valid source range signal is used for this point. 2 source range signals are available for use. If neither of the source range signals is valid, this point is marked invalid.

The source range inputs are logrithmic in nature.

Therefore, the highest valid source range signal is exponentiated to yield the value for this point

  • Page No. 25 STATION: North Anna 05/21/91 UNIT: 1 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: NI INTER RNG POINT ID: M1NM003C PLANT SPEC POINT DESC: INTERMEDIATE RANGE POYER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, INT RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: AMPS ENGR UNITS CONVERSION: 3e 120% Power MINIMUM INSTR RANGE: 1.0E-11 MAXIMUM INSTR RANGE: 1.2589E-3 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOY PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A

  • NI DETECTOR POYER SUPPLY TURN-ON POYER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: The highest valid intermediate range signal is used for this point. 2 intermediate range signals are available for use.

If neither of the intermediate range signals is valid, this point is marked invalid. The intermediate range inputs are logrithmic in nature. Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point .

Page No. 26 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: NI POWER RNG POINT ID: M1NM005C PLANT SPEC POINT DESC: POWER RANGE AVERAGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, POWER RANGE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid power range signals are averaged for this point.

4 power range signals are available for use. If none of the power range signals is valid, this point is marked invalid .

  • Page No.

DATE:

27 REACTOR UN IT :

05/17/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: CORE FLOW POINT ID: F1RC004C PLANT SPEC POINT DESC: AVERAGE RCS LOOP FLOW GENERIC/COND DESC: TOTAL REACTOR FLOW ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-260 11 H20 0-96400 GPM 0-35e6 LBM/HR MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 9 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STEAM GEN DISCH UPSTRM OF RCP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the flow of coolant* from the steam generator to the reactor coolant pump *. The average of the 3 loop calculated average flows is used for this point. The 3 loop average values are calculated by taking the average of the valid flow signals for each loop. If all loop flow signals are valid, 3 flow readings will be used for each loop .

Page No. 28 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: REAC VES LEV POINT ID: L1RC001C PLANT SPEC POINT DESC: REAC VSL FULL RANGE LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: The 2 reactor full range level signals are used in conjunction with the reactor coolant pump CRCP) breaker statuses to calculate this value. The full range readings are invalid if any RCP is running; therefore, this point will be set invalid if any RCP breaker is closed. If none of the RCP breakers are closed, the average of the valid full range level signals is used to calculate this point *

  • Page No.

DATE:

29 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/9)

DATA FEEDER: N/A NRC EROS PARAMETER: PRZR LEVEL POINT ID: L1RC002C PLANT SPEC POINT DESC: PRESSURIZER LEVEL GENERIC/COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 3.91 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 0% CORRESPONDS TO 660.35 GALLONS H20 PROC OR SENS: p NUMBER OF SENSORS: 3 HO\.I PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS:* PRESSURIZER - HP LOCATED 32.57 1 ABOVE LP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF PO\.IER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON PO\.IER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses pressurizer level and provides alarm and control function inputs when the plant is operating normally (calibrated for 550 DEGF). The valid signals are averaged (3 signals if all are valid). If none of the signals are valid, this point is marked invalid *

  • Page No.

DATE:

30 REACTOR UNIT:

03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT* LIBRARY REFERENCE FILE 05/21/91 NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: REAC VES LEV POINT ID: L1RC003C PLANT SPEC POINT DESC: RVLIS DYNAMIC HEAD LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: The 2 DYNAMIC HEAD level signals are used in conjunction with the reactor coolant punp (RCP) breaker statuses to calculate this value. The dynamic head readings are invalid if no RCP's are running; therefore, this point will be set invalid if no RCP breakers are closed. If any of the RCP breakers are closed, the average of the valid dynamic head level signals is used to calculate this point *

  • Page No.

DATE:

31 REACTOR UNIT:

03/21/91 NA1 STATION: North Anna UNIT: 1 P~R DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS PRESSURE POINT ID: P1RC001C PLANT SPEC POINT DESC: RCS AVERAGE PRESSURE GENERIC/COND DESC: REACTOR COOLANT SYSTEM PRESSURE ANALOG/DIG ITAL : A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 3000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 H~ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR P~ER SUPPLY CUT-OFF P~ER LEVEL: N/A NI DETECTOR P~ER SUPPLY TURN-ON P~ER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: PT-1455, PT-1456, and PT-1457 all measure pressurizer narrow range pressure and are used for pressurizer pressure protection. PT-1402 is located on the loop C hot leg and PT-1403 is located on the loop A hot leg and both monitor RCS wide ra~ge pressure. The valid narrow range signals are averaged (3 signals if all are valid). If none of the narrow range signals valid, the average of the valid wide range signals is used (2 signals if all are valid). If none of the narrow or wide range signals is val id, thi.s point is marked invalid *

  • Page No.

DATE:

32 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 1/A POINT ID: T1RC002A PLANT SPEC POINT DESC: LOOP A WR T COLD (RD)<>

GENERIC/COND DESC: STM GEN A OUTLET TEMPERATURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A cold leg temperature

Page No. 33 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: HL TEMP 1/A POINT ID: T1RC003A PLANT SPEC POINT DESC: LOOP A WR HOT LEG TEMP (RD)<>

GENERIC/COND DESC: STM GEN A INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES.: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A hot leg temperature.

Page No. 34 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 2/B POINT ID: T1RC004A PLANT SPEC POINT DESC: LOOP B WR T COLD (WT)<>

GENERIC/COND DESC: STM GEN B OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B COLD LEG ALARM/TRIP SETPOINTS: VARIABLE Nl DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop B cold leg temperature.

Page No. 35 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: HL TEMP 2/8 POINT ID: T1RC005A PLANT SPEC POINT DESC: LOOP B WR HOT LEG TEMP (WT)<>

GENERIC/COND DESC: STM GEN B INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop B hot leg temperature.

  • Page No.

DATE:

36 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 3/C POINT ID: T1RC006A PLANT SPEC POINT DESC: LOOP C WR T COLD (BL) <>

GENERIC/COND DESC: STM GEN C OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOil PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop C cold leg temperature.

  • Page No.

DATE:

37 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 3/C POINT ID: T1RC007A PLANT SPEC POINT DESC: LOOP C WR HOT LEG TEMP (BL)<>

GENERIC/COND DESC: STM GEN C OUTLET TEMPERATURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C HOT LEG ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses Loop C hot Leg temperature.

  • Page No.

DATE:

38 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: TEMP CORE EX POINT ID: T1RC001C PLANT SPEC POINT DESC: PEAK CORE EXIT TEMP GENERIC/COND DESC: HIGHEST TEMPERATURE AT CORE EXIT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 2400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 50 HO\,I PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: EXIT OF SELECTED FUEL ASSEMBLIES IN-CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\,IER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the reactor coolant exit temperature. The highest valid incore thermocouple is used. If none of the thermocouples is valid, .this point is marked invalid .

Page No. 39 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SUB MARGIN POINT ID: T1RC020C PLANT SPEC POINT DESC: CORE EXIT TSAT MARGIN GENERIC/COND DESC: SATURATION TEMP - HIGHEST CET ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -35.0 MAXIMUM INSTR RANGE: 200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HO\.I PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: WR RCS PRESS AND INCORE TIC'S ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\.IER SUPPLY CUT-OFF PO\.IER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: The valid saturation margin inputs from the RVLIS system are averaged (2 signals if all are valid). If none of the signals are valid, this point is marked invalid .

  • Page No.

DATE:

40 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 1/A POINT ID: R1RM201C PLANT SPEC POINT DESC: MS LINE A RAD MON (170)

GENERIC/COND DESC: STM GEN A STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E*2 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER* M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch A main steam safety line indicates radiation level .

  • Page No.

DATE:

41 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PIJR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 2/B POINT ID: R1RM202C PLANT SPEC POINT DESC: MS LINE BRAD MON (171)

GENERIC/COND DESC: STM GEN B STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-2 MAXIMUM INSTR RANGE: 1. OE+?

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER - M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch B main steam safety line and indicates radiation level .

  • Page No.

DATE:

42 REACTOR UNIT:

03/21/91 NA1 STATION: North Anna UNIT: 1 P~R DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 3/C POINT ID: R1RM203C PLANT SPEC POINT DESC: MS LINE C RAD MON (172)

GENERIC/COND DESC: STM GEN C STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-2 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HO\.I PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER - M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\,IER SUPPLY CUT-OFF PO\.IER LEVEL: N/A NI DETECTOR PO\.IER SUPPLY TURN-ON PO\.IER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch C main steam safety Line and indicates radiation Level

  • Page No.* 43 STATION: North Anna 05/21/91 UN IT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R1RM204C PLANT SPEC POINT DESC: AUX STM LINE RAD MON (176)

GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 6.31E-5 MAXIMUM INSTR RANGE: 1. OE+4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE-DRIVEN AUX FEED PUMP EXHAUST ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level in the turbine-driven auxiliary feed pump exhaust ("Terry" turbine) .

Page No. 44 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: COND A/E RAD POINT ID: R1RM205C PLANT SPEC POINT DESC: CONDENSER AE RAD MON (121)

GENERIC/COND DESC: COND AIR EJECTOR RADIOACTIVITY ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTPUT OF CONDENSOR AIR EJECTORS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level in the gaseous effluent from the condensor air ejectors. On high radiation any radioactive air is diverted into the Reactor Containment .

Page No. 45 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R1RM206C PLANT SPEC POINT DESC: CNTMT GAS RAD MON (160)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1. OE+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of air taken from the reactor containment .

  • Page No.

DATE:

46 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM207C PLANT SPEC POINT DESC: CNTMT HR RAD MON COL4(166)

GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.3162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: ON THE INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level within the reactor containment .

  • Page No.

DATE:

47 REACTOR UN IT :

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM208C PLANT SPEC POINT DESC: CNTMT HR RAD MON COL 12 GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.3162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: ON THE INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level within the reactor containment .

  • Page No.

DATE:

48 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R1RM209C PLANT SPEC POINT DESC: CNTMT PERS HATCH RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E*5 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1.

HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously .monitors the radiation level in the Personnel Hatch area *

  • Page No.

DATE:

49 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R1RM210C PLANT SPEC POINT DESC: CNTMT PARTICULATE RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CµT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of particles in the air taken out of the reactor containment .

  • Page No.

DATE:

50 03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT :

DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R1RM211C PLANT SPEC POINT DESC: DISCHARGE TUNNEL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES:- CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.DE+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: DSCHRG TUNL PAST LAST PT OF RAD ADDITION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY

-* CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION

_FOR DP TRANSMITTERS:

N/A N/A N/A LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors effluent (service water, condensate cooling water, and liquid waste) in the discharge tunnel beyond the last point of radiation addition to ensure that the radiation activity levels of the plant discharge do not exceed limits .

  • Page No.

DATE:

51 REACTOR UN IT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: R1RM214C PLANT SPEC POINT DESC: RCS LETDOWN HIGH RAD MON GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: RCS LETDOWN LINE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation level in the reactor coolant by means of a sample from the letdown line .

Page No. 52 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R1RM215C PLANT SPEC POINT DESC: CNTMT AREA RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3. 162E-5 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: REACTOR CONTAINMENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Detects ganma radiation in the reactor containment.

Page No. 53 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R1RM216C PLANT SPEC POINT DESC: SW FR RCS CLR 1A RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ

. ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 1-SW-P-5 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 1-RS-E-1A which will then be monitored for radiation and returned to the service water line .

Page No. 54 STATION: North Anna 05/21/91

_ UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAO POINT ID: R1RM217C PLANT SPEC POINT DESC: SW FR RCS CLR 1B RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 1-SW-P-6 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 1-RS-E-1B which will then

  • be monitored for radiation and returned to the service water line
  • Page No. 55 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT IO: R1RM218C PLANT SPEC POINT OESC: SW FR RCS~CLR 1C RAD MON GENERIC/COND OESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 1-SW-P-7 will withdraw a continuous sample from the service water outlet Line of recirculation spray heat exchanger 1-RS-E-1C which will then be monitored for radiation and returned to the service water Line .

  • Page No.

DATE:

56 03/21/91 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R1RM219C PLANT SPEC POINT DESC: SW FR RCS CLR 10 RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 1-SW-P-8 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 1-RS-E-1D which will then be monitored for radiation and returned to the service water line .

Page No. 57 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SG BD RAD 1A POINT ID: R1RM220C PLANT SPEC POINT DESC: SG A BLWDN RAD MON GENERIC/COND DESC: STM GEN A BLOWDOWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors radiation levels in the liquid phase of steam generator 1-RC-E-1A blowdown. The sample is returned to the steam generator blowdown tank after being monit_ored *

  • Page No.

DATE:

58 REACTOR UNIT:

03/21/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: SG BD RAD 2B POINT ID: R1RM221C PLANT SPEC POINT DESC: SG B BLWDN RAD MON GENERIC/COND DESC: STM GEN B BLOWDOWN RAD LEVEL ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FORD~ TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation levels in the liquid phase of steam generator 1-RC-E-1B blowdown. The sample is returned to the steam generator blowdown tank after being monitored .

  • Page No. 59 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: SG BD RAD 3C POINT ID: R1RM222C PLANT SPEC POINT DESC: SG C BLWDN RAD MON GENERIC/COND DESC: STM GEN C BLO~OWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation levels in the liquid phase of steam generator 1-RC-E-1C blowdown. The sample is returned to the steam generator blowdown tank after being monitored .

Page No. 60 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: LP SI FLOW POINT ID: F1Sl001A PLANT SPEC POINT DESC: L HD !NJ HEADER FLOW A (NL)

GENERIC/COND DESC: LOW PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 499.3 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LPSI PUMP A DISCHARGE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides flow indication from LHSI pump A.

  • Page No.

DATE:

61 REACTOR UNIT:

05/17/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: LP SI FLOW POINT ID: F1SI002A PLANT SPEC POINT DESC: L HD INJ HEADER FLOW B (NL)

GENERIC/COND DESC: LOW PRESSURE SI FLOW ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 499.3 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LPSI PUMP B DISCHARGE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication from LHSI pump B.

  • Page No.

DATE:

62 REACTOR UN IT:

05/17/91 NA1 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F1SI003A PLANT SPEC POINT DESC: TOTAL HOT LEG SI FLOW CWT)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRGING PMP DISCH UPSTRM OF HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHS!

pumps to the hot leg of each loop

  • Page No. 63 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: HP SI FLOW POINT ID: F1SI001C PLANT SPEC POINT DESC: TOT COLD LEG HHS! FLOW GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: o.o MAXIMUM INSTR RANGE: 750.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: SUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CHRGING PMP DISCH UPSTRM OF COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHSI pumps to the cold leg of each loop. The 3 loop high head SI flows are totaled for this value. If any one of the loop SI values is invalid, this point will be marked invalid .

Page No. 64 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM001A PLANT SPEC POINT DESC: WEATHER - SIGMA THETA (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: PRIMARY TOWER TRAILER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Uses Lower wind direction to find the standard deviation of the wind direction angle which is referred to as horizontal atmospheric stability .

Page No. 65 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM002A PLANT SPEC POINT DESC: WEATHER - UPPER DELTA (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -9.0 MAXIMUM INSTR RANGE: 9.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 2 RTD 1 S AT 35 1 & 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLr TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

UNIQUE SYSTEM DESC:

N/A N/A N/A Uses the difference of upper temperature and lower temperature to calculate vertical atmospheric stability

  • Page No. 66 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM003A PLANT SPEC POINT DESC: LOWER WIND DIRECTION (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 540.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35 1 ON PRIMARY & BACKUP TOWERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses the wind direction at 35 1

  • Page No. 67 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM004A PLANT SPEC POINT DESC: UPPER WIND DIRECTION (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 540.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150' ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses the wind direction at 150°.

Page No. 68 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED POINT ID: M3MM007A PLANT SPEC POINT DESC: LOWER WIND SPEED (NL)

GENERIC/COND DESC: WIND SPEED AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35' ON PRIMARY & BACKUP TOWERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures the wind speed at 35 1

  • Page No. 69 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91

-REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED POINT ID: M3MM008A PLANT SPEC POINT DESC: UPPER WIND SPEED (NL)

GENERIC/COND DESC: WIND SPEED AT THE REACTOR SITE ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI _DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Measures the wind speed at 150 1

  • Page No. 70 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: STAB CLASS POINT ID: T3MM001A PLANT SPEC POINT DESC: ATMOS AMBIENT TEMPERATURE (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -22.0 MAXIMUM INSTR RANGE: 122.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: RTD AT 35 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Measures air temperature at 35 1 elevation on the primary tower .

Page No. 71 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM211C PLANT SPEC POINT DESC: PV GAS RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: PROCESS VENT LINE DWNSTRM OF EVAPORATORS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of a sample taken from the process vent after it has passed through the particulate filters

  • Page No. 72 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM212C PLANT SPEC POINT DESC: PV PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the particules in a sample taken from the process vent

  • Page No. 73 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM214C PLANT SPEC POINT DESC: SW DISCH TO RSVR RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF-LINE IN A CMN HOR OF 2 36"DSCH LINES ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the service water discharge to the service water reservoir .

  • Page No. 74 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM215C PLANT SPEC POINT DESC: SW DISCH TO CANAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF*LINE IN A CMN HOR OF 2 24 11DSCH LINES ALARM/TRIP SETPOINTS: VARIABLE NI* DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the service water discharge to the discharge canal

  • Page No. 75 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM216C PLANT SPEC POINT DESC: SW FROM CC HX RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF-LINE IN A CMN HOR OF 4 HEAT XCHNGERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A_

UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the service water effluent from the component cooling heat exchangers .

Page No. 76 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21791

  • REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM217C PLANT SPEC POINT DESC: VS GASEOUS RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 84 11 DIAMETER VENTILATION STACK ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of a variable sample of the ventilation stack air taken through a multiprobe isokinetic sampling nozzle .

Page No. 77 STATION: North Anna 05/21/91 UNIT: 1 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM218C PLANT SPEC POINT DESC: VS PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOY PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 84" DIAMETER VENTILATION STACK ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation Level of the particles in a variable sample of the ventilation stack air taken through a multiprobe isokinetic sampling nozzle

  • Page No. 78 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM219C PLANT SPEC POINT DESC: VV GAS RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1. OE+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 90 11 DIAMETER VENT! LAT ION VENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of a variable sample of the ventilation vent air taken through a multiprobe isokinetic sampling nozzle .

Page No. 79 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM220C PLANT SPEC POINT DESC: VV PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 90 11 DIAMETER VENTILATION VENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of particles in a variable sample of the ventilation vent air taken through a multiprobe isokinetic sampling nozzle *

  • Page No. 80 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM221C PLANT SPEC POINT DESC: VV GAS SAMPLE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation in an air sample taken from one of eight areas. The operator can select a sampling time at each of the eight areas between 30 min. and 24 hrs. The areas that can be selected are fuel bldg., safeguards area of unit 1 or unit 2, aux bldg. central area (2 separate sampling apparatus), containment purge, decontamination bldg., and a spare .

Page No. 81 STATION: North Anna 05/21/91 UNIT: 1 P\.IR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM222C PLANT SPEC POINT DESC: VV PART SAMPLE RAD HON GENERIC/COND OESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HO\.I PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation of particles in an air sample taken from one of eight areas. The operator can select a sampling time at each of the eight areas between 30 min. and 24 hrs.

The areas that can be selected are fuel bldg., safeguards area of unit 1 or unit 2, aux bldg. central area (2 separate sampling apparatus), containment purge, decontamination bldg., and a spare .

Page No. 82 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM223C PLANT SPEC POINT DESC: PV HIGH RADN RATE MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+5 MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SERV BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Takes a sample from stacks A & Band measures the radiation level in the sample. This is the high range instrument for this data .

Page No. 83 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM224C PLANT SPEC POINT DESC: PV NORM RADN RATE MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG* STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 .

MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SWGR BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continually senses radiation Level in a sample stream from the process vent and provides a signal to RM-GW-108-1A's micro computer for determination of radiation release rate.

This is the normal range instrunent for this data .

Page No. 84 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM225C PLANT SPEC POINT DESC: PV NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SWGR BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continually senses radiation level in a sample stream from the process vent. This is the normal range instrument for this data .

Page No. 85 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM226C PLANT SPEC POINT DESC: VS A HIGH RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-4 MAXIMUM INSTR RANGE: 1.0E+S ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation Level in a sample taken from vent stack "A". This is the high range instrument for this data .

Page No. 86 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM227C PLANT SPEC POINT DESC: VS A HIGH RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+S MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-2A's microcomputer for determination of radiation release rate. This is the high range instrument for this data

  • Page No. 87 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM228C PLANT SPEC POINT DESC: VS A NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: senses radiation level in a sample taken from vent stack "A". This is the normal range instrument for this data .

Page No. 88 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM229C PLANT SPEC POINT DESC: VS A NORM RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a salll)le taken from vent stack "A" and provides a signal to RG-VG179-1A's microcomputer for determination of radiation release rate. This is the normal range instrument for this data .

Page No. 89 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM230C PLANT SPEC POINT DESC: VS B HIGH RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3. 162E-4 MAXIMUM INSTR RANGE: 1 .OE+S ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR PO\..IER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack 11 811 and provides a signal to RG*VG-180-2A's microcomputer for determination of radiation release rate. This is the high range instrument for this data

  • Page No. 90 STATION: North Anna. 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM231C PLANT SPEC POINT DESC: VS B HIGH RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+5 MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FA! LURE MOOE: . N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sa~le taken from vent stack "B". This is the high range instrument for this data .

Page No. 91 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM232C PLANT SPEC POINT DESC: VS B NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI. DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack 11 8 11

  • This is the normal range instrument for this data
  • Page No. 92 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM233C PLANT SPEC POINT DESC: VS B NORM RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a saq,le taken from vent stack "B" and provides a signal to RG-VG180-1A's microcomputer for determination of radiation release rate. This is the normal range instrument for this data

  • Page No. 93 STATION: North Anna 05/21/91 UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA1 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM234C PLANT SPEC POINT DESC: PV HIGH RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-4 MAXIMUM INSTR RANGE: 1.0E+S ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SERV BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample stream from the process vent. This is the high range instrl.lllent for this data .

  • ATTACHMENT 4 NORTH ANNA UNIT 2 DATA POINT LIBRARY LISTINGS

-- -- ~---------------

  • Page No.

DATE: 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: RCS CHG/MU POINT ID: F2CH003A PLANT SPEC POINT DESC: CHARGING LOOP FLOW (NL)

GENERIC/COND DESC: PRIM SYS CHARGING OR MAKEUP FLOW ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-648 11 H_20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHARGING LINE UPSTREAM OF REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Flow transmitter FT-2122 transmits a signal to a controller located in the control cabinets, and to a flow indicator in the main control room. The controller operates the charging water flow control valve (FCV-2122) to maintain a preset charging fl~w in conjunction with a signal from the pressurizer level instrllllentation. The two signals maintain pressurizer level within the proscribed band and limit the maximum and minimun charging flow rates .

  • Page No.

DATE:

2 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LTDN RAD POINT ID: F2CH004A PLANT SPEC POINT DESC: LOW PRESSURE LETDOWN FLOW (NL)

GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-560 11 H20 MINIMUM INSTR RANGE: o.o MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS.A DIRECT SENSOR INPUT SENSOR LOCATIONS: LETDOWN LINE DWNSTRM OF NON-REGEN HX ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides indication of letdown stream flow rate in the Control Room .

  • Page No.

DATE:

3 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DS/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: BWST LEVEL POINT ID: L2CS001C PLANT SPEC POINT DESC: RWST LEVEL GENERIC/COND DESC: BORATED WATER STORAGE TANK LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 4700 GALLONS MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 16970 GALLONS REMAIN AT ZERO POINT PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: MINUMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RWST ALARM/TRIP SETPOINTS: VARIABLE

-. NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION N/A N/A.

N/A FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: DRY UNIQUE SYSTEM DESC: Indicates the level in the RWST. The lowest valid signal is used. If none of the 4 signals is valid, this point is marked invalid .

  • Page No.

DATE:

4 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT SMP WR POINT ID: L2DA001C PLANT SPEC POINT DESC: CONTAINMENT WR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP WR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 11.33 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE

  • SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: RECIRC SPRAY SUMP*SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Two transmitters CLT*RS*251A*2 & B-2) monitor recirc spray sunp Level in the sunp itself (0-6 1 8 11 ) and an two additional transmitters CLT-RS-251A-1 &B-1) monitor the Level above the sunp itself (6 1 811 -11 1 411 ) . The valid wide range signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

  • Page No.

DATE:

5 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PIJR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT SMP NR POINT ID: L2DA002C PLANT SPEC POINT DESC: CONTAINMENT NR SUMP LEVEL GENERIC/COND DESC: CONTAINMENT SUMP NR LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 0.12 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOIJ PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CONTAINMENT SUMP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment sunp level. The largest valid narrow range signal is used for this point. If all signals are valid, 2 signals are considered. If both signals are invalid, this point is marked invalid .

  • Page No.

DATE:

6 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 1/A POINT ID: F2FW001A PLANT SPEC POINT DESC: AFW FLOW TO SG A (BL)<>

GENERIC/COND DESC: STM GEN A AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-60011 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.00 ZERO POINT.

REFERENCE:

N/A

. REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed punp discharge to steam generator A.

  • Page No.

DATE:

7 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 2/8 POINT ID: F2FW002A PLANT SPEC POINT DESC: AFW FLOW TO SG B (YW) <>

GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-600 11 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.00 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 18 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed pump discharge to steam generator B.

  • Page No.

DATE:

8 REACTOR UN IT :

03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE*

05/21/91 NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: AX FD FL 2/B POINT ID: F2FW003A PLANT SPEC POINT DESC: AFW FLOW TO SG C (WT)<>

GENERIC/COND DESC: STM GEN B AUX FEEDWATER FLOW ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0-600 11 H20 MINIMUM INSTR RANGE: -0.2 MAXIMUM INSTR RANGE: 500.00 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: AUX FEED PMP DISCH UPSTRM OF STM GEN 1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses auxiliary feed punp discharge to steam generator C.

Page No. 9 STATION: North Anna 05/21/91 UNIT: 2 PWR_DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 1/A POINT ID: F2FW005C PLANT SPEC POINT DESC: SG A MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN A MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0-796.92 11 H20 MINIMUM INSTR RANGE: -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HEATR DISCH UPSTRM OF STM GEN 1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1A.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used .

  • Page No.

DATE:

10 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: MN FD FL 2/B POINT ID: F2FW006C PLANT SPEC POINT DESC: SG B MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN B MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0-796.92 11 H20 MINIMUM INSTR RANGE: -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HEATR DISCH UPSTRM OF STM GEN 1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL ~EFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1B.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used *

  • Page No.

DATE:

11 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: MN FD FL 3/C POINT ID: F2FW007C PLANT SPEC POINT DESC: SG C MAIN FEEDWATER FLOW GENERIC/COND DESC: STM GEN C MAIN FEEDWATER FLOW ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: 0-796.9211 H20 MINIMUM INSTR RANGE: -0.1 MAXIMUM INSTR RANGE: 5.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: FEEDWTR HEATR DISCH UPSTRM OF STM GEN 1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses flow in main feedwater line to steam generator 1C.

The average of the valid feed flow signals is used for this point. If all signals are valid, 2 signals will be used *

  • Page No.

DATE:

12 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG LEVEL 1/A POINT ID: L2FW004A PLANT SPEC POINT DESC: SG A WR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 2-RC-E*1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2-RC*E-1A.

Page No. 13 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC .ERDS PARAMETER: SG LEVEL 2/B POINT ID: L2FW008A PLANT SPEC POINT DESC: SG B WR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 2-RC-E-1B ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2-RC-E-1B.

  • Page No.

DATE:

14 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PYR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L2FY012A PLANT SPEC POINT DESC: SG CYR LEVEL (NL)<>

GENERIC/COND DESC: STEAM GENERATOR C YATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-575 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOY PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: STEAM GENERATOR 2-RC-E-1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A NI DETECTOR POYER SUPPLY TURN-ON POYER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: YET UNIQUE SYSTEM DESC: Senses the water level in steam generator 2-RC-E-1C.

  • Page No.

DATE:

15 REACTOR UNIT:

05/17/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 1/A POINT ID: L2FW001C PLANT SPEC POINT DESC: STEAM GENERATOR A LEVEL GENERIC/COND DESC: STEAM GENERATOR A WATER LEVEL ANALOG/0 I GIT AL : A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.44" H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 3 HQ\./ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 533 11 & TOP AT 67711 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMEN~ FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1A. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

  • Page No.

DATE:

16 05/17/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 2/B POINT ID: L2FW002C PLANT SPEC POINT DESC: STEAM GENERATOR B LEVEL GENERIC/COND DESC: STEAM GENERATOR B WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 3 HO\J PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN*BOTTOM AT 533 11 & TOP AT 67711 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF PO\JER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1B. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 17 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: SG LEVEL 3/C POINT ID: L2FW003C PLANT SPEC POINT DESC: STEAM GENERATOR C LEVEL GENERIC/COND DESC: STEAM GENERATOR C WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 1.44 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

UTUBES REFERENCE POINT NOTES:

PROC OR SENS: P NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STM GEN-BOTTOM AT 533 11 & TOP AT 677" ALARM/TRIP SETPOINT.S: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: Senses the water level in steam generator 1C. The valid narrow range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

I Page No. 18 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NAZ DATA FEEDER: N/A NRC ERDS PARAMETER: H2 CONC POINT ID: A2GW001C PLANT SPEC POINT DESC: CNTMT H2 CONCENTRATION GENERIC/COND DESC: CONTAINMENT HYDROGEN CONC ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -1.5 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: AUX BLDG ELEV 259 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Takes a sample of containment atmosphere and measures the hydrogen concentration in the sample.

The valid signals are averaged (2 signals if all are valid).

If none of the signals is valid, this point is marked invalid .

Page No. 19 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAM.ETER: CTMNT PRESS POINT ID: P2LM001C PLANT SPEC POINT DESC: CONTAINMENT PRESSURE GENERIC/COND DESC: CONTAINMENT PRESSURE ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: PSIA ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 180.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CABLE PENETRATION AREA IN AUX BLDG ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment pressure. The valid intermediate range signals (4 signals if all are valid) are averaged. If no intermediate range signals are valid, the average of the wide range signals is used (2 signals if all are valid). If no signals are valid, this point is marked invalid *

  • Page No. 20 STATION: North Anna 05/21/91 UNIT: 2 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT TEMP POINT ID: T2LM001C PLANT SPEC POINT DESC: CONTAINMENT TEMPERATURE GENERIC/COND DESC: CONTAINMENT TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: REACTOR CONTAINMENT ELEV 270 ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POYER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses reactor containment temperature. The valid signals are averaged (2 signals if all are valid). If neither signal is valid, this point is marked invalid .

Page No. 21 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 1/A POINT ID: P2MS001C PLANT SPEC POINT DESC: SG A PRESSURE GENERIC/COND DESC:

  • STEAM GENERATOR A PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -14.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE *sYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 2*RC-E-1A ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A

. TEMPERATURE COMPENSATION FOR OP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator A to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

  • Page No.

DATE:

22 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS 2/B POINT ID: P2MS002C PLANT SPEC POINT DESC: SG B PRESSURE GENERIC/COND DESC: STEAM GENERATOR B PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -14.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 2-RC-E-1B ALARM/TRIP SETPO!NTS: VARIABLE Ni' DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator B to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

  • Page No.

DATE:

23 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: SG PRESS 3/C POINT ID: P2MS003C PLANT SPEC POINT DESC: SG C PRESSURE GENERIC/COND DESC: STEAM GENERATOR C PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -14.0 MAXIMUM INSTR RANGE: 1400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOIJ PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: OUTPUT OF STM GEN 2-RC-E-1C ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides pressure of the steam which is on route from steam generator C to the main steam manifold. The valid wide range signals are averaged (3 signals if all are valid). If none of the signals is valid, this point is marked invalid .

Page No. 24 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: NI SOURC RNG POINT ID: M2NM001C PLANT SPEC POINT DESC: SOURCE LEVEL POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, SOURCE RNG ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPS ENGR UNITS CONVERSION: 1e 1e-3% Power MINIMUM INSTR RANGE: 1.0 MAXIMUM INSTR RANGE: 1000000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: 10e-10 AMPS IR NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: <10e-10 AMPS IR INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:_

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: NI cut off requires the listed reading on either of the intermediate range instruments and NI cut on requires- the listed reading on both of the intermediate range instruments CIR is on the intermediate range power scale). The highest valid source range signal is used for this point. 2 source range signals are available for use. If neither of the source range signals is valid, this point is marked invalid.

The source range inputs are logrithmic in nature.

Therefore, the highest valid source range signal is exponentiated to yield the value for this point .

  • Page No.

DATE:

25 REACTOR UN IT:

05/17/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA2 DATA FEEDER: N/A NRC EROS PARAMETER: NI INTER RNG POINT ID: M2NM003C PLANT SPEC POINT DESC: INTERMEDIATE RANGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, INT RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: AMPS ENGR UNITS CONVERSION: 3e 120% Power MINIMUM INSTR RANGE: 1.0E-11 MAXIMUM INSTR RANGE: 1.2589E-3 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The highest valid intermediate range signal is used for this point. 2 intermediate range signals are available for use.

If neither of the intermediate range signals is valid, this point is marked invalid. The intermediate range inputs are logrithmic in nature. Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point .

  • Page No.

DATE:.

26 REACTOR UNIT:

05/17/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/9~

DATA FEEDER: N/A NRC ERDS PARAMETER: NI POWER RNG POINT ID: M2NMOOSC PLANT SPEC POINT DESC: POWER RANGE AVERAGE POWER GENERIC/COND DESC: NUCLEAR INSTRUMENTS, POWER RANGE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p.

NUMBER OF SENSORS: 4 HOW PROCESSED: AVERAGE* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: ADJACENT TO OUTSIDE OF REACTOR VESSEL ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid power range signals are averaged for this point.

4 power range signals are available for use. If none of the power range signals is valid, this point is marked invalid

  • l
  • Page No.

DATE:

27 05/17/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: CORE FLOW POINT ID: F2RC004C PLANT SPEC POINT DESC: AVERAGE RCS LOOP FLOW GENERIC/COND DESC: TOTAL REACTOR FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 0-260 11 H20 0-96400 GPM 0-35e6 LBM/HR MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR ~ANGE: 120.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p

  • NUMBER OF SENSORS: 9 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: STEAM GEN DISCH UPSTRM OF RCP ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the flow of coolant from the steam generator to the reactor coolant pump. The average of the 3 loop calculated average flows is used for this point. The 3 loop average values are calculated by taking the average of the valid flow signals for each loop. If all loop flow signals are valid, 3 flow readings will be used for each loop *

  • Page No.

DATE:

28 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: REAC VES LEV POINT ID: L2RC001C PLANT SPEC POINT DESC: REAC VSL FULL RANGE LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: The 2 reactor full range level signals are used in conjunction with the reactor coolant pump (RCP) breaker statuses to calculate this value. The full range readings are invalid if any RCP is running; therefore, this point will be set invalid if any RCP breaker is closed. If none of the RCP breakers are closed, the average of the valid full range level signals is used to calculate this point .

Page No. 29 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: PRZR LEVEL POINT ID: L2RC002C PLANT SPEC POINT DESC: PRESSURIZER LEVEL GENERIC/COND DESC: PRIMARY SYSTEM PRESSURIZER LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: 1% = 3.91 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: 0% CORRESPONDS TO 660.35 GALLONS H20 PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: PRESSURIZER - HP LOCATED 32.57' ABOVE LP ALARM/TRIP SETPOINTS: VARIABLE NJ DETECTOR POWER SUPPLY CUT-OFF*POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A WET UNIQUE SYSTEM DESC: Senses *pressurizer level and provides alarm and control function inputs when the plant is operating normally (calibrated for 550 DEGF). The valid signals ar~ averaged (3 signals if all are valid). If none of the signals are valid, this point is marked invalid .

  • Page No.

DATE:

30 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: REAC VES LEV POINT ID: L2RC003C PLANT SPEC POINT DESC: . RVLIS DYNAMIC HEAD LEVEL GENERIC/COND DESC: REACTOR VESSEL WATER LEVEL ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: PCT ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 120.0 ZERO POINT

REFERENCE:

TNKBOT REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 5 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: HEAD VENT (TOP) & BOTTOM OF VESSEL ALARM/TRIP SETPOINTS: VARIABLE NrDETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: WET UNIQUE SYSTEM DESC: The 2 DYNAMIC HEAD level signals are used in conjunction with the reactor coolant punp CRCP) breaker statuses to calculate this value. *The dynamic head readings are invalid if no RCP's are running; therefore, this point will be set invalid if no RCP breakers are closed. If any of the RCP breakers are closed, the average of the valid dynamic head level signals is used to calculate this point .

  • Page No.

DATE:

31 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: RCS PRESSURE POINT ID: P2RC001C PLANT SPEC POINT DESC: RCS AVERAGE PRESSURE GENERIC/COND DESC: REACTOR COOLANT SYSTEM PRESSURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 3000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: SEE SYSTEM DESCRIPTION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: PT-2455, PT-2456, and PT-2457 all measure narroe range pressurizer pressure and are used for pressurizer pressure protection. PT-2402 is located on the loop C hot 'teg and PT-2403 is located on the loop A hot leg and both monitor RCS wide range pressure. The valid narrow range signals are averaged (3 signals if all are val id). If none of the narrow range signals valid, the average of the valid wide range signals is used (2 signal.s if all are valid). If none of the narrow or wide range signals is valid, this point is marked invalid .

  • Page No.

DATE:

32 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNJT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 1/A POINT ID: T2RC002A PLANT SPEC POINT DESC: LOOP A WR T COLD (RD)<>

GENERIC/COND DESC: STM GEN A OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES.: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: . LOOP A COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A cold leg temperature.

  • Page No.

DATE:

33 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NAZ DATA FEEDER: N/A NRC ERDS PARAMETER: HL TEMP 1/A POINT ID: T2RC003A PLANT SPEC POINT DESC: LOOP A WR HOT LEG TEMP (RD)<>

GENERIC/COND DESC: STM GEN A INLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: a.a MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP A HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop A hot leg temperature .

  • Page No.

DATE:

34 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: CL TEMP 2/B POINT ID: T2RC004A PLANT SPEC POINT DESC: LOOP B WR T COLD CWT)<>

GENERIC/COND DESC: STM GEN B OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s

.* NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop B cold leg temperature.

  • Page No. 35 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: HL TEMP 2/B POINT ID: T2RC005A PLANT SPEC POINT DESC: LOOP B WR HOT LEG TEMP CWT)<>

GENERIC/COND DESC: STM GEN B INLET TEMPERATURE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: . N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP B HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop B hot leg temperature.

  • Page No.

DATE:

36 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: *CL TEMP 3/C POINT ID: T2RC006A PLANT SPEC POINT DESC: LOOP C WR T COLD (BL)<>

GENERIC/COND DESC: STM GEN C OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop C cold leg temperature.

  • Page No.

DATE:

37 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: CL TEMP 3/C POINT ID: T2RC007A PLANT SPEC POINT DESC: LOOP C WR HOT LEG TEMP (BL)<>

GENERIC/COND DESC: STM GEN C OUTLET TEMPERATURE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 700.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A

  • THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LOOP C HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses loop* C hot leg temperature .

  • Page No.

DATE:

38 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: TEMP CORE EX POINT ID: T2RC001C PLANT SPEC POINT DESC: PEAK CORE EXIT TEMP GENERIC/COND DESC: HIGHEST TEMPERATURE AT CORE EXIT ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 2400.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 50 HOW PROCESSED: MAXIMUM - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: EXIT OF SELECTED FUEL ASSEMBLIES IN-CORE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the reactor coolant exit temperature. The highest valid incore thermocouple is used. If none of the thermocouples is valid, this point is marked invalid .

  • Page No.

DATE:

39 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: SUB MARGIN POINT ID: T2RC020C PLANT SPEC POINT DESC: CORE EXIT TSAT MARGIN GENERIC/COND DESC: SATURATION TEMP - HIGHEST CET ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -35.0 MAXIMUM INSTR RANGE: 200.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: AVERAGE - SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: WR RCS PRESS AND INCORE T/C's ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: The valid saturation margin inputs from the RVLIS system are averaged (2 signals if all are valid). If none of the signals are valid, this point is marked invalid *

  • Page No.

DATE:

40 03/21/91 STATION: North Anna UNIT: 2 PWR DATA.POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: MAIN SL 1/A POINT ID: R2RM201C PLANT SPEC POINT DESC: MS LINE A RAD MON (270)

GENERIC/COND DESC: STM GEN A STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-2 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER - M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch A main steam safety line and indicates radiation level .

  • Page No.

DATE:

41 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: MAIN SL 2/B POINT ID: R2RM202C PLANT SPEC POINT DESC: MS LINE BRAD MON (271)

GENERIC/COND DESC: STM GEN B STEAM LINE RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-2 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER - M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch B main steam safety line and indicates radiation Level .

  • Page No.

DATE:

42 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL 3/C POINT ID: R2RM203C PLANT SPEC POINT DESC: MS LINE C RAD MON (272)

GENERIC/COND DESC: STM GEN C STEAM LINE RAD LEVEL ANALOG/DIG ITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-2 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: MN STM SAFETY VLV RISER - M.S. VLV HOUSE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR OP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the 32 inch C main steam safety Line and indicates radiation level

  • Page No. 43 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R2RM204C PLANT SPEC POINT DESC: AS LINE RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 6.31E-5 MAXIMUM INSTR RANGE: 1.0E+4 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURBINE-DRIVEN AUX FEED PUMP EXHAUST ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level in the turbine-driven auxiliary feed pump exhaust ("Terry" turbine) .

  • Page No.

DATE:

44 REACTOR UN IT :

03/21/91 NA2

, STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: COND A/E RAD POINT ID: R2RM205C PLANT SPEC POINT DESC: CNDSR AIR EJECT RAD MON GENERIC/COND DESC: COND AIR EJECTOR RADIOACTIVITY ANALOG/0 I GIT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTPUT OF CONDENSOR AIR EJECTORS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level in the gaseous effluent from the condensor air ejectors. On high radiation any radioactive air is diverted into the Reactor Containment .

i I

  • Page No. 45 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R2RM206C PLANT SPEC POINT DESC: CNTMT AREA GAS RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM

-ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation Level of air taken from the reactor containment .

  • Page No.

DATE:

46 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM207C PLANT SPEC POINT DESC: CNTMT HR RAD MON COLUMN 4 GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.3162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: ON THE INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level within the reactor containment .

  • Page No.

DATE:

47 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM208C PLANT SPEC POINT DESC: CNTMT HR RAD MON COL 12 GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.3162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: ON THE INSIDE CRANE WALL ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level within the reactor containment .

Page No. 48 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R2RM209C PLANT SPEC POINT DESC: CNTMT PERS HATCH RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-5 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE*CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level in the Personnel Hatch area *

  • Page No.

DATE:

49 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: CNTMNT RAD POINT ID: R2RM210C PLANT SPEC POINT DESC: CNTMT PARTICULATE RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OUTSIDE CONTAINMENT PERSONNEL HATCH ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of particles in the air taken out of the reactor containment .

  • Page No.

DATE:

50 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF LIQ RAD POINT ID: R2RM211C PLANT SPEC POINT DESC: DISCHARGE TUNNEL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: DSCHRG TUNL PAST LAST PT OF RAD ADDITION ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors effluent (service water, condensate cooling water, and liquid waste) in the discharge tunnel beyond the last point of radiation addition to ensure that the radiation activity levels of the plant discharge do not exceed limits .

  • Page No.

DATE:

51 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: RCS LTDN RAD POINT ID: R2RM214C PLANT SPEC POINT DESC: RCS LETDOWN HIGH RAD MON GENERIC/COND DESC: RAD LEVEL OF RCS LETDOWN LINE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: RCS LETDOWN LINE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation level in the reactor coolant by means of a sample from the letdown line .

  • Page No.

DATE:

52 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: CNTMNT RAD POINT ID: R2RM215C PLANT SPEC POINT DESC: CNTMT AREA RAD MON GENERIC/COND DESC: RADIATION LEVEL IN CONTAINMENT ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-5 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: REACTOR CONTAINMENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT _FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Detects garrma radiation in the reactor containment.

  • Page No.

DATE:

53 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF LIQ RAD POINT ID: R2RM216C PLANT SPEC POINT DESC: SW FR RCS CLR 2A RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 2-SW-P-5 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 2-RS-E-1A which will then be monitored for radiation and returned to the service water line .

  • Page No.

DATE:

54 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R2RM217C PLANT SPEC POINT DESC: SW FR RCS CLR 2B RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 2-SW-P-6 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 2-RS-E-1B which will then be monitored for radiation and returned to the service water line .

  • Page No.

DATE:

55 REACTOR UN IT:

03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF LIQ RAD POINT ID: R2RM218C PLANT SPEC POINT DESC: SW FR RCS CLR 2C RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMI'c INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 2-SW-P-7 will withdraw a continuous sample from the service water outlet line of recirculation spray heat exchanger 2-RS-E-1C which will then be monitored for radiation and returned to the service water line .

  • Page No.

DATE:

56 REACTOR UN IT :

03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R2RM219C PLANT SPEC POINT DESC: SW FR RCS CLR 2D RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SRVC WTR SPLY FRM RECIRC SPRY HEAT XCHNG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: In the event of an accident 2-SW-P-8 will withdraw a continuous sample from the service water outlet Line of recirculation spray heat exchanger 2-RS-E-1D which will then be monitored for radiation and returned to the service water Line.

( ..

  • Page No.

DATE:

57 D3/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: SG BD RAD 1A POINT ID: R2RM220C PLANT SPEC POINT DESC: SG A BL~N RAD MON GENERIC/COND DESC: STM GEN A BL~OWN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE.

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation levels in the liquid phase of steam generator 2*RC-E-1A blowdown. The sample is returned to the steam generator blowdown tank after being monitored .

  • Page No.

DATE:

58 REACTOR UN IT :

03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA2 DATA FEEDER: N/A NRC EROS PARAMETER: SG BD RAD 28 POINT ID: R2RM221C PLANT SPEC POINT DESC: SG B BLWDN RAD MON GENERIC/COND DESC: STM GEN B BLOWDO\JN RAD LEVEL ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors radiation Levels in the Liquid phase of steam generator 2-RC-E-18 blowdown. The sample is returned to the steam generator blowdown tank after being monitored .

Page No. 59 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: SG BD RAD 3C POINT ID: R2RM222C PLANT SPEC POINT DESC: SG C BLWDN RAD MON GENERIC/COND DESC: STM GEN C BLOWDOWN RAD LEVEL ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors radiation levels in the liquid phase of steam generator 2-RC-E-1C blowdown. The sample is returned to the steam generator blowdown tank after being monitored *

  • Page No. 60 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: LP SI FLOW POINT ID: F2SI001A PLANT SPEC POINT DESC: L HD !NJ HEADER FLOW A (NL)

GENERIC/COND DESC: LOW PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 499.3 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSJR RANGE: 4000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LPSI PUMP A DISCHARGE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication from LHSI pump A.

Page No. 61 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 05/17/91 REACTOR UN IT: NAZ DATA FEEDER: N/A NRC ERDS PARAMETER: LP SI FLOW POINT ID: F2SI002A PLANT SPEC POINT DESC: L HD !NJ HEADER FLOW B (NL)

GENERIC/COND DESC: LOW PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: 0 - 499.3 11 H20 MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 4000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: LPSI PUMP B DISCHARGE ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication from LHSI pump B*

  • Page No.

DATE:

62 05/17/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F2SI003A PLANT SPEC POINT DESC: TOTAL HOT LEG SI FLOW (WT)

GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 1000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: CHRGING PMP DISCH UPSTRM OF HOT LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHS!

pumps to the hot leg of each loop .

Page No. 63 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: HP SI FLOW POINT ID: F2SI001C PLANT SPEC POINT DESC: TOT COLD LEG HHS! FLOW GENERIC/COND DESC: HIGH PRESSURE SI FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 750.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 3 HOW PROCESSED: SUM* SEE SYSTEM DESCRIPTION SENSOR LOCATIONS: CHRGING PMP DISCH UPSTRM OF COLD LEG ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Provides flow indication on the SI headers from the HHS!

pumps to the cold leg of each loop. The 3 loop high head SI flows are totaled for this value. If any one of the loop SI values is invalid, this point will be marked invalid .

  • Page No.

DATE:

64 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM001A PLANT SPEC POINT DESC: WEATHER* SIGMA THETA (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 45.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: PRIMARY TOWER TRAILER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Uses lower wind direction to find the standard deviation of the wind direction angle which is referred to as horizontal atmospheric stability .

Page No. 65 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: M3MM002A PLANT SPEC POINT DESC: WEATHER* UPPER DELTA (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -9.0 MAXIMUM INSTR RANGE: 9.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 2 RTD'S AT 35 1 & 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE Nl DETECTOR POWER, SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Uses the difference of upper temperature and lower temperature to calculate vertical atmospheric stability .

Page No. 66 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: WIND DIR POINT ID: M3MM003A PLANT SPEC POINT DESC: LOWER WIND DIRECTION (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 540.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35' ON PRIMARY & BACKUP TOWERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MOOE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses the wind direction at 35 1 *

  • Page No.

DATE:

67 REACTOR UNIT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: WIND DIR POINT ID: M3MM004A PLANT SPEC POINT DESC: UPPER WIND DIRECTION (NL)

GENERIC/COND DESC: WIND DIR AT THE REACTOR SITE ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: DEG ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 540.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150 1 ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses the wind direction at 150°.

  • Page No.

DATE:

68 D3/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED POINT ID: M3MM007A PLANT SPEC POINT DESC: LOWER WIND SPEED (NL)

GENERIC/COND DESC: WIND SPEED AT THE REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 35' ON PRIMARY & BACKUP TOWERS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Measures the wind speed at 35 1

  • Page No. 69 STATION: North Anna 05/21/91 UNIT: 2 PYR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: YIND SPEED POINT ID: M3MM008A PLANT SPEC POINT DESC: UPPER YIND SPEED (NL)

GENERIC/COND DESC: YIND SPEED AT THE REACTOR SITE

.ANALOG/DIGITAL:* A ENGR UNITS/DIG STATES: MPH ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0.0 MAXIMUM INSTR RANGE: 100.0 ZERO- POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOY PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: 150 1 ON PRIMARY TOYER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POYER SUPPLY CUT-OFF POYER LEVEL: N/A

  • NI DETECTOR POYER SUPPLY TURN-ON POYER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Measures the wind speed at 150 1 *

  • Page No.

DATE:

70 03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE

. 05/21/91 REACTOR UNIT:

DATA FEEDER: N/A NRC EROS PARAMETER: STAB CLASS POINT ID: T3MM001A PLANT SPEC POINT DESC: ATMOS AMBIENT TEMPERATURE (NL)

GENERIC/COND DESC: AIR STABILITY AT REACTOR SITE ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: DEGF ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: -22.0 MAXIMUM INSTR RANGE: 122.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: s NUMBER OF SENSORS: N/A HOW PROCESSED: N/A - THIS IS A DIRECT SENSOR INPUT SENSOR LOCATIONS: RTD AT 35' ON PRIMARY TOWER ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Measures air temperature at 35' elevation on the primary tower .

  • Page No.

DATE:

71 REACTOR UNIT:

03/21/91 NAZ STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM211C PLANT SPEC POINT DESC: PV GAS RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: PROCESS VENT LINE DWNSTRM OF EVAPORATORS ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of a sample taken from the process vent after it has passed through the particulate filters .

Page No. 72 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM212C PLANT SPEC POINT DESC: PV PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the particules in a sample taken from the process vent .

Page No. 73 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM214C PLANT SPEC POINT DESC: SW DISCH TO RSVR RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIG IT AL : A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF-LINE IN A CMN HOR OF 2 36"DSCH LINES ALARM/TRIP SETPOINTS: VARIABLE NI*DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation Level of the service water discharge to the service water reservoir *

  • Page No.

DATE:

74 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM215C PLANT SPEC POINT DESC: SW DISCH TO CANAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF-LINE IN A CMN HOR OF 2 24 11 DSCH LINES ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the service water discharge to the discharge canal .

  • Page No.

DATE:

75 REACTOR UN IT:

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: EFF LIQ RAD POINT ID: R3RM216C PLANT SPEC POINT DESC: SW FROM CC HX RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED LIQ ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: OFF-LINE IN A CMN HDR OF 4 HEAT XCHNGERS ALARM/TRIP SETPOINTS: VARIABLE NI.DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continuously monitors the radiation level of the service water effluent from the component cooling heat exchangers .

  • Page No.

DATE:

76 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM217C PLANT SPEC POINT DESC: VS GASEOUS RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 84 11 DIAMETER VENTILATION STACK ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of a variable sample of the ventilation stack air taken through a multiprobe isokinetic sampling nozzle .

Page No. 77 STATION: North Anna 05/21/91 UNI.T: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM218C PLANT SPEC POINT DESC: VS PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+7 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 84 11 DIAMETER VENT! lATION STACK ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of the particles in a variable sample of the ventilation stack air taken through a multiprobe isokinetic sampling nozzle

  • Page No. 78 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM219C PLANT SPEC POINT DESC: VV GAS RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 H~ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 90 11 DIAMETER VENTILATION VENT ALARM/TRIP SETPOINTS: VARIABLE

.NI DETECTOR POWER SUPPLY CUT-OFF P~ER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation level of a variable sample of the ventilation vent air taken through a multiprobe isokinetic sampling nozzle .

Page No. 79 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM220C PLANT SPEC POINT DESC: VV PARTICULATE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: 90 11 DIAMETER VENT! LATION VENT ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Monitors the radiation level of particles in a variable sample of the ventilation vent air taken through a multiprobe isokinetic sampling nozzle .

Page No. 80 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91.

REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM221C PLANT SPEC POINT DESC: VV GAS SAMPLE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: -p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE. SYSTEM DESC: Monitors the radiation in an air sample taken from one of eight areas. The operator can select a sampling time at each of the eight areas between 30 min. and 24 hrs. The areas that can be selected are fuel bldg., safeguards area of unit 1 or unit 2, aux bldg. central area (2 separate sampling apparatus), containment purge, decontamination bldg., and a spare .

  • Page No.

DATE:

81 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM222C PLANT SPEC POINT DESC: VV PART SAMPLE RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: CPM ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: AUX BLDG ELEV 292 ALARM/TRIP SETPOINTS: VARIABLE Nr DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Monitors the radiation of particles in an air sample taken from one of eight areas. The operator can select a sampling time at each of the eight areas between 30 min. and 24 hrs.

The areas that can be selected are fuel bldg., safeguards area of unit 1 or unit 2, aux bldg. central area (2 separate sa~ling apparatus), containment purge, decontamination bldg., and a spare .

  • Page No.

DATE:

82 REACTOR UN IT:

03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM223C PLANT SPEC POINT DESC: PV HIGH RADN RATE MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+5

. MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 H~ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SERV BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Takes a sample from stacks A & Band measures the radiation level in the sample. This is the high range instrument for this data .

Page No. 83 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM224C PLANT SPEC POINT DESC: PV NORM RADN RATE MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.DE-2 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SWGR BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE Ni DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Continually senses radiation level in a sample stream from the process vent and provides a signal to RM-GW-108-1A's micro computer for determination of radiation release rate.

This is the normal range instr1.111ent for this data .

Page No. 84 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM225C PLANT SPEC POINT DESC: PV NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1. OE-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SWGR BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Continually senses radiation Level in a sample stream from the process vent. This is the normal range instrument for this data

  • Page No. 85 STATION: North Anna 05/21/91 UNIT: 2 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM226C PLANT SPEC POINT DESC: VS A HIGH RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E*4 MAXIMUM INSTR RANGE: 1.0E+S ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE Nl DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "A". This is the high range instrument for this data.

Page No. 86 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM227C PLANT SPEC POINT DESC: VS A HIGH RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+5 MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-2A's microcomputer for determination of radiation release rate. This is the high range instrument for this data.

  • Page No.

DATE:

87 REACTOR UN IT :

03/21/91 NA2 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: R3RM228C PLANT SPEC POINT DESC: VS A NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "A". This is the normal range instrument for this data.

  • Page No.

DATE:

88 03/21/91 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE 05/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM229C PLANT SPEC POINT DESC: VS A NORM RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-2 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-1A's microcomputer for determination of radiation release rate. This is the-normal range instrument for this data .

  • Page No. 89 STATION: North Anna 05/21/91 UNIT: 2 PIJR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM230C PLANT SPEC POINT DESC: VS B HIGH RADN RATE MQN GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-4 MAXIMUM INSTR RANGE: 1.0E+5 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOIJ PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POIJER SUPPLY CUT-OFF POIJER LEVEL: N/A NI DETECTOR POIJER SUPPLY TURN-ON POIJER LEVEL: N/A INSTRUMENT FA~LURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "B" and provides a signal to RG-VG-180-2A's microcomputer for determination of radiation release rate. This is the high range instrument for this data

  • Page No. 90 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM231C PLANT SPEC POINT DESC: VS B HIGH RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.259E+5 MAXIMUM INSTR RANGE: 1.0E+13 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE Ni.DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation Level in a sample taken from vent stack "B". This is the high range instrUT1ent for this data.

Page No. 91 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UNIT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM232C PLANT SPEC POINT DESC: VS B NORMAL RAD MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E-7 MAXIMUM INSTR RANGE: 10.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A

  • NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

INSTRUMENT FAILURE MODE:

TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG:

N/A N/A N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack 11 8 11

  • This is the normal range instrument for this data .

Page No. 92 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT : NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM233C PLANT SPEC POINT DESC: VS B NORM RADN RATE MON GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIG IT AL: A ENGR UNITS/DIG STATES: UCI/S ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 1.0E*2 MAXIMUM INSTR RANGE: 1.0E+6 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: TURB BLDG ELEV 303 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT*OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN*ON POWER LEVEL: N/A INSTRUMENT FAILURE MOOE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation level in a sample taken from vent stack "B" and provides a signal to RG*VG180*1A's microcomputer for determination of radiation release rate. This is the normal range instri..ment for this data

  • Page No. 93 STATION: North Anna 05/21/91 UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE: 03/21/91 REACTOR UN IT: NA2 DATA FEEDER: N/A NRC EROS PARAMETER: EFF GAS RAD POINT ID: R3RM234C PLANT SPEC POINT DESC: PV HIGH RADIATION MONITOR GENERIC/COND DESC: RADIOACTIVITY OF RELEASED GASES ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: UCI/CC ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 3.162E-4 MAXIMUM INSTR RANGE: 1.0E+5 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: EXPONENTIATED VALUE OF LOGARITHMIC INPUT SENSOR LOCATIONS: SERV BLDG ELEV 307 ALARM/TRIP SETPOINTS: VARIABLE NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL: N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL: N/A INSTRUMENT FAILURE MODE: N/A TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE LEG: N/A UNIQUE SYSTEM DESC: Senses radiation Level in a sample stream from the process vent. This is the high range instrunent for this data.

e

ATTACHMENT 5 NORTH ANNA UNITS 1 & 2 DATA POINT LIBRARY LISTINGS REVISION HISTORY 5/20/91 POINT ID DESCRIPTION OF CHANGE

1. F1SI003A Changed the point description to indicate that the reading is a totalized flow.
2. F2SI003A Changed the point description to indicate that the reading is a totalized flow.
3. MlNM005C Changed the unique system description to remove the discussion of exponentiating the input signal. This is a linear input.
4. M2NM005C Changed the unique system description to remove the discussion of exponentiating the input signal. This is a linear input.
5. FlRC004C Changed the location field to remove the loop specific reference to the transmitter location since this is an averaged point .
  • 6.

7.

F2RC004C FlSIOOlA Changed the location field to remove the loop specific reference to the transmitter location since this is an averaged point.

Added this point.

omitted.

Low head SI signals were previously

8. FlSI002A Added this point. Low head SI signals were previously omitted.
9. F2SI001A Added this point. Low head SI signals were previously omitted.
10. F2SI002A Added this point. Low head SI signals were previously omitted.
11. LlFWOOlC Corrected reference note field to correctly identify the 0% level reference.
12. L1FW002C Corrected reference note field to correctly identify the 0% level reference.
13. L1FW003C Corrected reference note field to correctly identify the 0% level reference.

ATTACHMENT 5 (Continued)

NORTH ANNA UNITS 1 & 2 DATA POINT LIBRARY LISTINGS REVISION HISTORY 5/20/91

14. L2FW001C Corrected reference note field to correctly identify the 0% level reference.
15. L2FW002C Corrected reference note field to correctly identify the 0% level reference.
16. L2FW003C Corrected reference note field to correctly identify the 0% level reference.
17. MlNMOOlC Corrected typographical errors in the engineering units conversion field, the NI cut on field and the NI cut off field.
18. M2NM001C Corrected typographical errors in the engineering units conversion field, the NI cut on field and the NI cut off field.
19. M1NM003C Corrected typographical error in the engineering units conversion field .
  • 20. M2NM003C Corrected typographical error in the engineering units conversion field.