Requests Extension Until 850331 to Complete Environ Qualification of GE Charging Pump Component Cooling Water Pump Motors.Justification for Continued Operation Encl
ML18142A123
Person / Time
Site: Surry  
Issue date: 11/15/1984
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Harold Denton, Varga S
Office of Nuclear Reactor Regulation
References
549, NUDOCS 8411260380
Download: ML18142A123 (2)


Text

l.:

~

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 W. L. STEWART VICE PRESIDENT NUCLEAR OPERATIONS November 15, 1984 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation Attention:

Mr. Steven A. Varga, Chief Serial No. 549 E&C/MGD/jdm:2006N Docket Nos. 50-280 Operating Reactors Branch No. 1 Division of Licensing 50-281 License Nos. DPR-32 DPR-37 U.S. Nuclear Regulatory Commission Washington, DC 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION - UNITS 1 AND 2 ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT In accordance with 10CFR50.49 paragraph (h) of the Equipment Qualification Rule, we are requesting an extension to March 31, 1985 for completing the environmental qualification of the Surry Unit 1 charging pump component cooling water pump motors.

The existing motors are being replaced with new, environmentally qualified motors.

Due to design differences between the new and existing motors, new pumps that are physically compatible with the new motors must also be procured.

Purchase orders for the new pumps and motors have been issued with delivery presently scheduled for mid-February, 1985.

We plan to install this equipment in Unit 1 during the first quarter of 1985.

The Unit 2 equipment will be installed during the Refueling Outage presently scheduled to begin in mid-March, 1985.

A Justification for Continued Operation is attached.

Thank you for your consideration in this matter.

Attachment cc: Mr. James P. O'Reilly Regional Administrator Region II USNRC


"'\\,

~~--~--80 841115 I,

841126DOO~K 05000280

\\

PDR A PDR I

p

\\~

1 ry truly yours,

~,~

W. L. Stewart'\\

Mr. Don J. Burke NRC Resident Inspector Surry Power Station

.j

l.

e JUSTIFICATION FOR CONTINUED OPERATION 1-CC-P-2A/28, 2-CC-P-2A/28 SURRY POWER STATION UNITS 1 AND 2 Attachment to Letter Seri a 1 No. 549 General Electric Charging Pump Component Cooling Water Pump Motors The charging pump component cooling water pumps provide seal cooling water for the charging pumps.

The flow from the component cooling water pumps cools the charging pumps while they are in their safety mode of safety injection.

In the event of a cooling water pump failure, the manufacturer has determined that the charging pumps can operate indefinitely in normal ambient conditions without seal water coolant as long as the pumped fluid is less than 115°F.

For the purpose of environmental qualification, the accident of concern is the HELB.

Vepco has evaluated the areas of the charging pumps and charging pump

  • CCW pumps, and has determined that there is no single HELB that can simultaneously render both the charging pump and CCW pump environments harsh.

In the safety injection mode the suction of the charging pumps is diverted from the normal source, at the volume control tank, to the refueling water storage tank by the safety injection signal.

The water in the refueling water storage tank is cooled by Tech Spec requirement to a temperature of slightly below 45°F.

Since the pumped fluid is less than 115°F, we have concluded that the charging pumps can operate in the event of any HELB that might cause failure of the CCW pump motors.

It is concluded that the failure of the component cooling water pumps would not significantly degrade the safety function or provide misleading information to the operator under the accident environment resulting from a design basis event.