' I Vepco VIRGINIA ELECTRIC AND POWER COMPANY Surry Power Station

. /'I I:: I 27

. J '-: ~; L AlO : ~ D P. o. Box 315 Surry, Virginia 23883 July 24, 1979 Docket No:

50-280 Mr. James P. O'Reilly, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100

. I

  • /

Atlanta, Georgia 30303

\\ ' ' '.

~ ~ ~ - ~--.J-~_i...:~-~~----;__.:_.,* j~.:~~

~':"".:'"-" __......,._ '-"~.......

Subject:

IoE. Bulletin No. 79-13

Dear Sir:

In accordance with the provisions of IE Bulletin 79-13, VEPCO supplements our earlier reports for Surry Power Station with the following:

As of this date, the following welds have rejectable indications:

"A" S.G.

Wf/3 Wi/4 Wf/5 W1113 "B" S.G.

Will Wl/10 "C" S.G.

Wf/5 Wf/6 Wl/11 Wl/9.

14-WFPD-17-601 Small area of rejectable porosity, (reported to NRC 07-16-79).

Two small linear indications in the root area, (reported to NRC 07-16-79).

Small area, lack of fusion - reject (reported 07-23-79).

Small areas of rejectable incomplete fusion (reported to NRC 07-12-79).

14-WFPD-13-601 Small area of rejectable porosity, (reported to NRC 07-12-79).

Small area of slag/incomplete fusion - reject 14-WFPD-9-601 Small area of rej ectable porosity, (reported to NRC 07-16-79).

Small area of rejectable incomplete fusion, (reported to NRC 07-16-79)..

Small area of rejectable incomplete fusion, (reported to NRC 07-16-79).

Small area of rejectable incomplete fusion, (reported to NRC 7-23-79).

7qo433 UL !lCIAL coh.

cp

"C" S.G.

Wlll3 W/114 2 -

July 24, 1979 14-WFPD-9-601 (Continued)

Small area of slag - reject (reported 07-23-79).

Small areas of slag/incorrect fusion - reject (reported Oi-23-79).

This completes the R.T. of all feedwater lines in #1 Containment.

Repair work is in progress.

The total number of rejectable welds is 12.

OYournw~*

. -r-~-

w. L. Stewart Station Manager