ML18102A196

From kanterella
Jump to navigation Jump to search
Determines That License Change Request 96-05,proposing to Temporarily Modify TS 3/4.7.6 to Allow Core Alterations While CR Emergency AC Sys Inoperable for Extensive Mods, During Modes 5 & 6,has Minimal Impact to Operator Safety
ML18102A196
Person / Time
Site: Salem 
Issue date: 06/10/1996
From: Tosch K
NEW JERSEY, STATE OF
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9606250156
Download: ML18102A196 (2)


Text

..

.~

Christine Todd Whitman Governor Department of Environmental Protection Division of Environmental Safety, Health, Analytical Programs Robert C. Shinn, Jr.

Commissioner Radiation Protection Programs Bureau of Nuclear Engineering CN-415 Trenton, NJ 08625-0415 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 To Whom It May Concern:

June 10, 1996

Subject:

Salem Generating Station DdcketNo. 50-311 *

  • *Amendment to Facility Operating*:Lic~nse.,.*
'. Lic$nse Change*:Request 96'.-05 The subject request*was submitted to the NRC by PSE&G letter dated May 7,*,1996 ~

The request** proposes to* temporarily modify Technical Specification 3/4. 7. 6 to.:allow Core Alterations while the Control Room Emergency Air Conditioning System (CREAS) is inoperable for extensive modifications, during Modes 5 and 6.

The New Jersey Department of Environmental Protection's Bureau of Nuclear Engineering (BNE) has reviewed the request in accordance with the requirements of 10 CFR 50. 91 (b).

  • NRC NUREG-1431, Standard Technical Specifications Westinghouse Plants, was reviewed and compared to this License Change Request.

The State of New Jersey has determined that this change has minimal impact t'o plant operator safety, provided that the following recommendations are implemented.

1.

Maintaining the CAACS outside air intakes either isolated or capable of being manually isolated during the full duration of the modification to the CREAS.

2.

Restricting the commencement of the proposed modification until the Fuel Handling Building ventilation systemis fully restored.

3.

Restrictingdeliveries of :ammonium hydroxide until the Control Room Emergency Air Conditioning System modifications are completed.

9606250156 960610 PDR ADOCK 05000311 P

PDR New Jersey is an Equal Opportunity Employer Recycled Paper

  • .~

If you have any questions, please contact Dave Vann at (609) 984-7548.

c:

Distribution Jill Lipoti N.J. DEP D. Zannoni N.J. DEP D. Chawaga

.Sincerely, J/

~- '\\ -------1

. 4

~vu<:* 05 --

Kent w. Tosch, Manager Bureau of Nuclear Engineering NRC Region I State Liaison Officer

c. Marschall NRc*sr. Resident Inspector L. Olshan NRC Project Manager D. Powell PSE&G