FORM NC.DE-AP.ZZ-0002-1 CALCULATIONCOVERSHEET*

-. * -........ Cover Sheet

.. Page 1 of Ji CALC. NO.:

ES-4.004(0)

PSE & G REVISION:

.2,

.. : : FOR INFORMATION ONLY TITLE:

125 Volt DC Batterv and Batterv Charger S1Z1ng Calculat1on

~Jcfiv

.-.-3/'..J..*3**-**-***-**--*-

-* ***--*'~~!

  1. SHTS.(CALC):,.Hf/' l/njrtp ATTACHMENTS: #/TOTALSHTS.:. *z+t6- ~~o/b.. TOTAL.~~rs.:. 1//5/7~

CHECK ONE: D INTERIM (Proposed Plant Change)

D VOID 12{]

FINAL (Supports Installed Condition)

DESCRIPTION OF REVISION: Refer to Revision Summary on Page I of the calculation for the scope of the revision.

REASON FOR REVISION: This revision supersedes Revision I of this calculation in its entirety. In addition to sizing the battery chargers, this revision will also size the 125V DC batteries and determine the battery voltage profile, using the battery duty cycles established in calculation ES-4.003(Q), Revision 1.

HOPE CREEK Q - LIST (SALEM) ?

IMPORT ANT TO SAFETY?

DNo DNo IZI N/A FUTURE CONFIRMATION REQUIRED ?

iXJ YES l&J YES DYES IXJ NO If yes list page No(s). ----------

DOCUMENTS AFFECTED? (CBDs, FSAR, etc.): YES; CBD: DE-CB.125-0018(0). Rev. 3 STATION PROCEDURES IMP ACTED? ("NIA" FOR CALCS RELATED TO DCP) 7';:;z,::X

~

YES OR UNSURE

~NO l/lf/?' D N/A

- If "YES OR UNSURE", has System Engineer been contacted?

~YES

- If "YES" or "NO", has pertinent descriptive information been transmitted to System Engineer/Single Point Contact?

(transmittal required if System Engineer not contacted)

~YES

?w./f.~*~ #t!!!I~

ORIGIN>\\ TOR/COMPANY NAME:;lciJ.. f>&*/Li: J.Y.S..;!r.:_Sagent&Lundy J,.,d; JZ~--i:;

PEER REVIEWER/COMPANY NAME:

~~~f:

Sargent & Lundy l!/~~-

VERIFIER/COMPANY NAME:

.~/e /n sc.bn-.1// *- S q,r<"/ea t t-Lu.ndy APPROVE_>>_=~~-~-~~~=--~ -~~~

(,----- -9605280229 960119 i.. AN ""Ji~

.. PDR ADOCK 05000272

.f8 \\_; \\.~R~

I

. p PDR

~

Contractor Supervisor I

PSE&G Supervisor 1/13/96 Date 1/13/96 Date

. 1/1~/c;c, Date Date I/ff/I/

Date

/

calculation is either Q-List, Q, Qs, Qsh, F, R, or Important to Safety "YES", completion of the Certification for Design Verificatio~orm NC.DE-AP.ZZ-0010-1) is required.

Lft' Ce. (

Nuclear Common

( il.J> A dot. ; "-~ c YI a f,/ 0 ( s /, l{., -

I 4 t-:; r r '1ievision 4 0

/1 Je1se CctlVo - 01£-4 t

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 1 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4. 004 (Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 125 Volt DC Battery and Battery Charger Sizing Calculation ES-4.004(Q)

1.

REVISION

SUMMARY

AND METHOD OF REVIEW:

A. Revision Summary:

REVISION O:

Initial Issue. Signatures for Revision 0 can be found on Exhibit 1 of Revision 0 of the calculation.

REVISION 1: Incorporates changes associated with CP No. 2EC-3124/12.

Signatures for Revision 1 can be found on Exhibit 1 of Revision 1 of the calculation.

REVISION 2: This revision supersedes Revision 1 of this calculation in its entirety. It also supersedes the portion of Calculation ES-45.002(0), Rev. 0 that relates to the sizing of the 125 Vdc battery for a Station Blackout event. In addition to sizing the battery, this revision will also size the 125 Vdc battery chargers and determine the battery voltage profile, using the battery duty cycles established in calculation ES-4.003(Q), Revision 1.

B. Method of Review:

A detailed review of Revision 2 of this calculation was performed.

Reviewer J. Krvavac Date January 13, 1996

_j

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G CALC. NO. :

ES-4. 004 (Q)

CALCULATION CONTINUATION/

REVISION HISTORY SHEET

REFERENCE:

ORIGINATOR,DATE REV:

LAV/;

2 I I 6

REVIEWER/VERIFIER, DATE 1-17:J-tj(:,

P~:?C ) ;y,.,c, SHEET : 2 of 18 CONT'D ON SHEET:

125 Volt DC Battery and Battery Charger Sizing Calculation ES-4.004 SECTION 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 TABLE OF CONTENTS REVISION

SUMMARY

AND METHOD OF REVIEW PURPOSE DESIGN BASIS DESIGN INPUT ASSUMPTIONS REFERENCES CALCULATION 7.1 METHODOLOGY 7.2 RESULTS CONCLUSIONS ATTACHMENTS

1.

Units 1 and 2, IEEE-485 Battery Cell Sizing Worksheets 1 A Sizing Sheets for Battery 1 A 1 B Sizing Sheets for Battery 1 B 1 C Sizing Sheets for Battery 1 C 2A Sizing Sheets for Battery 2A 28 Sizing Sheets for Battery 28 2C Sizing Sheets for Battery 2C

2.

References

3.

/)ey/7ri Veri/!/cvr-f/of1 SHEET NO.

1 3

3 3

6 7

8 8

13 17 J-i 2.

~:Jlt/11) (?

1-,,Ol./

J *- 7

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G CALC. NO.:

CALCULATION CONTINUATION/

REVISION HISTORY SHEET ES-4.004(Q)

REFERENCE:

SHEET :

2a of 18 CONT'D ON SHEET:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE Warning:

This document has been either partially or entirely prepared using electronic media, stored on diskettes controlled by Engineering Document Control. Any changes or revisions to this document will require diskette retrieval and changes to or by the following:

Media I. D.:

Media Revision Level:

Media

Title:

Media Quantity:

Software Title/Revision:

ES-4.004(0) 0 125 Volt DC Battery and Battery Charger Sizing Calculation

f'

.1j diskettes Microsoft Word, Version 6.0c

-Mierssoft EXCEL, Version 5:6 ~

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G ES-4.004(Q)

ORIGINATOR, DATE REV:

REVIEWER/VERIFIER, DATE 2.0 PURPOSE CALCULATION CONTINUATION/

REVISION HISTORY SHEET

REFERENCE:

2 SHEET : 3 of 18 CONT'D ON SHEET:

This calculation determines the minimum battery size required for the 125 Vdc system based on the Loss Of Offsite Power (LOOP) I Loss Of Coolant Accident (LOCA) and Station Blackout (SBO) duty cycles determined in calculation ES-4.003(Q), and the

. minimum battery charger requirements based on those duty cycles.

This calculation also determines the battery voltage profile for use in the system voltage drop calculation (ES-4.003(Q)). This calculation addresses the 125 Vdc battery systems at the Salem Generating Station, Unit 1 (1A, 1 Band 1 C) and Unit 2 (2A, 28 and 2C).

.. 3.0 DESIGN BASIS The batteries will be sized using the guidelines provided in IEEE Std. 485-1983. The duty cycle that will be used for sizing the battery is established in Calculation ES-4.003(Q), (Ref. 6.3). IEEE Std. 485-1983 recommends that batteries be replaced at 80% of their capacity (Ref. 6.1 ). The battery, therefore, must be sized to have adequate capacity when it reaches 80% of its original capacity. This is an aging factor of 1.25 (i.e., 1/0.80 = 1.25). A temperature correction factor of 1.08 (Ref. 6.1) corresponding to a minimum battery room temperature of 65°F (Assumption 5.4) will be used as per the recommendations of IEEE 485-1983. The Design Margin for all batteries is per Assumption 5.1.

~~ * !-.;rhe battery chargers will be sized using the guidelines provided in IEEE Std. 946- //

~

~S 7~

1992. The chargers will have the ability to recharge the battery following a design

\\l ~s duty cycle discharge and carry the normal operating load. The recharge time used after a discharge is 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> (Assumption 5.3). There are two battery chargers per battery, however, only one is normally connected at a time (Ref. 6.6).

t)f 4.0 DESIGN INPUT 4.1 Per Reference 6.5, the Battery Rooms take their air supply from the Control Area Relay Rooms, which have a design minimum temperature of 76° F.

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 4 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO. :

ES-4. 004 (Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 4.2 Not Used.

4.3 The C&D, LCR-33 and LC-33 batteries have sixteen positive plates per cell and have 60 cells (Ref. 6.4 and Ref. 6.6).

4.4 The minimum battery electrolyte temperature of 65°F corresponds to a correction factor of 1.08 (Ref. 6.1 ).

4.5 IEEE Std. 485-1983 recommends that batteries be replaced at 80% of their rated capacity (Ref. 6.1 ). The battery, therefore, must be sized to have adequate capacity when it reaches 80% of its original rated capacity. This is an aging factor of 1.25 (i.e., 1/0.80 = 1.25). The Design Margin for all batteries is per Assumption 5. 1.

4.6 Batteries 1A, 1 B, 1 C, 2A and 28 are type LCR-33 manufactured by C&D Charter Power Systems. The characteristics of the cells are based on the C&D fan curve - Drawing D-841, Revision No. 1, dated April 2, 1987 (Ref.

6.4). Battery 2C is an LC-33, also manufactured by C&D. The characteristics of the LC-33 cells are similar to those of the LCR-33 cells (based on Ref. 6. 7) and, therefore, the fan curve for the LCR-33 cells (Drawing D-841) can be used.

4. 7 The duty cycle for the batteries is obtained from calculation ES-4.003(0),

(Ref. 6.3). These values are summarized below:

4.7.1 Unit 1 Normal Operating Load; (i.e., the unit at full power) 121.66 114.84 75.46

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET SHEET : 5 of 18 CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE

\\-1;-tl~

-;;~

I / t-,

  • CJ~

Battery LOOP/LOCA Load Time in Minutes 0-1 1-30 30-60 60-120 Battery 1A 604.23 292.45 293.SO 293.SO Battery 1 B 606.63 26S.24 266.69 266.69 Battery 1 C S33.4S 3SS.82 3SS.7S 3SS.7S Battery SBO Load Time in Minutes 0-1 1-30 30-239 239-240 Battery 1A S79.77 294.07 208.44 249.62 Battery 1 B S84.90 273.82 273.77 31S.89 Battery 1 C S36.80 3S7.92 320.19 362.38 In addition to the above load the following additional load will be added to the batteries to account for future load growth during LOOP/LOCA and SBO scenarios only.

LOOP/LOCA SBO Battery 1A SA SA Battery 1 B 40A 20A Battery 1C 40A 1SA 4.7.2 Unit 2 Normal Operating Load; (i.e., the unit at full power) 87.81 117.06 79.57

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 6 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE Time in Minutes 0-1 1-30 30-60 60-120 Battery 2A 546.96 264.83 265.87 265.87 Battery 2B 586.43 264.75 266.19 266.19 Battery 2C 504.52 326.24 326.13 326.18 Battery SBC Load Time in Minutes 0-1 1-30 30-239 239-240 Battery 2A 510.83 254.47 168.84 211.07 Battery 2B 564.99 273.62 273.57 31S.70 Battery 2C 506.91 327.38 289.07 331.26 In addition to the above load the following additional load will be added to the batteries to account for future load growth during LOOP/LOCA and SBO scenarios only.

LOOP/LOCA SBO Battery 2A SA SA Battery 2B 40A 20A Battery 2C 40A 15A 4.8 The 125 VDC battery chargers are rated to supply a continuous output current of 250 A (Ref. 6.6).

5.0 ASSUMPTIONS The design margin will be assumed to be S% for Batteries 1 A, 2A, 1 B, 2B and 2C, however, no design margin was assum~ fQf ~.9~!ery 1 C. These design margins are acceptable because the battery~willbeWaluated for capacity before any new load is added. Thus, a battery can not be overloaded inadvertently due to new load additions.

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 7 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

ES-4. 004 (Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 5.2 For the purpose of the charger sizing calculation, the normal system load is assumed to be the load under normal plant operation. During the recharge of the battery after a discharge, the DC system normal load is assumed to be constant.

5.3 The optimum battery recharge time is a compromise between protecting against a too rapid recharge and minimizing DC System down time. For the purpose of this calculation, a recharge time of 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> will be selected arbitrarily.

5.4 The minimum battery electrolyte temperature is assumed to be 65°F. This is conservative since the Battery Rooms draw supply air from the Control Area Relay Rooms, which maintain a temperature of 76°F (Ref. 6.5). Analysis contained in Change Nos. 1 EC-3189, Package No. 1 and 2EC-3163, Package No. 1 (References 6.8 and 6.9) discuss changes made to ensure that the minimum Battery Room temperature remains above 65°F during the postulated events (including SBO).

6.0 REFERENCES

6.1 6.2 6.3 6.4 6.5 6.6 IEEE Std. 485-1983, "IEEE Recommended Practice for Sizing Large Lead Storage Batteries for Generating Stations and Substations".

IEEE 946-1992, "IEEE Recommended Practice for the Design of DC Auxiliary Power Systems for Generating Stations" Salem Calculation ES-4.003(Q), "125 Volt DC Short Circuit and System Voltage Drop Calculation", Rev. 1.

The discharge characteristics of the cells are based on the C&D fan curve -

drawing D-841, Revision No. 1, dated April 2, 1987, (copy attached).

.u~,.,~-~~

l.l

12.

x Salem Updated Final Safety Analysis Report (UFSAR), Section 9.4.1, Rev~ 0 ~o/~

and Figure 9.4-1A, Rev.~- JI/

n~

..({t,.,~_,} I/IT /P1'1 125 Vdc Control Power System Configuration Baseline Documentation, DE-CB.125-0018(0), Rev. 3.

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 8 of 18 0 PS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 7.0 7.1

6. 7 Memorandum of the July 31, 1995 telephone conversation between Mr.

Graham Walker of C&D Charter Power Systems and Mr. J. Krvavac of S&L, (copy attached).

6.8 Change No. 1 EC-3189, Package No. 1, Rev. O 6.9 Change No. 2EC-3163, Package No. 1, Rev. O CALCULATION METHODOLOGY 7.1.1 Voltage Profile Calculation The voltage profile at battery end of life is determined by using the manufacturer's fan curve (Ref. 6.4). The cell voltage is determined by the intersection of the cumulative total ampere-hours per positive plate "removed" from the cell during each discharge period and the discharge rate in amperes per positive plate for the specific period. The voltage corresponding to the intersection of the two points is the expected cell voltage. Interpolation between the adjacent "final volts" lines may be required. The cell voltage (V/cell) is then multiplied by the number of cells (i.e., 60) connected in series to obtain the battery terminal voltage. See Section 7.2.1.

7.1.2 Battery Sizing Salem Station has three safety-related 125 Vdc batteries per unit. They will be sized using the guidelines provided in IEEE 485-1983, using the battery duty cycles developed in Calculation ES-4.003(0).

The load currents and duration for each period of the duty cycle taken from Calculation ES-4.003(0) have been rounded up where necessary. The aging and temperature correction factors are per the design input (Section 4.0). The batteries are sized two times, once for LOOP/LOCA, and once for the SBO condition. See Attachment 1 for the battery sizing sheets. It is not necessary to consider the "normal load" scenario because, under that scenario, the battery is being maintained at the float voltage and is fully charged. The charger is only

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 9 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE I\\

needed to supply the normal operating load current and the current to maintain 1

the batteries in their fully cha~d condition.

r 'Y 7iG ~

'-"':,,..t; ~

o..Jk a-

~~

f!" p:,, ~

~

~A- ~

7.

Example

~~..;.7

-;f,.,

.,4--"fl°-ta

~->-~ A.e~ a-A.

. ~

-et-

~~ cJyr-

~)"-

c;l:,.r~

~"'""

Using the data for Battery 1A during the LOOP/LOCA loading scenario.

Column 2:

The load amperes are obtained from Section 4.7.

Column 3:

The change in load amperes between the periods. For the first period this value will be identical to the duty cycle load during the first minute.

Column 4:

Duration of the period, in minutes. The duration of the first period is 1 minute.

Column 5:

Time to end of section, in minutes. This value will be 1 for the first minute Column 6:

The "T Min. Rate" (Rr ) capacity can be obtained from the C&D discharge curves (Ref. 6.4). This is obtained from the intersection of the minute rating curves with the cell voltage curve of the battery at its minimum required voltage 108V (i.e., 1.80V/cell). For the one minute rate this value is the intersection between the 1' line and the minimum cell voltage curve of 1.80. This value is 109 amps/positive plate. This value must be multiplied by the "cell sizing correction factors" table in the upper right hand corner of the graph. For the one minute rate, for the LCR-33 battery, the correction factor is 1.00. Therefore, the actual Rr value is 109 Amps/pas. plate.

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 10 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

ES-4. 004 (Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE Column 'l:

Required section size. Divide Column 3 by Column 6. This is the amount of positive plates the battery must have to support the duty cycle during the particular period.

Continuing this procedure for all of the duty cycle sections as outlined in IEEE 485-1983. The Column 7 value for the section with the highest required number of positive plates is then multiplied by the temperature correction factor, the design margin and the aging factor. The solution is the minimum required positive plates that the battery requires to support the duty cycle. If this value is less than the number of positive plates available, the battery can support the duty cycle.

7.1.3 Battery Charger Sizing The formula for determining the battery charger rating is from IEEE 946-1992 as follows:

I L

1.1 AH T

R.6 \\.'.3'2---

b\\Y')-.~~ 1.o I

~ v°'fa,v".v6 ~

~

! s,y_.\\-

fl'"</

"i I.IV"'~

p\\-~ if~ J(f.._~ u.,.,./

=Minimum required charger rating in amperes

.-t-r~ ~'1/'IY V if'

= Continuous DC load in amperes 1.;r

\\.

rY u,..

l

= Constant that compensates for battery losses P

rrfP':;. V ~

\\vr ~

= Ampere-hours discharged from the battery or the eight hour ampere- ~ -9 y hour rating of the battery.

pr-I

= L + 1.l(AH)/T

= Time in hours to recharge the battery to approximately 95% of capacity The 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> rating of the C&D LCR-33 battery to 1. 75 volts per cell is 2320 A-hr (Ref.

6.6). However, based on the LOOP/LOCA duty cycle (which lasts 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />) or the SBO duty cycle (which lasts 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />), the battery will not be completely discharged. Per IEEE 946-1992, either the 8 hr ampere-hour rating of the battery or the actual ampere-hrs discharged from the battery may be used. The ampere hours discharged from the battery during the duty cycle can be calculated using the duty cycle of the battery (Section 4. 7) as follows:

,. !~

~<<:pru-0

,,.... "A

~ /£ n..:!"

......e~

.D~o 1-.,,~~

....,,,,_.-, ~~'),,.-....,._ ~

,t?'l--J-.-.

( fo s v) -

r,.r),M J..<._.

.?'-'-'

cf

-fto 0

FORM NC~DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 11 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 7.1.3.1 Unit1 LOOP/LOCA Battery 1A = 609.23A*1min(1hr/60min)+ 297.45A*29min(1hr/60min)+

298.50A*30min(1hr/60min)+298.50A*60min(1 hr/60min) = 601.67 A-hrs v

v------

Battery 1B = 646.63A*1min(1hr/60min)+ 305.24A*29min(1hr/60min)+

306.69A*30min(1 hr/60min)+ 306.69A*60min(1 hr/60min) = 618.34 A-hrs v<

V" Battery 1 C = 573.45A *1 min(1 hr/60min)+ 395.82A *29min(1 hr/60min)+

395.75A*30min(1 hr/60min)+ 395.75A*60min(1 hr/60min) = 794.50 A-hrs SBO Battery 1A = 584.77A*1min(1hr/60min)+ 299.07A*29min(1 hr/60min)+

213.44A*209min(1hr/60min)+ 254.62A*1min(1hr/60min) = 902.02 A-hrs Battery 1 B = 604.90A*1 min(1hr/60min)+293.82A*29min(1 hr/60min)+

293.77A*209min(1hr/60min)+ 335.89A*1min(1hr/60min) = 1180.99 A-hrs Battery 1 C = 551.80A*1 min(1hr/60min)+372.92A*29min(1 hr/60min)+

  • 335.19A*209min(1hr/60min)+ 377.38A*1min(1hr/60min) = 1363.31 A-hrs Therefore, the maximum ampere-hours that could reasonably be discharged during a LOOP/LOCA scenario is 601.67 A-hrs for the 1A Battery, 618.34A-hrs for the 1 B Battery, and 794.50-hrs for Battery 1 C, and during a SBO scenario is 902.02 A-hrs for Battery 1A, 1180.99A-hrs for Battery 1 Band 1363.31A-hrs for Battery 1 C. These values will be used for the ampere-hours that need to be replaced by the battery chargers. The recharging time of the battery is chosen to be 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> (Assumption 5.3). Using the IEEE Std. 946-1992 equation, the required charger ratings are as follows: (Note: the "continuous load" used for sizing the charger is considered the continuous load during normal plant operation)

LOOP/LOCA Battery 1A= 121.66A(continuous load Battery 1A)+ 1.1*(601.67A-hrs/30hrs)= 143.72A Battery 1 B = 114.84A(continuous load Battery 1B)+1.1 *(618.34A-hrs/30hrs)= 137.51A

\\

}

p FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET SHEET : 12 of 18 CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGI:~ATOR,DATE REV:

2 REVI:EWER/VERI:FI:ER,DATE Battery 1 C = 75.46A(continuous load Battery 1 C)+ 1.1 *(794.50A-hrs/30hrs)= 104.59A Battery 1 A = 121.66A( continuous load Battery 1 A)+1.1 *(902.02A-hrs/30hrs )=154. 73A Battery 1B = 114.84A(continuous load Battery 1B)+ 1.1*(1180.99A-hrs/30hrs)=158.14A Battery 1 C = 75.46A(continuous load Battery 1 C)+ 1.1 *(1363.31A-hrs/30hrs)=125.45A 7.1.3.2 Unit 2 LOOP/LOCA Battery 2A = 551.96A*1 min(1 hr/60min)+269.83A*29min(1 hr/60min)+

270.87 A*30min(1 hr/60min)+270.87 A*60min(1 hr/60min) = 545.92A-hrs Battery 2B = 626.43A *1 min(1hr/60min)+304.75A *29min(1 hr/60min)+

306.19A *30min( 1 hr/60min)+306.19A *60min( 1 hr/60min) = 617. 02A-hrs Battery 2C = 544.52A*1 min(1 hr/60min)+366.24A*29min(1 hr/60min)+

366.13A *30min(1 hr/60min)+366.18A*60min(1 hr/60min) = 735.34A-hrs SBO Battery 2A = 515.83A*1min(1hr/60min)+259.47A*29min(1hr/60min)+

173.84A *209min(1hr/60min)+216.07 A *1 min(1 hr/60min) = 7 43.15A-hrs Battery 2B = 584.99A*1min(1hr/60min)+293.62A*29min(1hr/60min)+

293.57 A *209min(1hr/60min)+335.70A *1 min(1 hr/60min) = 1179.86A-hrs Battery 2C = 521.91A*1 min(1 hr/60min)+342.38A*29min(1 hr/60min)+

304.07A*209min(1hr/60min)+346.26A*1min(1hr/60min) = 1239.13A-hrs Therefore, the maximum ampere-hours that could reasonably be discharged during a LOOP/LOCA scenario is 545.92A-hrs for the 2A Battery, 617.02A-hrs for the 2B Battery, and 735.34A-hrs for Battery 2C, and during a SBO scenario is 7 43.1 SA-hrs for Battery 2A, 1179.86A-hrs for Battery 2B and 1239.13A-hrs for Battery 2C. These

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 13 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE values will be used for the ampere-hours that need to be replaced by the battery chargers. The recharging time of the battery is chosen to be 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> (Assumption 5.3). Using the IEEE Std. 946-1992 equation, the required charger ratings are as follows: (Note: the "continuous load" used for sizing the charger is considered the continuous load during normal plant operation)

LOOP/LOCA Battery 2A = 87.81A(continuous load Battery 2A)+ 1.1 *(545.92A-hrs /30hrs) = 107.83A Battery 2B = 117.06A(continuous load Battery 2B)+ 1.1 *(617.02A-hrs/30hrs) = 139.68A Battery 2C = 79.57 A( continuous load Battery 2C)+1.1 *(735.34A-hrs/30hrs) = 106.53A

, Battery 2A = 87. 81 A( continuous load Battery 2A)+1.1*(743.15A-hrs/30hrs )= 115. 06A Battery 2B ~~continuous load Battery 2B)+1.1*(11;9.86A-hts/30hrs)= 160.32A 178.3/Vt Battery 2C = 79.57A(continuous load Battery 2C)+1.1*(1239.13A-hrs/30hrs)= 125.00A 7.2 RESULTS 7.2.1 Battery Voltage Profile:

Based upon the procedure outlined in section 7.1.1 the battery terminal voltages are as follows:

7.2.1.1 Unit 1 B tt 1AS OV I a erf B

o tages Period Length Load

  • Adjust Adjusted Total total A-H Total A-Amps Equiv Camos\\

factor Amperes Time removed Hr/PP per PP Volts*60 1

1 584.n 1.4175 828.911 1

13.815 0.863 51.807 113.52 2

29 299.07 1.4175 423.932 30 218.716 13.670 26.496 116.04 3

209 213.44 1.4175 302.551 239 1272.602 79.538 18.909 114.24 4

1 254.62 1.4175 360.924 240 1278.618 79.914 22.558 113.58

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR,DATE REV:

2 REVIEWER/VERIFIER,DATE B tt a erl(

0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos\\

factor Amoe res Time removed Hr/PP 1

1 609.23 1.4175 863.583 1

14.393 0.9 2

29 297.45 1.4175 421.635 30 218.183 13.636 3

30 298.50 1.4175 423.124 60 429.745 26.859 4

60 298.50 1.4175 423.124 120 852.869 53.304 B tt a er If 18 SBOV It 0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos\\

factor Amoe rs Time removed Hr/PP 1

1 604.90 1.4175 857.446 1

14.291 0.893 2

29 293.82 1.4175 416.490 30 215.594 13.475 3

209 293.77 1.4175 416.419 239 1666.120 104.132 4

1 335.89 1.4175 476.124 240 1674.055 104.628

.. B tt a erf 1 B LOOP/LOCA V It 0 ages Period Length Load

  • Adjust Adjusted Total totalA-H Total A-(amos\\

factor Amoeres Time removed Hr/PP 1

1 646.63 1.4175 916.598 1

15.277 0.955 2

29 305.24 1.4175 432.678 30 224.404 14.025 3

30 306.69 1.4175 434.733 60 441.771 27.611 4

60 306.69 1.4175 434.733 120 876.504 54.782 B tt a er°'I( 1CSBOV It 0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amps)

Factor Ampere Time removed Hr/PP s

1 1

551.80 1.35 744.930 1

12.415 0.776 2

29 372.92 1.35 503.442 30 255.746 15.984 3

209 335.19 1.35 452.507 239 1831.976 114.499 4

1 377.38 1.35 509.463 240 1840.467 115.029 B tt a erir 1 C LOOP/LOCA V It 0 ages Period Length Load

  • Adjust Adjusted Total totalA-H Total A-Camm::\\

Factor Amoe res Time removed Hr/PP 1

1 573.45 1.35 774.158 1

12.903 0.806 2

29 395.82 1.35 534.357.

30 271.175 16.948 3

30 395.75 1.~

534.263 60 538.306 33.644 4

60 395.75 1.35 534.263 120 1072.569 67.036

  • Temp Correction X Design Margin X Aging Factor SHEET : 14 of 18 CONT'D ON SHEET:

Amps Equiv oerPP Volts*60 53.974 113.34 26.352 116.04 26.445 115.68 26.445 114.48 Amps Equiv oerPP Volts*60 53.590 113.34 26.031 116.10 26.026 111.24 29.758 110.40 Amps Equiv oerPP Volts*60 57.287 112.98 27.042 115.98 27.171 115.56 27.171 114.30 Amps Equiv per PP Volts*60 46.558 114.06 31.465 115.38 28.282 109.14 31.841 108.36 Amps Equiv oerPP Volts*60 48.385 113.88 33.397 115.14 33.391 114.48 33.391 112.74

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET O~S~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REV:IEWER/VER:IF:IER,DATE 7.2.1.2 Unit 2 B tt 2ASBOV I a er'{

o tages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos) factor Amoe res Time removed Hr/PP 1

1 515.83 1.4175 731.189 1

12.186 0.762 2

29 259.47 1.4175 367.799 30 189.956 11.872 3

209 173.84 1.4175 246.418 239 1048.313 65.520 4

1 216.07 1.4175 306.279 240 1053.417 65.839 B tt 2A LOOP/LOCA V It a er'{

0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos) factor Amoe res Time removed Hr/PP 1

1 551.96 1.4175 782.403 1

13.040 0.815 2

29 269.83 1.4175 382.484 30 197.907 12.369 3

30 270.87 1.4175 383.958 60 389.886 24.368 4

60 270.87 1.4175 383.958 120 n3.845 48.365 B tt 28 SBO V It a erl(

0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos) factor Amperes Time removed Hr/PP 1

1 584.99 1.4175 829.223 1

13.820 0.864 2

29 293.62 1.4175 416.206 30 214.987 13.437 3

209 293.57 1.4175 416.135 239 1664.526 104.033 4

1 335.70 1.4175 475.855 240 1672.457 104.529 B tt 28 LOOP/LOCA V It a er'{

0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos) factor Amoeres Time removed Hr/PP 1

1 626.43 1.4175 887.965 1

14.799 0.925 2

29 304.75 1.4175 431.983 30 223.591 13.974 3

30 306.19 1.4175 434.024 60 440.603 27.538 4

60 306.19 1.4175 434.024 120 874.628 54.664 B tt 2C SBO V It a erl(

0 ages Period Length Load

  • Adjust Adjusted Total total A-H Total A-(amos)

Factor Amperes Time removed Hr/PP 1

1 521.91 1.4175 739.807 1

12.330 o.n1 2

29 342.38 1.4175 485.324 30 246.903 15.431 3

209 304.07 1.4175 431.019 239 1748.286 109.268 4

1 346.26 1.4175 490.824 240 1756.466 109.n9 SHEET : 15 of 18 CONT'D ON SHEET:

Amps Equiv per PP Volts*60 45.699 114.12 22.987 116.46 15.401 115.68 19.142 114.96 Amps Equiv per PP Volts*60 48.900 113.82 23.905 116.34 23.997 116.10 23.997 115.08 Amps Equiv per PP Volts*60 51.826 113.52 26.013 116.10 26.008 111.24 29.741 110.40 Amps Equiv per PP Volts*60 55.498 113.16 26.999 115.98 27.127 115.56 27.127 114.30 Amps Equiv oerPP Volts*60 46.238 114.06 30.333 115.56 26.939 110.40 30.676 109.44

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 16 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE B tt a er~

o tages Period Length Load

  • Adjust Adjusted Total total A-H Total A-Amps Equiv (amos)

Factor Amoeres Time removed Hr/ PP oerPP Volts*60.

1 1

544.52 1.4175 771.857 1

12.864 0.804 48.241 113.88 2

29 366.24 1.4175 519.145 30 263.784 16.487 32.447 115.26 3

30 366.13 1.4175 518.989 60 523.279 32.705 32.437 114.66 4

60 366.18 1.4175 519.060 120 1042.339 65.146 32.441 112.98

  • Temp Correction X Design Margin X Aging Factor 7.2.2 Battery Sizing The remaining capacity for all of the Salem Units 1 and 2, 125 Vdc batteries during the LOOP/LOCA and SBO duty cycles are tabulated below (see Attachment 1 for the IEEE 485-1983 Cell Sizing Worksheets):

Unit 1 Battery Remaining Capacity Remaining Capacity LOOP/LOCA (%)

SBO (%)

1A 42.8 31.0 1B 41.2 9.5 1C 28.0 1.3 Unit 2 Battery Remaining Capacity Remaining Capacity LOOP/LOCA (%)

SBO (%)

2A 48.1 42.7 28 41.4 9.6 2C 30.0 5.6 Please note, these remaining capacities are based upon a temperature correction factor of 1.08 (65°F), an aging factor of 1.25 and a design margin of 1.05 (5%) for Batteries 1 A, 18, 2A, 28 and 2C and no design margin for Battery 1 C.

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 17 of 18 OPS~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2 REVIEWER/VERIFIER, DATE 7.2.3 Battery Charger Sizing The battery charger rated output verses the required battery charger size is tabulated below:

Unit 1 Battery Charger Battery Charger Size Battery Charger Size Battery Rating (Ref. 6.6)

Reqd. (LOOP/LOCA)

Reqd. (SBO) 1A 250A 143.72A 154.73A 1B 250A 137.51A 158.14A 1C 250A 104.59A 125.45A Unit 2 Battery Charger Battery Charger Size Battery Charger Size Battery Rating (Ref. 6.6)

Reqd. (LOOP/LOCA)

Reqd. (SBO) 2A 250A 107.83A 115.06A 28 250A 139.68A 160.32A 2C 250A 106.53A 125.00A

8.0 CONCLUSION

S Battery Sizing The Salem Unit 1 125 Vdc Batteries 1 A, 1 B and 1 C and the Unit 2 125 Vdc batteries 2A, 2B and 2C have adequate capacity to supply the design duty cycle of the 125 Vdc system for both the LOOP/LOCA and SBO loading scenarios. However, battery sizing and voltage drop considerations must be evaluated before any new loads are to be added to the 125 Vdc system.


~

---~----

FORM NC.DE-AP.ZZ-0002-2 CALCULATION CONTINUATION/REVISION HISTORY SHEET SHEET : 18 of 18 O~S~G CALCULATION CONTINUATION/

REVISION HISTORY SHEET CONT'D ON SHEET:

CALC. NO.:

ES-4.004(Q)

REFERENCE:

ORIGINATOR, DATE REV:

2*

REVIEWER/VERIFIER,DATE Battery Charger Sizing The Salem Unit 1 and Unit 2, 125 Vdc battery chargers are Exide, Type USF. They have a continuous output current rating of 250A with current limit capabilities (Ref.

6.6). Two battery chargers are provided for each battery. While one battery charger is in use the other is in standby mode. The results indicate that the required current output of the charger (to support recharging the batteries to 95% capacity in 30 hrs following the postulated discharge duty cycle, while powering the required de loads for steady state operation) may. be set to the most restrictive value (i.e., largest) listed on page 17 of this calculation for Batteries 1A, 18, 1 C, 2A, 28 and 2C.

SARGENT & LUNDY, ENGINEERS LOOP/LOCA Model CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 1A PROJECT NUMBER:

PAGE:

UNIT: 1 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

c:cs::::::=sc=::~:c:E=:=:::::c:::::::::::::::::==::==:==:::::::::::::::===::::::::::::::===::::::::::::::::::::::::::

Lowest Expected Electrolyte Teq>: 65.00 Mini111.111 Battery Voltage ********* : 108.00 Mini111.111 Cell Voltage ************ : 1.800 Cell Mfg: c&D (IEEE-450,1980)

Cell Type: LCR (ALL M<DELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16 I c1> I c2>

<3>

I

<4>

<5>

I

<6>

I

<7>

I I

Change in I Duration Time to Encl I Capacity at I Req*d seetion Size I

I Load I

Load I of Period of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res)

I

(~res)

I (minutes)

I (minutes)

IA!rps/Pos (RT) I Positive Plates

=l====z=l===============l=====================l============l======================l=====--=======1=============

1 I

1 I A1 = 609.230 I A1 -o

=

609.230 I M1

=

1 I T = M1

=

1 I 109.000 I

5.589 I

I I

I I

I I Total =

5.589


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

2. I 1 I A1 = 609.230 I A1 -o

=

609.230 I M1

=

1 I T = M1 + ** +M2 = 30 I 83.500 I

7.296 I

2 I A2 = 297.450 I A2 -A1

= -311.780 I M2 = 29 I T = M2

= 29 I 84.300 I

-3.698 I

I I

I I

I I Total =

3.598


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

3 I

1 I A1 = 609.230 I A1 -o

=

609.230 I M1

=

1 I T = M1 + ** +M3 = 120 I 46.500 I

13.102 I

2 I A2 = 297.450 I A2 -A1

= -311.780 I M2 = 29 I T = M2 + ** +M3 = 119 I 46.767 I

-6.667 I

_3 I A3 = 298.500 I A3 -A2 =

1.050 I M3 = 90 I T = M3

= 90 I 54.500 I

.019 I

I I

I I

I I Total =

6.454


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

MaxillLlll section size = Uncorrected size (US) =

6.454 frcm period 3 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 6.454 1.08 1.05 1.25 9.149 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

42.8X Confirm by calculation.

Calculation ES-4.004(Q)

Rev.2 Page / of 12.

--~-----------------------------------------------------------------------------------------------------------------------

SARGENT & LUNDY, ENGINEERS SBO MOOEL CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 1A PROJECT NUMBER:

PAGE:

UNIT: 1 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

****am=-c.~*==*=*=c=======--=-==========================================================================================

Lowest Expected Electrolyte Teq>: 65.00 Mfnfrrun Battery Voltage ********* : 108.00 Minirrun Cell Voltage ************ : 1.800 Cell Mfg: c&D (IEEE-450,1980)

Cell Type: LCR (ALL MODELS EXCEPT 2LCR*13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

=================================================================--============================================

I c1> I c2>

<3>

I

<4>

<5>

I

<6>

I en I

I Change in I Duration Tfme to Encl I Capacity at I Req 1d Section Sfze I

I Load I

Load I of Period I of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res) I

<~res)

I (minutes) I (minutes) l~/Pos CRT> I.Positive Plates

=1======1===============1=================================1======================1=============1=============

1 I

1 I A1 = 584.770 I A1 -o

= 584.770 M1 = 1 I T = M1

= 1 I 109.000 I

5.365 I

I I

I I

I Total =

5.365


1------1---------------1--------------------- ------------1----------------------1-------------1-------------------

2 I

1 I A1 = 584.770 I A1 -o

= 584.770 M1 = 1 I T = M1 + ** +M2 = 30 I 83.500 I

7.003 I

2 I A2 = 299.070 I A2 *A1 = -285.700 M2 = 29 I T = M2

= 29 I 84.300 I

-3.389 I

I I

I i

I Total =

3.614


1------1--------~------1--------------------- ------------1----------------------1-------------1-------------------

3 I

1 I A1 = 584.770 I A1 -o

= 584.770 M1 = 1 I T = M1 + ** +M3 = 239 I 30.100 I

19.428 I

2 I A2 = 299.070 I A2 *A1 = -285.700 M2 = 29 I T = M2 + ** +M3 = 238 I 30.200 I

-9.460 I

3 I A3 = 213.440 I A3 -A2 = -85.630 M3 = 209 I T = M3

= 209 I 33.100 I

-2.587

.. I I

I I

I I Total =

7.380

---~---1-**;*-1-~;*:--;~:~-1-~;*:~---:---~~:;;~-1-~;-*:***;**1*;*:-~;-:::~*-:-~~~-1----~~:~~~---1----------*;;:~;~--

I 2 I A2 = 299.070 I A2 *A1 = -285.700 I M2 = 29 I T = M2 + ** +M4 = 239 I 30.100 I

-9.492 I

3 I A3 = 213.440 I A3 *A2 = -85.630 I M3 = 209 I T = M3 + ** +M4 = 210 I 33.000 I

-2.595 I

4 I A4 = 254.620 I A4 -A3 =

41.180 I M4 = 1 I T = M4

= 1 I 109.000 I

.378 I

I I

I I

I I Total =

7.784


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

Maxirrun section size= Uncorrected size (US> =

7.784 frm period 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINlllM REQUIRED SIZE 7.784 1.08 _

1~

1.25 11.033

......---=

Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining=

31.0%

Confirm by calculation

Rev.2 Page). of Q

--~-----------------------------------------------------------------------------------------------------------------------

SARGENT & LUNDY, ENGINEERS LOOP/LOCA Model BATTERY SIZING CALCULATION CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 1B PROJECT NUMBER:

UNIT:

PAGE:

USER: rn DATE: 01-13-96

3:z:z::::zm:===============:mD:~=====*=c:c::::==========================================================================

Lowest Expected Electrolyte Tef11>:

65.00 MinilllJll Battery Voltage ********* : 108.00 MinillfJlll Cell Voltage ************ : 1.800 Cell Mfg: c&D CIEEE-450,1980)

Cell Type: LCR CALL M<X>ELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

================z=::r:=================n==*==*m=================================================================

(1)

(2)

Load (3)

Change in Load I

<4>

I Duration I of Period I

I I

(5)

Time to End of Section I

<6>

I en I Capacity at I Req'd Section Size I T min. rate I (3) I (6)

SectionlPeriodl

(~res) I

(~res)

I (minutes) I (minutes) l.Alrps/Pos CRT) I Positive Plates

z====(=================zzmz==========~==========(==========~=I===================================(=================

I 1

A1 = 646.630 A1 -o = 646.630 I M1 = 1 I T = M1

= 1 109.000 I

5.932 I

I I

I Total =

5.932


1------ --------------- ---------------------1------------1---------------------- -------------1-------------------

2 I

1 A1 = 646.630 A1 -o

=

646.630 I M1

=

1 I T = M1 + ** +M2 = 30 83.500 I

7.744 I

2 A2 = 305.240 A2 -A1 = -341.390 I M2 = 29 I T = M2

= 29 84.300 I

-4.050 I

I I

I Total =

3.694


1------ --------------- ---------------------1------------1---------------------- -------------1-------------------

3 I

1 A1 = 646.630 A1 -o

=

646.630 I M1

=

1 I T = M1 + ** +M3

= 120 46.500 I

13.906 I

2 A2 = 305.240 A2 -A1

= -341.390 I M2 = 29 I T = M2 + ** +M3

= 119 46.767 I

-7.300 I

3 A3 = 306.690 A3 *A2 =

1.450 I M3 = 90 I T = M3

= 90 54.500 I

.027

~ I I

I I Total =

6.633

.
;;;1;;;;;;;,;;;;;;*
-;;;;;;;;~;;;;*;;;;*;~;-
---~
~---;;;;,;*;,;;
1;;;--;----------------- -------------1-------------------

us X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 6.633 1.08 1.05 1.25 9.402 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining=

41.2%

Confirm by calculation.

Calculation ES-4.004 ( Q)

Rev.2 Page 3 of I '2.

SARGENT & LUNDY, ENGINEERS SBO MOOEL CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 1B PROJECT NUMBER:

PAGE:

UNIT: 1 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

**=~=*=*==*az:smsm========z**mmza:::s:::a.:c::=====*=======s=============================================================

Lowest Expected Electrolyte Terap: 65.00 Mini111.111 Battery Voltage ********* : 108.00 Mfni1111.111 Cell Voltage ************ : 1.800 Cell Mfg: c&D CIEEE-450,1980)

Cell Type: LCR CALL MODELS EXCEPT 2LCR*13, 2LCR*15)

No. Cells: 60 No. Pos. Plates:

16

sz:cz:c::==*~===============*======================================--=====================================================

I c1> I (2)

I I

I I

Load (3)

Change fn Load I

<4>

I Duration I of Period CS)

Tfme to End of Section I

<6>

I

<7>

I Capacity at I Req'd Section Size I T min. rate I (3) I (6)

SectfonlPeriodl

(~res) I C~res)

I (minutes)

I

<minutes)

IAirps/Pos CRT) I Positive Plates

*=s~l======l===============l=====================l============l======================l=============I================

1 I

1 I A1 = 604.900 I A1 -o = 604.900 I M1 = 1 I T = M1

= 1 I 109.000 I

5.550 2

3

  • ---~---

I I

I I

I I

I Total =

5.550


1---------------1---------------------1------------1----------------------1-------------1-------------------

1 I A1 = 604.900 I A1 -o

=

604.900 I M1

=

1 I T = M1 + ** +M2 = 30 I 83.500 I

7.244 2

I A2 = 293.820 I A2 -A1

~ -311.080 I M2

= 29 I T = M2

= 29 I 84.300 I

-3.690 I

I I

I I

I Total =

3.554


1---------------1---------------~-----1------------1----------------------1-------------

1 -------------------

1 I A1 = 604.900 I A1 -o = 604.900 I M1 = 1 I T = M1 + ** +M3 = 239 I 30.100 2

I A2 = 293.820 I A2 -A1 = *311.080 I M2 = 29 I T = M2 + ** +M3 = 238 I 30.200 3 I A3"' 293.770 I A3 *A2 =

-.050 I M3 = 209 I T = M3

= 209 I 33.100 I

I I

I I

Total =

20.096

-10.301

-.002 9.794


1---------------1---------------------1------------1----------------------1-------------*-------------------

1 I A1 = 604.900 I A1 -o = 604.900 I M1 = 1 I T = M1 + ** +M4 = 240 I 30.000 20.163 2 I A2 = 293.820 I A2 -A1 = -311.080 I M2 = 29 I T = M2 + ** +M4 = 239 I 30.100

-10.335 3

I A3 = 293.770 I A3 -A2 =

-.050 I M3

= 209 I T = M3 + ** +M4 = 210 I 33.000

-.002 4

I A4 = 335.890 I A4 -A3 =

42.120 I M4 = 1 I T = M4

= 1 I 109.000

.386 I

I I

I I

Total =

10.213


1------1---------------1---------------------1------------1----------------------1-------------*-------------------

Maxi111.111 section size = Uncorrected size (US) = 10.213 from period 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 10.213 1.08 1.05 1.25 14.477 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

Confirm by calculation.

9.5X Calculation ES-4.004 ( Q)

Rev.2 Page4 of 12.

SARGENT & UJNDY, ENGINEERS LOOP/LOCA Model CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 1C PROJECT NUMBER:

PAGE:

UNIT: 1 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

=~===================================================================================================================--

Cell Mfg: c&D (IEEE-450,1980)

Lowest Expected Electrolyte T~: 65.00 MinillLlll Battery Voltage ********* : 108.00 MinillLlll Cell Voltage ************ : 1.800 Cell Type: LCR (ALL MODELS EXCEPT 2LCR*13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

==============================================================================================================

I <1> I c2>

<3>

I

<4>

<5>

I

<6>

I en I

I Change in I Duration Time to End I Capacity at I Req 1d Section Size I

I Load Load I of Period of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res) I

(~res)

I (minutes) I (minutes)

IAq>s/Pos CRT> I Positive Plates

*====1=====2 1==~============1====================~1============1====================================================

1 I

1 I A1 = 573.450 I A1 -o = 573.450 I M1 = 1 I T = M1

= 1 109.000 5.261 I

I I

I I

Total =

5.261


1------1---------------1---------------------1------------1---------------------- ------------- -------------------

2 I

1 I A1 = 573.450 I A1 -o = 573.450 I M1 = 1 I T = M1 + ** +M2 = 30 83.500 6.868 I

2 I A2 = 395.820 I A2 -A1 = -177.630 I M2 = 29 I T = M2

= 29 84.300

-2.107 I

I I

I I

Total =

4. 761

1------1---------------1---------------------1------------1---------------------- ------------- -------------------

3 I

1 I A1 = 573.450 I A1 -0 = 573.450 I M1 = 1 I T = M1 + ** +M3 = 120 46.500 12.332 I

2 I A2 = 395.820 I A2 *A1 = -177.630 I M2 = 29 I T = M2 + ** +M3 = 119 46.767

-3.798 I

3 I A3 = 395.750 I A3 -A2 =

-.070 I M3 = 90 I T = M3

= 90 54.500

-.001

.. I I

I I

I Total =

8.533


1------1---------------1---------------------1------------1---------------------- ------------- -------------------

Maxinun section size = Uncorrected size (US) = 8.533 from period 3 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 8.533 1.08 1.00 1.25 11.519 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

28.0X Confirm by calculation.

Calculation ES-4.004 ( Q)

Rev.2 Page 5of 12

~SARGENT & LUNDY, ENGINEERS SBO MOOEL BATTERY SIZING CALCULATION CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: SALEM BATTERY 1C PROJECT NUMBER:

PAGE:

UNIT: 1 USER: rn DATE: 01-13-96

========----==============--=====================================================================================

Cell Mfg: C&D (IEEE-450,1980)

Lowest Expected Electrolyte Teirp: 65.00 Mini111.111 Battery Voltage ********* : 108.00 Mfni111111 Cell Voltage ************ : 1.800 Cell Type: LCR (All M<X>ELS EXCEPT 2LCR-13, 2LCR*15)

No. Cells: 60 No. Pos. Plates: 16 z****=*=czz=*~========~============*====*==============================================================================

I <1> I c2>

<3>

I

<4>

<5>

I

<6>

I en I

I Change in I Duration Time to End I Capacity at I Req'd Section Size I

I Load Load I of Period of Section I T min. rate I (3) I (6)

SectionlPeriodl (aq:>eres)

I (811'>eres)

I (minutes) I (minutes) l~/Pos (RT>I Positive Plates

a*ss**J~=*m**f==========~====J============z========J============J======================================================

1 I

1 I A1 = 551.800 I A1 -o

=

551.800 I M1

=

1 I T = M1

= 1 109.000 5.062 I

I I

I I

Total =

5.062

-******l******l***************l*********************l*********-**I********************** ************* *******************

2 I

1 I A1 = 551.800 I A1 *O = 551.800 I M1 = 1 I T = M1 + ** +M2 = 30 83.500 6.608 I

2 I A2 = 372.920 I A2 *A1

= *178.880 I M2 = 29 I T = M2

= 29 84.300

  • 2.122 I

I I

I I

Total =

4.486

              • l******l***************l*********************l************I********************** ************* *******************

3 I

1 I A1 = 551.800 I A1 *O

=

551.800 I M1

=

1 I T = M1 + ** +M3 = 239 30.100 18.332 1

2 1 A2 = 372.920 r A2 -A1

= -118.880 1 M2

=* 29 1 T = M2 + ** +M3 = 238 30.200

-5.923 I

3 I A3 = 335.190 I A3 *A2 = -37.730 I M3 = 209 I T = M3

= 209 33.100

-1.140 I

I I

I I

Total =

11.269

        • -**l******l***************l*********************l************l***************-****-*1-************I**************-****

4 I

1 I A1 = 551.800 I A1 *O

=

551.800 I M1

=

1 I T = M1 + ** +M4

= 240 I 30.000 I

18.393 I

2 I A2 = 372.920 I A2 *A1

= *178.880 I M2 = 29 I T = M2 + ** +M4

= 239 I 30.100 I

  • 5.943 I

3 I A3 = 335.190 I A3 *A2 =

  • 37.730 I M3 = 209 I T = M3 + ** +M4 = 210 I 33.000 I
  • 1.143 I

4 I A4 = 377.380 I A4 *A3 =

42.190 I M4 = 1 I T = M4

= 1 I 109.000 I

.387 I

I I

I I

I I Total =

11.694

              • l******l***************l******************-**l*********--*l-*-**-***-------------1-************I*******************

Maxi111.111 section size= Uncorrected size (US)= 11.694 from period 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMl.M REQUIRED SIZE 11.694 1.08 1.00 1.25 15.787 Selected battery pos plates = 16 I Battery capacity remaining =

1.3X Calculation ES-4.004 ( Q)

Rev.2 Page(? of 12

SARGENT & LUNDY, ENGINEERS CHICAGO, ILLINOIS ELMS-DC VERSION 2-00 PROJECT NUMBER:

PAGE:

. STATION: Salem Battery 2A UNIT: 2 USER: rn DATE: 01-13-96 LOOP /LOCA Model BATTERY SIZING CALCULATION

*=z=======*=================================================--=========================================================

Lowest Expected Electrolyte T~: 65.00 Mini111.111 Battery Voltage ********* : 108.00 Mini111.111 Cell Voltage ************ :

1.800 Cell Mfg: c&D CIEEE-450,1980)

Cell Type: LCR CALL M<DELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

======*=======================================================================================================

I <1> I c2>

<3>

I

<4>

c5>

I

<6>

I en I

I Change in I Duration Time to End I Capacity et I Req'd Section Size I

I Load Load I of Period I of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res)

I (aq>eres)

I (minutes) I (minutes)

IAq>s/Pos CRT) I Positive Plates

=1======1===============1=====================1==================================1=============1=============

1 I

1 I A1 = 551.960 I A1 -0

=

551.960 I M1

=

1 T = M1

=

1 I 109.000 I

5.064 I

I I

I I

I Total =

5.064


1------1---------------1---------------------1------------


1-------------1----------------~--

2 I

1 I A1 = 551.960 I A1 -o

=

551.960 I M1

=

1 T = M1 + ** +M2

= 30 I 83.500 I

6.610 I

2 I A2 = 269.830 I A2 -A1

= -282.130 I M2 = 29 T = M2

= 29 I 84.300 I

-3.347 I

I I

I I

I Total =

3.264


1------1---------------1---------------------1------------ ----------------*------1-------------1-------------------

3 I

1 I A1 = 551.960 I A1 -o

=

551.960 I M1

=

1 T = M1 + ** +M3

= 120 I 46.500 I

11.870 I

2 I A2 c 269.830 I A2 -A1

= -282.130 I M2 = 29 T = M2 + ** +M3

= 119 I 46.767 I

-6.033 I

3 I A3 = 270.870 I A3 -A2 =

1.040 I M3 = 90 T = M3

= 90 I 54.500 I

.019 I

I I

I I

I Total =

5.856


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

MaXillLlll section size = Uncorrected size (US) =

5.856 from period 3

µs X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINlll.M REQUIRED SIZE 5.856 1.08 1.05 1.25 8.302 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining=

48.1%

Confirm by calculation.

Calculation ES-4.004 ( Q)

Rev. 2 Page 7 of I;(.

SARGENT & LUNDY, ENGINEERS CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 2A PROJECT NUMBER:

PAGE:

UNIT: 2 USER: rn DATE: 01-13-96 sea MODEL BATTERY SIZING CALa.JLATION

*z**====*zz~a*=========:sc::z:===========================================================================================

Lowest Expected Electrolyte Teq>: 65.00 Minillllll Battery Voltage ********* : 108.00 Minillllll Cell Voltage ************ : 1.800 Cell Mfg: c&:> CIEEE-450,1980)

Cell Type: LCR CALL MCl>ELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

****a*z==*~*a**=====================**z===================z=======----==================================================

I <1> I c2>

<3>

I

<4>

<5>

I

<6>

I en I

I Change in I Duration Time to End I Capacity at I Req'd Section Size I

I Load Load I of Period of Section I T min. rate I (3) I (6)

SectionlPerfodl (aq:>eres)

I Caq:>eres)

I (minutes)

I (minutes)

IAD1>S/Pos CRT>I Positive Plates

****zzl==z***l=*=============l=====================l============l======================I===============================

1 I

1 I A1 = 515.830 I A1 -o

= 515.830 I M1 = 1 I T = M1

= 1 I 109.000 4.732 I

I I

I I

I Total =

4.732


1------1---------------1---------------------1------------1----------------------1------------- -------------------

2 I

1 I A1 = 515.830 I A1 -o

= 515.830 I M1 = 1 I T = M1 + ** +M2 = 30 I 83.500 6.178 I

2 I A2 = 259.470 I A2 -A1 = -256.360 I M2 = 29 I T = M2

= 29 I 84.300

-3.041 I

I I

I I

I Total =

3.137


------1---------------1---------------------1------------1----------------------1------------- -------------------

3 I A1 = 515.830 I A1 -0

= 515.830 I M1 = 1 I T = M1 + ** +M3 = 239 I 30.100 17.137 2 I A2 = 259.470 I A2 -A1 = -256.360 I M2

= 29 I T = M2 + ** +M3 = 238 I 30.200

-8.489 3 I A3 = 173.840 I A3 -A2 = -85.630 I M3 = 209 I T = M3

= 209 I 33.100

-2.587 I

I I

I I

Total =

6.061


------1---------------1---------------------1------------1----------------------1-------------1-------------------

4 1 I A1 = 515.830 I A1 -o

=

515.830 I M1 = 1 I T = M1 + ** +M4

= 240 I 30.000 I

17.194 2 I A2 = 259.470 I A2 -A1

= -256.360 I M2 = 29 I T = M2 + ** +M4 = 239 I 30.100 I

-8.517 3 I A3 = 173.840 I A3 -A2 = -85.630 I M3 = 209 I T = M3 + ** +M4 = 210 I 33.000 I

-2.595 4 I A4 = 216.070 I A4 -A3 =

42.230 I M4 = 1 I T = M4

= 1 I 109.000 I

.387 I

I I

I I

I Total =

6.470


------1---------------1---------------------1------------1----------------------1-------------1-------------------

Maxinl.lll section size = Uncorrected size (US) = 6.470 from period 4 US X TEMP. CORR. X DESIGH MARGIN X AGING FACTOR = MINIMlJI REQUIRED SIZE 6.470 1.08 1.05 1.25 9.171 Selected battery pos plates = 16 IJARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

42.7" Confirm by calculation

Rev.2 Page 2 of r2

~

SARGEllT & LIJNDY, EHGJIEERS LOOP/LOCA Model BATTERY SIZING CALCULATION CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 2B PROJECT Nll4BER:

PAGE:

UNIT: 2 USER: rn DATE: 01-13-96

==============================================================================================================

Cell Mfg: c&D CIEEE-450,1980)

Lowest Expected Electrolyte Teq>: 65.00 Mini111111 Battery Voltage ********* : 108.00 Mini111111 Cell Voltage ************ : 1.800 Cell Type: LCR CALL MCX>ELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

z=======================================================================--=============================================

I c1 > I (2)

I I

I I

Load (3)

Change in Load I

<4>

I Duration I of Period (5)

Time to End of Section I

<6>

I en I Capacity at I Req'd Section Size I T min. rate I (3) I C6>

SectfonlPeriodl (aq>eres)

I

(~res)

I (minutes) I (11inutes) l~/Pos CRT> I Positive Plates

"'~===1======1===============1=====================1============1======================1=============1=================

1 I

1 I A1 I: 626.430 I A1 -o I:

626.430 I M1

=

1 I T = M1 1 I 109.000 I

5.747 I

I I

I I

I I Total =

5.747


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

2 I

1 I A1 = 626.430 I A1 -o

= 626.430 I M1 = 1 I T = M1 + ** +M2 = 30 I 83.500 I

7.502 I

2 I A2 = 304.750 I A2 -A1 = -321.680 I M2 = 29 I T = M2

= 29 I 84.300 I

-3.816 I

I I

I I

I I Total =

3.686


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

3 I

1 I A1 = 626.430 I A1 -o

=

626.430 I M1 = 1 I T = M1 + ** +M3 = 120 I 46.500 I

13.472 I

2 I A2 = 304.750 I A2 -A1 = -321.680 I M2 = 29 I T = M2 + ** +M3 = 119 I 46.767 I

-6.878 I

3 I A3 = 306.190 I A3 -A2 =

1.440 I M3 = 90 I T F M3

= 90 I 54.500 I

.026

.. I I

I I

I I

I Total =

6.620


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

Maxillllll section size = Uncorrected size (US) =

6.620 fran period 3 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMll4 REQUIRED SIZE 6.620 1.08 1.05 1.25 9.383 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

41.4X Confirm by calculation.

Calculation ES-4.004 (Q)

Rev.2 Page q of 12

.SARGENT & LUNDY, ENGINEERS SBO MOOEL CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 2B PROJECT NUMBER:

PAGE:

UNIT: 2 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

*=======~================--============================================================================================

Lowest Expected Electrolyte T~: 65.00 Mfnil!J.all Battery Voltage ********* : 108.00 Minil!J.all Cell Voltage ************ : 1.800 Cell Mfg: c&D CIEEE-450,1980)

Cell Type: LCR CALL MODELS EXCEPT 2LCR*13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16 I o> I c2>

<3>

I c4>

<5>

I

<6>

I en I

I Change in I Duration Time to End I Capacity at I Req 1d Section Size I

I Load Load I of Period of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res)

I

(~res)

I (minutes)

I (minutes)

IA111:>S/Pos CRT) I Positive Plates

*===*1======1==============1=====================1============1======================1=============1=================

1 I

1 I A1 = 584.990 I A1 -o

= 584.990 I M1 = 1 I T = M1

= 1 I 109.000 I

5.367 I

I I

I I

I I Total =

5.367


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

2 I

1 I A1 = 584.990 I A1 -0

= 584.990 I M1 = 1 I T = M1 + ** +M2 = 30 I 83.500 I

7.006 I

2 I A2 = 293.620 I A2 -A1 = -291.370 I M2 = 29 I T = M2

= 29 I 84.300 I

-3.456 I

I I

I I

I I Total =

3.550


1------1---------------1---------------------1------------1----------------------1------------- -------------------

3 I

1 I A1 = 584.990 I A1 -o

= 584.990 I M1 = 1 I T = M1 + ** +M3 = 239 I 30.100 19.435 I

2 I A2 = 293.620 I A2 -A1 = -291.370 I M2 = 29 I T = M2 + ** +M3 = 238 I 30.200

-9.648

~ I 3 I A3 = 293.570 I A3 -A2 =

-.050 I M3 = 209 I T = M3

= 209 I 33.100

-.002 I

I I

I I

I Total =

9.785


1------1---------------1---------------------1------------1----------------------1------------- -------------------

4 I

1 I A1 = 584.990 I A1 -0

=

584.990 I M1 = 1 I T = M1 + ** +M4 = 240 I 30.000 I

2 I A2 = 293.620 I A2 -A1

= -291.370 I M2 = 29 I T = M2 + ** +M4 = 239 I 30.100 I

3 I A3 = 293.570 I A3 -A2 =

-.050 I M3 = 209 I T = M3 + ** +M4 = 210 I 33.000 I

4 I A4 = 335.700 I A4 -A3 =

42.130 I M4 =

I T = M4

= 1 I 109.000 I

I I

I I

I Total =

19.500

-9.680

-.002

.387 10.205


1------1---------------1---------------------1------------1----------------------1------------- -------------------

Maximum section size c: Uncorrected size (US) = 10.205 from period 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 10.205 1.08 1.05 1.25 14.465 Selected battery pos plates = 16 WARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

Confirm by calculation

Rev. 2 Page 1~ of /2..

SARGENT & LUNDY, ENGINEERS LOOP/LOCA Model CHICAGO, ILLINOIS ELMS-DC VERSION 2.00 STATION: Salem Battery 2C PROJECT NUMBER:

PAGE:

UNIT: 2 USER: rn DATE: 01-13-96 BATTERY SIZING CALCULATION

~===============================================================================================================

Lowest Expected Electrolyte Teq>:

65.00 Mini111111 Battery Voltage ********* : 108.00 Mini111111 Cell Voltage ************ :

1.800 Cell Mfg: c&D CIEEE-450,1980)

Cell Type: LCR CALL MODELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

zz:cz::zz:::::::::======~==================================================================================================

I en I c2>

c3>

I c4>

c5>

I

<6>

I c7>

I I

Change in I Duration Time to End I Capacity at I Req 1d Section Size I

I Load Load I of Period of Section I T min. rate I (3) I (6)

SectionlPeriodl

(~res) I

(~res)

I (minutes) I (minutes) l~/Pos CRT) I Positive Plates

zl======l===============l=====================l============l======================I==========================

1 I

1 I A1 = 544.520 I A1 -o

=

544.520 I M1

=

1 I T = M1

=

1 I 109.000 4.996 I

I I

I I

I Total =

4.996


1------1--------------- ---------------------1------------1----------------------1------------- -------------------

2 I

1 I A1 = 544.520 A1 -o

=

544.520 I M1

=

1 I T = M1 + ** +M2

= 30 I 83.500 6.521 I

2 I A2 = 366.240 A2 -A1

= -178.280 I M2 = 29 I T = M2

= 29 I 84.300

-2.115 I

I I

I I

Total =

4.406


1------1--------------- ---------------------1------------1----------------------1------------- -------------------

3 I

1 I A1 = 544.520 A1 -o

=

544.520 I M1

=

1 I T = M1 + ** +M3

= 60 I 65.500 8.313 I

2 I A2 = 366.240 A2 -A1

= -178.280 I M2 = 29 I T = M2 + ** +M3

= 59 I 66.033

-2.700

.. I 3 I A3 = 366.130 A3 -A2 =

-.110 I M3 = 30 I T = M3

= 30 I 83.500

-.001 I

I I

I I

Total =

5.612


1------1--------------- ---------------------1------------1----------------------1------------- -------------------

4 I

1 I A1 = 544.520 A1 -0

=

544.520 I M1

=

1 I T = M1 + ** +M4

= 120 I 46.500

11. 710 I

2 I A2 = 366.240 A2 -A1

= -178.280 I M2 = 29 I T = M2 + ** +M4

= 119 I 46.767

-3.812 I

3 I A3 = 366.130 A3 -A2 =

-.110 I M3 = 30 I T = M3 + ** +M4

= 90 I 54.500

-.002 I

4 I A4 = 366.180 A4 -A3 =

.050 I M4 = 60 I T = M4

= 60 I 65.500

.001 I

I I

I I

Total =

7.897


1------1--------------- ---------------------1------------1----------------------1------------- -------------------

Maxi111111 section size = Uncorrected size (US) =

7.897 from perio:J 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMUM REQUIRED SIZE 7.897 1.08 1.05 1.25 11.194 Selected battery pos plates = 16

~ARNING: Fewer plates may not be adequate!

I Battery capacity remaining =

30.0X Confirm by calculation

Rev.2 Page rt of 12.

~SARGENT & LUNDY, ENGINEERS SBO MOOEL BATTERY SIZING CALCULATION CHICAGO, ILLINOIS ELMS-DC VERSION 2-00 STATION: Salem Battery 2C PROJECT NUMBER:

PAGE:

UNIT: 2 USER: rn DATE: 01-13-96

zm*====:cz:::::::::~z======~================================================================================================

Cell Mfg: c&D CIEEE-450,1980)

Lowest Expected Electrolyte T~: 65.00 Minina.n Battery Voltage_ ******** : 108.00 Mfnina.n Cell Voltage ************ : 1.800 Cell Type: LCR (ALL MCl>ELS EXCEPT 2LCR-13, 2LCR-15)

No. Cells: 60 No. Pos. Plates: 16

====~:n::z=====================================================================================================

I < 1 > I (2)

I I

I I

Load (3)

Change in Load I

(4)

I Duration I of Period I

I I

(5)

I

<6>

I

<7>

Time to End I Capacity et I Req 1d Section Size of Section I T min. rate I (3) I C6>

SectfonlPerfodl Carrperes)

I Carrperes)

I (minutes) I (minutes) l~/Pos CRT>I Positive Plates

*====l=m====l===============l=====================l============I===================================!=================

1 I

1 I A1 = 521.910 I A1 -o

=

521.910 I 141 = 1 I T = M1

= 1 109.000 I

4.788 I

I I

I I

I Total =

4. 788

1------1---------------1---------------------1------------1---------------------- -------------1-------------------

2 I

1 I A1 = 521.910 I A1 -o = 521.910 I M1 = 1 I T = M1 + ** +M2 = 30 83.500 I

6.250 I

2 I A2 = 342.380 I A2 -A1

= -179.530 I M2 = 29 I T = M2

= 29 84.300 I

-2.130 I

I I

I I

I Total =

4.121


1------1---------------1---------------------1------------1---------------------- -------------1-------------------

3 I

1 I A1 = 521.910 I A1 -0 = 521.910 I M1 = 1 I T = M1 + ** +M3 = 239 30.100 I

17.339 I

2 I A2 = 342.380 I A2 -A1 = -179.530 I M2 = 29 I T = M2 + ** +M3 = 238 30.200 I

-5.945 I

3 I A3 = 304.070 I A3 -A2 = -38.310 I M3 = 209 I T = M3

= 209 33.100 I

-1.157

"' I I

I I

I I Total =

10.237


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

4 I

1 I A1 ~ 521.910 I A1 -o = 521.910 I M1 = 1 I T = M1 + ** +M4 = 240 I 30.000 I

17.397 I

2 I A2 = 342.380 I A2 -A1 = -179.530 I M2 = 29 I T = M2 + ** +M4 = 239 I 30.100 I

-5.964 I

3 I A3 = 304.070 I A3 -A2 = -38.310 I M3 = 209 I T = M3 + ** +M4 = 210 I 33.000 I

-1.161 I

4 I A4 = 346.260 I A4 -A3 =

42.190 I M4 = 1 I T = M4

= 1 I 109.000 I

.387 I

I I

I I

. I I Total =

10.659


1------1---------------1---------------------1------------1----------------------1-------------1-------------------

Maxinun section size = Uncorrected size (US) = 10.659 from period 4 US X TEMP. CORR. X DESIGN MARGIN X AGING FACTOR = MINIMlJ4 REQUIRED SIZE 10.659 1.08 1.05 1.25 15.109 Selected battery pos plates = 16 I Battery capacity remaining =

5.6X Calculation ES-4.004( Ii)

Rev.2 Page /J. of P..

ATTACHMENT 2 REFERENCES Calculation ES-4.004(Q)

Rev.2 Page 1 of 3

.~t T

l I

r I

~.

i I

I I

  • j I

J HI

ff 11 t~

I I

i uo l.i lWl ooc Wd)©J

!}= ~-= @&:

00~~

=.;>)!n~ntf.ll::\\

~

j
..

. (.. :

~

o~

©

\\!..,

=

t\\]

.@(,)

.!! {l)

"ij ~

~<bf)

~Ii";

t' 1:.

! ~ ) I

'1 J

,... 1~ur 1 i H j"u. *u I h 111 11 IU r. l m I

11 200 :

220 POSITIVE PLATE 10SITIVE.. ~LATE Calculation ES-4.004 ( Q)

Rev. 2.

PageZb of 3 REF.

'-~

Hi Ii. i I I U

II I

240 J.

REVISIONS ZONE NO.

m DESCRIPTION C.1h.)..l1.~ Mod.t.L "t"JP~ f~C>M' LC::

fo "Lc.R:

DATE I

APPROVED

't~&7 I 4.\\\\J~t~

R e.f. G.,.- e,.* ' r a_ JSr. B I.

I 2.00. U).

...J

... 0 1.9~ : >

1.so i

_J

..J l1J

(.)

.. -I 1-70 <

i=

      • z 1.60 ' -

I I 'i f

m 1~50 DISCHARGE RATE OR CELL SIZING CORRECTION FACTORS FOR DETERMINING INDIVIDUAL CELL TYPE CAP ABILITY tlNTERPOLATE BETWEEN TIME. PERIODS)

I DISCHARGE TIME PERIOD *

!.!ll 2 a hr J hr

. I hr JO' 15'

.10*

5*

1

  • 1.055 1.125 1.095 1.065 l.045 1.000 2.Lr.11.-lS l.(\\'.l'\\

l.noo. --*.a.ass 1.12.5 1.0195 1.on

l. cr, 5 I. ()Qi;\\

-Lea.-::*-

!.CJS

1. o:;~
.c~s 1.040 l.030
.os:i 1.0.SO 1.0.50 LCl.. U 1.035 l.oso 1.035 l.040 1.050 1.oso 1.050 1.050 I LCJl-17 l.035 l.0.50 1,035 l.040 1.050 1.05:>

1.050 1.050 LCll*l9 1.035 1.050 1.050 l.085 I. Ill l.113 1.121 1.143 LCl*21 l.035 l.050 l.050 l.0115 1.113 1.113 1.1211.

1.143 LCll*2l l.035 1.050 l.050 1.075 1.087 1.080

!.'180 I.OU LC1*25 l.OJS 1.050 l.040 1.052 1.055 l.OSS 1.0~5 1.071 LCR.-21 l.035 1.030 l.025 1.050 1.050 1.040 1.040 1.040 LCR-29 1.000 1.000 LOIS l.030 l.035 1.024 1.0U I.OU

~""'-

l. 000 1.000 1.000 l.010 l.005 l.005
  • l.005 1.005 lV 1.ouu I.ODO 1,000 1.000 1.000 l.Ot:O 1.000 1.000 TO XET!!RMINE THE PERFORMANCE CAPABILITY OF A MODEL CR TE IN AMPS OR CAPACITY IN AMP-HRS ), MULTIPLY
  1. .MN!.QR.AMP-HRS Pl;R.Pq~ITIVE PLATE, FOR SPECIFIED IUA! AND VOLTAGE, BY THE APrLICADL'E CORRECTION FACTOR, r

10 CALCULATE HOW LONO A MODEL CAN CARRY A LOAD, FIRST DIVIDE THE LOAD CAMPI) BY THE APPLICABLE CORRECTION FACTOR

  • f 280.

26(:..

300 320.

340

. 360

=~


POWER SYSTEMS 30-43 WALTON ROAD, PLYMOUTH MEETING, PA 10-482 DISCHARGE CHARACTERISTICS APPROVED SIZE I CODE IDENT. NO.

c D - 841 APPROVED SCALE N 0 NE I REV. NO.

I I SHEET

'-~

I

J

~

I I~ *....

~

~ i'

. nos PRINT ANO THE ltlfOOMATION SHOIVtl THfOEON IS THI! PROPERTY OP

....... Jc & 0 Powi:n 'YllTl!M.S ANO, IS BEINO fURHISHEO AS A COllFIOENTU.L OllCLOIURI.

IT MAY NOT DE DELilleREO TO OTHERI NOR REPROOUCE.D fOR GENERAL CU*CULATIOH WITHOUT THI Wl'ITIIN APPROVAL or ALLIED c I. D P.OWER IYITEML l1l1!J E:

©~

"2

~d(Q) ~~

D I

[}= D= ~.!! ~,

~

-d

<::)

a-rl. rl

"""'"'"' 1 an cn.111J111.111111IIll11111" 1111,..,,.,,,,,., **, **

°'1

~~~ 1m!.;!I;'

zwg l

I

.d~

I

~~

..*.,r.

~ ;4*');

I I

    • .* 200 I I I

Utrlll ll I I II IJll l.11111 ti llJ.IJ I tl111111il I I!

I* 180 o I *

~. : *

  • 1eo
  • D:t1J

~ ~

> "O I

  • 1

-i m 140 I I c

-i :0

, I I m J:

I 0

J:

I c

0 I

a c

.CfJ :O"

. ~.: '(' " 120 Hlflf ll"lllW"Mlm m "O

P m

.. :p

"'CJ 0

"'CJ.**

(J) 0 10000i'"""'~

en.

  • ~. ~.

)1

... 'f M *** llmOO!Hll!l!Ull'mU!illlU!!U!l!!U!llmwm111111111m11111111111111111nnmnmm

-
;!!.. 8 ci 11 I I l l.

NJ 1114'1001110011111111 fltttUf tlUlll llllllHI 111111 Ulllll II II II lllllli

-i >

0 I m. fri 1111111ru E 11rn111111 m11111111111 m11111 N 11H111111ru1m111 N11111 r.1e 8-'

I I

!' QI A

u i

i,

  • **,:*.s 0

llMll~l~llllllllll~-l-*Bij~l~llllmllllll~""'

1 m

04

~1~1 I

r

' I JllitlBl-1~**

  • Ullllllllllll ll Ilrmllilllll11llJlllll 20

[

~*

  • 11*

ltlt'M I

.O*~**

    • o 20 40*
eo.

80 *;

100 120 140 160 CELL_ MODE~:*-*---.--

NUMBER OF PLATES*-* __

ELECTAOL YTE* Sp.Gr.* __

TEM~EAATUAE*-* -.------

TEST* PROCEDURE *-* ---

Calculation ES-4.004 CQ)

Rev. 2.

Page Z4 of 3 Ref.

~.4

. :.1. ~I

  • 13 thru
  • 33 *
1.

.. 1.215. :f.005

. :. 17~,:. <26~ c)

  • *1.
  • IEEE Std 450-198C:

~

N

~

  • ~ *
  • AMPERES
  • 0 WATTS F Data Is based on *125 volt battery terminal vqlts *

. *.. standa:rci ceu arriroeffienf :. *

,. 1 Staridar~ ln_t~rCi! coonector~. * *

  • 1 ---:----ie-:-

~,

Parson Ca.ll1nq Projaat sa1mn Subjeot Disousaed:

c:;a.11.1.,. t -*-*

ccmpG.ny

Projeo'C No.

pA60*043

  • f"r:,,... !I"'"-

IA&li4AJFllll

-Jl,,,.).. _ _..,_...,.L,_,.

Summary c~ Dieouesion, oeci$io~* and CQJl!mitmant*

Mr. wa.u:er imliGA*ted tbi:it t:he d.i*charq.a aharact*ri*'t:ioa.:urve (D-841 1 Rev.

~i

~or t;h* typ-8 LC1\\ oc11 o&~ algo ba utilized tor tbe typ~ ~c oe11,

( ~.. &,\\ ~. e.)

ooa a. L. Renwick -

23 J. J. Bojan ~ 23

s. v.

8~lkc.r -

(~alom-S,L) l.. 0 c'D Chart~r ~owar sy~tems: Please oonr1rm we h~ve 4QO~~~ly re~grded the eonversaticn 'Dy aiqninq ~elow and returnin9 to J, l(rv*v*c vi& tax to (31..~) 269*2179

  • c~ic.... l... f,o" t.s-1. oo "CQ)

~e.I). l.

ft TT ltC.HM l.~r 2.

P~u 3 of 3

FORM NC.DE-AP.ZZ-0010-1 Page 2 of 4 Ct?t /C""- !u ho,, !=5-L/,oo'f{L

/( e. v. ;L CERTIFICATION FOR DESIGN VERIFICATION Reference No. 1;;s - 4, oo LJ {Q)

SUMMARY

.. STATEMENT A f/e1c-hfi1 enf

~

ft::-,, 51 c..

I o f 7

A vfc/> f/C?.1-;c1 l(x

.::1 de.-i<<Pr; /eJ bq ~";v /(,i ~Y t!

1yc./e..

/nc /t,.,J/-,1 '?

C?pt!'rc.z let'-

&?c...- T/;,,, h.J' IS u.}~&1 fo w~ /cr.1?1,;,e l

01 t.t7rresj)(f';'/1~b ~ h~ l(e,-y Vt::?/ fe:,~ e. pr~ I'/ l-e fP.--

e.~c,,-A Se.pq;~q T<=-

bqflc,y f.ror;,,

fhe.

he::t'/lery J??~/lvz lu-c.ft;,rc.r The undersigned hereby certifies (in the right column) that the design verification for the subject document has been completed,

-the questions from the generic checklist have been revieWed and addressed as app~opr'ate, and all comments have been adequately incorporat~

I

__.,____..._~,__.,._----.....-1. ___ 1 __

~....._.~

~

~ ~

0 V°!t ifier Assi ne By Sigpature of Design Verifier / bate ure of Manager/Supervisor)

Design Verifier Assigned By Si~ature of Design Verifier / Date (signature of Manager/Supervisor)

Design Verifier Assigned By Sig~ature of Design Verifier / Date (signature of Manager/Supervisor)

Design Verifier Assigned By

-Sig~ature of Design Verifier / Date (signature of Manager/Supervisor)

  • If the Functional Manager/Supervisor acts as the Design Verifier, the signature of the next higher level of technical management is required.

Page

  • .of 7 Rev. 2 Page 13 of 17 Nuclear Common

Rev. 2 FORM NC.DE-AP.ZZ-0010-1 Page 3 of 4 CPr/C'IA /&-<.//on F-S-l/tOO'l(a}

Re 1.r..i.

/t /ft::<c. hP>e-Pl f 3

CERTIFICATION FOR DESIGN VERIFICATION pc,-p c. ;i._

0.f 7 0 -f f.h/.r

/f.,-

fhe en f ire..-/-v.

?

Page.2::_ of 7 Page 14 of 17 rf d? Is(?

St-;pe,.,,- S'e4_,

,ES-i/~ OD,;2. (a;), /(~v. 0 Nuclear Common

SENT BY:SARGE~T & Lll\\DY 23E12 1-17-96 ; 2:08PM SARGE~T & LLNDY...,123-09560144-l$SS~H ;# 2/ 4 Co; le-IA. /e;:,-/-/c-n

~s-'-/.Ol)l/(rx.)

~

  • c.D**u.z.z-001C*J.

Rev..?-

    • g* t o! t A #,?tc..l.n-. e rz f 3 CBR.TlF%CA'l'XOll J'OI, DBStGI" "fDJ.*le&.':l:C.

PM/ C:.

3 °-f 7 COMMENTS

/, /)/'JCt-t5$1'11"4 ll't.fa.c.//c;ns*.J,0

<<.,J ~.) '7"'

~'.!'n'"":Y "f*" /.,,-

te f 1Atr'" c /"' n*/;;'-./1'd'.1-1.

1"h""

S l<< leni~,, f f)J~-t fh#.:.

))t!f'fl~,,.i"eL,,

,,..;/I J;t!..re,J.il-"'c41 ~-1 ft;7p fr:,,* lie (l-e,-£ "C~ 6, J J.r. e Et:

lfFS-1,,, tJ t>

,";..,-,,,.rt>~I. i.Jtc.

t E EIE sft:<,,,,;;,,l /c,"i:.~* nof-re<;...,. tr& te.,Plt.a!,*ot:;.-,e"' t,..f.Yo~

a n,,I etr;. *h.1.<t I pf~ r_/5'( 1#1 *~a rt:') l~ce. IS by.PSt *f '".-

2~ S<.,.. */. ttv' iii o/ -

L M-c

'h:n,pe~""~ f~r f-Ae b.lf~,,..l fi¥'" fhe J;., fiery ~t'()J:>? ?

RESOLUl'ION

~e. ft:...$pr;;1~e o A Aff9~t.f!.J sAeJ.

"--.:"' n Jl.eT. a

'.P*11* 15 o! 1'

NllS:lt~ 96-ll-1
,r..a !N3S

SENT BY:SARGE.\\T & LUNDY 23E12 ; 1-17-96 ; 2:Q8PM SARGE.\\'T & LLNDY-1123-09560144-SUSSU ;# 31 4 c

CJ, I e""' I.,_/, o.h E5--t../, oo'-1 (ai POD: 111C!.1J**.U.Zli* 0010*1

/? e. v...2..

1'*9* 4 ot 4

  • . A H~c-h~c,., -I 3 CD.~:XPJ:CAT'Iml i'O& i>*l%Qll' VD.DXCUIOW J7 c.-:;;.:. tj c;-f 7 UJ'BR.INCB DOCUMBN'r NO. fPIJ. --------------

COMMENTS

'f A.s5~.. ~--rtrt:'.n

~I 3 -

frttr1,I

-/11' p,,-11?1,,*i*,I e..

~~{/I 1 ~""~I h,,..1J*s* fPr Jo AP.1.-tr y..,/,.,, e i'r

I~ fe. /),#I fh.it "~ )...., (!. /.5 If r b i*f votr ly l! ). O.!~ ~ *
f. 5cc..11"~n tf~ 7. I ~ fi'~~rl +r, pi'~v/,le ~~;;;1~~11t/1;, _.,.!" fo

,,,,_h-y fh c de.sr~n J?'J"'.?~*n fr>r b~ f/~,-y JC. ls (}

h".._~vt:r

  • f ht rr: I J 'f 0 ;4 ot,.. cf' / J r1 ft>r tt--i.Jv., t:. 7ro1.r,_-fJ) -/'Pr J..'20/'}htftt,-

P;l'iv/

~.$(} r!W'nJr/iP,;,/\\

fJ. T);e.

rt.1r1'~1*o;1.n

/~1-~I,, //Jk/

  • ffi'r ie.$J..(' r!. le: '1.e.' e.... G.. S-err t:.

l'I " f-

~ '1 rrr:. ~..f...

7. f3g. -;/ery e Ir~ r7 ~r :f" / 2: ih_:J s~""' fr/,.,,, '""~/""..,, *-f""l"'n.-

'.l r,, v.,. -I Ji

/op I 4't e.- *f, r f). ~-

(! '1n f l1'11A ()1N S De.

l~.t/.

RESOLUTION L--......---------~-+--..-:-:;--:----------1""~

Rev. 3

tap 1! of 1'1

. 1-11~'

DATR

,i..g lN3S

SENT BY:SARGE'iT & LUNDY 23E12 1-17-96 2:08PM SARGE:\\T & LL~DY~123-09560144-SS$SS$S:# 41 4 C q /~vi. /a l-/P~.E"::- J../, oo'l(Q)

/(e. //. ;L

/-U-/ae-h n, eh f 3 Daip Verification Cownt Res.olutiom - Calculartioll ES*'-004(2}

F07 e 5 e;f 7

1.

This section was revised to say that IEEE-485 msgmmends that the batteries be replaced. at 800./o of their capacity.

2.

This statement has been revised to address the electrolyte tcmpcl3turc rather than th~ ambient tcmperatnrc.

3.

This discussion has been revised to rcmovcthc phrase "significant transients". The discussion now says that the load on the charger is assumed constant. One must keep in mind that IEEE-946 does not define "normal load" with respect to charger sizing, therefore, there is some

fleXJl>ility in the term.
4.

This assumption has been revised to reflect that the value was arbitrarily selected.

S.

As5UIDption S.1 justifies the use of the assmned design margins. The additional load for future growth is not considered design margin. in the traditional sense. This additional load was considered at PSE&G' Iii request to s.ccoun1 for a specific modification.

6.

A UFSAR revision was issued during the time between preparation of the calculation and its issuance. The original calculation was marked up to reflect the current revision. The "hange does not impact the design input.

7.

The cakulation has been prepared to support the 125Vdc System in its present form. There is currcotly a design Change in progiess to replm: the batter:y chargers. Future growth margin c11n be consideJed as part of the modification process. The future growth value considered for batt.ety sizing was inlendcd for a spcci.fi.c modilication that added load to the vital inverters. The inverters are not included as part of the normal continuous load.

I FORM NC.DE-AP.ZZ-0010-2 Page 1 of 2 tv:/evz k~//on t:S-L-/. oo if {ex)

!<ev./-

/+/I.a c.. J; l'?>t: n f 3

Fu 7.e.

G o fl 7 qEHER.IC VERIFICATION CHECJCLIST REFERENCE DOCUMENT NUMBER/REVISION 1=5- '-/, 00'-/ {_Q)

/? e i..-,

L YES NO N/A WHERE FOUND COMMENTS PAGE NO.

(Y/N)

1. MERE DESIGN INPUTS CORRECTLY SELECTED AND l&I D

D Cl I I f'"?_:? es y

INCORPORATED INTO DESIGN?

t-AH<<c.h~e,.,f lf.2.

2.

ARE ASSlMPTIONS NECESSARY TO PERFORM THE 5ec..-lio;.. s-y DESIGN ACTIVITY ADEQUATELY DESCRIBED AND IBI D

D REASONABLE?

WHERE NECESSARY, ARE THE ASSUMPTIONS IDENTIFIED FOR SUBSEQUENT RE*VERIFICATION WHEN THE DETAILED DESIGN ACTIVITIES ARE COMPLETED?

D D

(gJ

3. ARE THE APPROPRIATE QUALITY AND QUALITY f!. t>vCr /7u7e-IV ASSURANCE REQUIREMENTS SPECIFIED?

~ D D

4.

ARE THE APPLICABLE CCX>ES, STANDARDS AND 5 e c /. 1' v r1 '

y REGULATORY REQUIREMENTS INCLUDING ISSUES AND ADDENDA PROPERLY IDENTIFIED AND ARE THEIR REeUIREMENTS FOR DESIGN MET?

lgj D

D

5.

HAVE APPLICABLE CONSTRUCTION AND OPERATING 5ec /./ohs 5 f o/

EXPERIENCE BEEN CONSIDERED?

IX!

D D

JV

6.

HAVE THE DESIGN JNTERFACE REQUIREMENTS BEEN

)e"c.. f t'r?n S" 3 f 'f SATISFIED?

IX!

D D

IV

7.

WAS.AN APPROPRIATE DESIGN METHCX> USED?

See-f 1*'711 7.

y lgj D

D

8. IS THE OUTPUT REASONABLE COMPARED TO INPUTS?

.Sec..f/o;. ~ f-

/V

~ D D

AH<<c.hn.o. f I

9.

ARE THE SPECIFIED PARTS, EQUIPMENT, AND PROCESSES SUITABLE FOR THE REQUIRED APPLICATION?

D D

jg]

10. ARE THE SPECIFIED MATERIALS COMPATIBLE WITH EACH OTHER AND THE DESIGN ENVIRONMENTAL CONDITIONS TO WHICH THE MATERIAL WILL BE EXPOSED?

D D

IBI

11. HAVE ADEQUATE MAINTENANCE FEATURES AND REQUIREMENTS BEEN SPECIFIED?

D D

[XI

12. ARE ACCESSIBILITY AND OTHER DESIGN PROVISIONS ADEQUATE FOR PERFORMANCE OF NEEDED MAINTENANCE AND REPAIR?

D D

IX!

Nuclear Common Page 16 of 17 Rev. 2


:-------------~

FORM NC.DE-AP.ZZ-0010-2 Page 2 of 2

('A/(' v. /,r. -f I(;,,_. £ 5 - '-/, t/Cl '-/ ( Q)

/?r.!..v. :2-A If ~c:.- h.n-i eh../- 3 P07 ::.

7 o-f 7 GENERIC VERIFICATION CHECKLIST REFERENCE DOCUMENT (CONTINUED)

NUMBER/REVISION

=r-

'-// 00 l/ ('Q)

I I?~"'* ;:z_

YES NO N/A WHERE FOUND COMMENTS PAGE NO.

(Y/N)

13. HAS ADEQUATE ACCESSIBILITY BEEN PROVIDED TO PERFORM THE IN-SERVICE INSPECTION EXPECTED TO BE REQUIRED DURING THE PLANT LIFE?

D 0

lgj

14. HAS THE DESIGN PROPERLY CONSIDERED RADIATION EXPOSURE TO THE PUBLIC AND PLANT PERSONNEL?

HAVE ALARA 0

0

~

CONSIDERATIONS BEEN ADDRESSED?

D 0

llil

15. ARE THE ACCEPTANCE CRITERIA INCORPORATED IN THE DESIGN DOCUMENTS SUFFICIENT TO ALLOJ VERIFICATION THAT s~c.--ho"' 7 DESIGN REQUIREMENTS HAVE BEEN SATISFACTORILY IV ACCOMPLISHED?

!Xl 0

D

16. HAS VERIFICATION OF THE ELECTRIC LOAD CONTROL PROGRAM CDE-TS.ZZ-2908(Q)] BEEN PERFORMED?

D 0

l&1

17. HAS THE EFFECT ON THE DIESEL GENERATOR LOAD SEQUENCE STUOY BEEN ANALYZED?

D D

~

18. HAVE ADEQUATE PRE-OPERATIONAL AND SUBSEQUENT PERIODIC TEST REQUIREMENTS BEEN APPROPRIATELY SPECIFIED?

D D

llil

19. ARE ADEQUATE HANDLING, STORAGE, CLEANING AND SHIPPING REQUIREMENTS SPECIFIED?

D D

~

20. ARE ADEQUATE IDENTIFICATION REQUIREMENTS SPECIFIED?

D D

~

21. ARE REQUIREMENTS FOR RECORD PREPARATION REVIE~,

oi I I f' q :;e.1 Al APPROVAL, RETENTION, ETC. ADEQUATELY SPECIFIED?

IX!

D D

Rev. 2 Page 17 of 17 Nuclear Common J'.