Requests Approval,Per Requirements of 10CFR50.55(a)(3),to Use ASME Code Case N-539, for Salem & Hope Creek Generating Stations
ML18101B079
Person / Time
Site: Salem, Hope Creek  
Issue date: 10/26/1995
From: Eric Simpson
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LR-N95165, NUDOCS 9511010206
Download: ML18101B079 (3)


Text

Public Service Electric and Gas

Company E. C. Simpson Public Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609-339-1700 Senior Vice President - Nuclear Engineering OCT 2 6 1995 LR-N95165 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

ASME CODE CASE N-539 SALEM GENERATING STATION UNIT NOS. 1 & 2 HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NOS. DPR-70, DPR-75 & NPF-57 DOCKET NOS. 50-272, 50-311 & 50-354 Public Service Electric and Gas Company (PSE&G) requests approval, in accordance with the requirements of 10CFR50.55a(a) (3), to use American Society Of Mechanical Engineers (ASME) Code Case N-539, "UNS N08367 (Cast Alloy CN-3MN) in Class 2 and 3 Valves,Section III, Division 1 11 (Copy Attached)_

for Salem Generating Station Unit Nos. 1 and 2 and Hope Creek Generating Station.

The use of this Code Case is not presently referenced in NRC Regulatory Guide 1.84, "Design and Fabrication Code Case Acceptability -

ASME Section III Division 1 11,

Revision 30 dated October, 1994.

Code Case N-539 provides the ANSI B16.34 requisite pressure-temperature ratings of the UNS N08367 materials, necessary for the use of this material in the construction of ASME Class 2 and 3 valves.

The UNS N08367 materials include SA-351 (Casting), SB-564 (Forging) and SB-688 (Plate).

These materials are ASME approved materials for Class 2 or 3 component construction, and have been incorporated for use in ASME Section III, Editions and Addenda and Code Cases that have been previously endorsed by the NRC.

However, prior to this code case, the UNS N08367 materials had never been assigned a pressure-temperature rating for specific use in valve construction.

The use of this material is desirable for valve construction because of its corrosion resistance properties.

Further, it is compatible with the piping materials that have been recently used in the Hope Creek and Salem Service Water System replacements.

The use of UNS N08367 materials in conjunction with the ANSI B16.34 pressure-temperature ratings per Code Case N-539 does not introduce any conditions that would compromise existing levels of safety or quality at either Salem or Hope Creek.

IZ,\\. Printed on

':ti Recycled Paper 9511010206 951026

~DR ADOCK 05000272 PDR

OCT 2 6 1995

' Document control Desk LR-N951.65 '~

2 Should you have any questions on this submittal, please contact us.

sincereuy, c;:,.//_

{(.}~~I~

Attachment (1) c Mr. T. T. Martin, Administrator - Region 1 U. s. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Mr. L. N. Olshan, Licensing Project Manager -

Salem U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Mail stop 14E21 Rockville, MD 20852 Mr. D. Jaffe, Licensing Project Manager -

Hope Creek U. s. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Mail Stop 14E21 Rockville, MD 20852 Mr. c. s. Marschall (X24)

USNRC Senior Resident Inspector Mr. R. Summers (X24)

USNRC Senior Resident Inspector Mr. Kent Tosch, Manager, IV NJ Department of Environmental Protection Division of Environmental Quality Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625 i

C&lle N-,39 UNS N08367 (Cast Alloy CN-3MN) in Class 2 and 3 Valves Section m, Division 1 l1f'luiry: Under what provisioru may solution annealed UNS N08367 (Cast Alloy CN-3MN) be uaed in Clua 2 and 3 Valves?

R~pfy: It la the opinion of the Committee that Class 2 and 3 val"t*e.s may be constructed from UNS N08367 (Cast Alloy CN-3MN) provided the following conditions u~ met:

I

1.

Pres.sure retaining materfala sh311 comply with one of the followJng specifications:

.Specltl catj ons SA-351 SB-'64 SB-688 Pro4u~ Form Caating11 For1inp Plate

~

CN-3MN UNS N08367 UNS N08367

2.

'The preuure-temperature ratings of B16.34-1988, Table 2-3.16 shall be used, e}tctpt that the mui.mum temperature shall not exceed 6SOF. All other applicable requiremtn~ of ASME/ANSI B16.34-1988 shall be met a.s requiffii by NCIND-3500.

3.

Welding qualifications shall be in accordance with Section IX. The material shall be considered P-No. 45.

4.

Forgings and plate.shall be heated to 202,F - 21SO P and shall be held for a sufficient time to heat the material to temperature, followed by quenchinr fn water or sfmHar rapid coollng by other means.

__ Ca.iltings s~~l! be heat treated at 2.1 OQP *.21.SOP for at least dtie *hour, followed by

--- quencliing 1n* water oi'slmI!ar*rapid cooling by other means. Heat treatment after forming or welding is not required. However, if heat treatment is applied, the solution* anne;iling treatment

.shall be repeated.

5.

All other requirements of Section ID, Division 1, ai; applicable, shall be met.

6.

This Case number s.hall be identifie.d on the C"Crtificate Holders' Data Report for the valve.