'I' e

PS~G Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038-0236 Nuclear Business Unit May 30, 1995 Chief George Caporale Bureau of Information Systems CN-029 Trenton, NJ 08625 NEW JERSEY DEPARTMENT OF ENVIRONMENTAL PROTECTION DISCHARGE MONITORING REPORT SALEM GENERATING STATION PERMIT NO. NJ0005622 Attached is a table of the results of tracer dye studies conducted to determine pump flow rates for the circulating water system as required by Part IV-B/C, Paragraph A.10 of NJPDES Permit No. NJ0005622.

These flow rates were used in calculating the discharge flow and facility heat values as reported in the April 1995 Discharge Monitoring Report.

If you have any questions on this information, please feel free to contact Scott Todd of the Salem Chemistry Department at (609) 339-2665.

WGB:pc Attachment (1) 9506150332 950530 PDR ADDCK 05000272 P

PDR very tru{l::f.yours, 1() 7,

~_Jb-J.___.

John C. Summers General Manager -

Salem Operations 95-2168 REV. 6/94

NJPDES Report April 1995

  • C Mr. Gerald M. Ransler - Executive Director USNRC - Document Control Desk Manager-Licensing & Regulations M. Vaskis D. Hurka Central Record Facility File RPC95-114

SALEM GENERATING STATION NJPDES PERMIT NO. NJ0005622 CIRCULATING WATER SYSTEM RESULTS OF TRACER DYE TESTS PUMP PURE DYE EFFLUENT OUTFALL PUMP NO.

DATE INJECTED (ml)

CONC. (ppb)

DSN FLOW (gpm) llA 3/15/95 16.07 0.18 481 157,754 llB 3/15/95 17.93 0.18 481 165,012 12A 3/15/95 14.48 0.19 482 164,781 12B 3/15/95 20.06 0.19 482 161,808 13A*

3/15/95 18.80 0.17 483 156,535 3/15/95 17.72 0.19 483 13B 3/15/95 12.32

0. 20 483 162,904 21A 3/14/95 12.02 0.17 484 164,173 21B 3/14/95 16.04 0.17 484 161,992 22A 3/14/95 16.16 0.17 485 153,361 22B 3/14/95 19.67 0.17 485 154,656 23A*

3/27/95 18.55 0.20 486 144,692 3/14/95 15.06 0.16 486 3/14/95 12.45 0.16 486 3/14/95 8.69 0.16 486 3/14/95 12.42 0.16 486 23B 3/14/95 18.80 0.17 486 168,156 TOTAL DYE INJECTED:

267.24 ml AVERAGE PUMP FLOW RATE:

159,652 gpm Multiple pump tests conducted due to dye injection and/or mechanical problems.

Results of pump retest are reported.