I UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 April 21, 1992 Docket Nos:
50-272/311 MEMORANDUM FOR:
Charles L. Miller, Director Project Directorate I-2 Division of Reactor Projects C/O FROM:
Faust Rosa, Chief Electrical Systems Branch Division of Systems Technology
SUBJECT:
ADEQUACY OF CONTAINMENT FAN COOLERS AT SALEM UNITS 1 AND 2 (TAC NOS~ M80443/M80444)
Plant Name:
Utility:
TAC NOS:
Operating License:
Project Manager:
Review Branch:
Review Status:
Salem Units 1 and 2 Public Service Electric and Gas Company M80443/M80444 OR J. Stone SELB/DST Complete Electrical Systems Branch (SELB) was requested to review the adequacy of containment fan cooler motors for their intended service.
The licensee performed an engineering analysis (Salem engineering analysis S-C-CBV-MEE-0527) to determine the BHP requirement of the containment fan coolers at different operating conditions.
SELB has completed its review of this analysis and has determined that the motors were adequately sized based on the following:
- 1)
Fan Motor name plate rating of 300/100 HP and Service Factor of 1.0
- 2)
BHP requirement during normal operation is 260-270 HP
- 3)
BHP requirement during accident condition is 85.4 HP
- 4)
Acceptability of the Salem engineering analysis by Plant system Branch (Refer to memorandum from C. E.
McCracken to Charles L. Miller dated December 31, 1991)
Contact:
Amar Pal, SELB/DST 504-2760 9205260241 920507 PDR ADOCK 05000272 p
- c. April 21, 1992 This concludes the SELB effort relative to TAC NOS. M80443 and M80444.
cc: A. Thadani J. stone Faust Rosa, Chief Electrical Systems Branch Division of Systems Technology