ML18096A701

From kanterella
Jump to navigation Jump to search
Submits SG Tube Plugging Rept in Support of 10th Refueling Outage.All Six Tubes Plugged Due to Imperfection Depths Greater than or Equal to 40% in Three Tubes & Three Tubes Plugged Due to Imperfection Depths Between 30% & 40%
ML18096A701
Person / Time
Site: Salem 
Issue date: 05/13/1992
From: Vondra C
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9205190006
Download: ML18096A701 (1)


Text

PSE<ie Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Salem Generating Station U. s. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Dear Sir:

SALEM GENERATING STATION LICENSE NO. DPR-70 DOCKET NO. 50-272 UNIT NO. 1 May 13, 1992 TECHNICAL SPECIFICATION SURVEILLANCE 4.4.5.5.a NOTIFICATION On May 4, 1992, Steam Generator (S/G) tube plugging, in support of the tenth refueling outage, was completed.

Attached is a list of the plugged tube locations.

In all, six (6) tubes were plugged of which:

three (3) tubes were plugged due to imperfection depths greater than or equal to 40% and three (3) tubes were plugged due to imperfection depths between 30 and 40%.

SIG Row/Column

% Depth 11 NONE 12 14/13 89 SIG Row/Column 13 14 6/4 15/46 43/34 44/59 35/76

% Depth 44 76 35 38 36 This notification is being made, within fifteen (15) days after tube plugging, as required by Technical Specification Surveillance 4.4.5.5.a.

ly yours, MJP:pc

~\\ I b The Energy Peopie

,,,--92-0519000'6 "920513 PDR ADOCK 05000272 p

PDR '

95-2189 (10M) 12-89