Stanley LaBruna "Jice President - Nuclear Operations Public Service Electric and Gas Company Public Service Electric and Gas Company P.o'. Box 236. Hancocks Bridge, NJ 08038 609-339-4800 June 13, 1989 NLR-N89112 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:
SUPPLEMENTAL RESPONSE TO NRC BULLETIN 88-10 SALEM AND HOPE CREEK GENERATING STATIONS DOCKET NOS.
~0-272, 50~311 AND 50-354 In a letter dated April 3, 1989, Public Service Electric and Gas Company (PSE&G) indicated that molded-case circuit breaker traceability investigations pursuant to NRC Bulletin 88-10 were continuing and that the results of these investigations along with the results of circuit breaker testing performed to date
. would be provided in June 1989.
The results of these efforts are presented below.
The total number of affected molded-case circuit breakers in stock is 389.
This number has changed from the 474 circuit breakers indicated in the April 3, 1989 letter, as further investigation revealed that 85 of the originally identified breakers were not used in safety-related applications due to administrative controls in place.
At this time 284 (73%) of the 389 circuit breakers have been determined to be traceable to the circuit breaker manufacturer (CBM).
A traceability determination was made for those circuit breakers received directly from the CBM or those circuit breakers received from a "Class 1 11 supplier.
Class 1 suppliers are those which operate under a 10CFR50 Appendix B - qualified QA program.
PSE&G has performed periodic QA audits of these suppliers to verify continuing adherence to these approved QA programs.
Of the 105 remaining circuit breakers, 17 are still undergoing a traceability documentation review.
The remaining 88 circuit breakers have been determined not to be traceable to the CBM and have been included in the testing program in accordance with NRC Bulletin 88-10, Attachment 1.
To date, 50 circuit breakers have been tested and the results are undergoing detailed engineering evaluation.
.. -r,.***,
- e.
Document Control Desk NLR-N89112*
2 is an information summary, prepared for those*
circuit breakers that could not be traced to the CBM in accordance with Action Item 1 (c)" of the subject bulletin.
This summary will be updated and transmitted with the final test results when the traceability reviews have been completed for the remaining 17 circuit breakers.
The PSE&G letter dated April 3, 1989 stated that we expected the traceability reviews to be completed by June 1, 1989.
PSE&G has not met this target date due to the amount of support required from sources external to the company.
As indicated above, the final results of PSE&Gs traceability reviews will be included with the final test results.
As discussed in our April 3, 1989 letter, affected molded case circuit breakers for which traceability could not be confirmed have been appropriately tagged to prevent their use in safety-related applications while investigation into their traceability continues.
Testing will continue until all non-traceable circuit breakers in stock have been tested.
The test population may increase as the remaining traceability investigations (17 circuit breakers) are completed.
It is anticipated that circuit breaker testing will
- be completed by September 1, 1989.
PSE&G will submit the final test results by September 29, 1989.
Of the 389 affected molded-case circuit breakers in stock, it should be noted that none have been traced to the suppliers identified in Bulletin 88-10 and Information Notice 88-46.
- If you have.any questions with regard to this transmittal, please do not hesitate to contact us.
sincerely, Attachment
I Document Control Desk NLR-N89112 C
Mr. J. c. Stone 3
Licensing Project Manager -
Salem Ms. K. Halvey Gibson Senior Resident Inspector -
Salem Mr. c. Y. Shiraki Licensing Project Manager -
Hope Creek Mr. G. w. Meyer Senior Resident Inspector -
Hope Creek Mr. w. T. Russell, Administrator Region I Mr. Kent Tosch, Chief New Jersey Department of Environmental Protection Division of Environmental Quality Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625
REF:
PSE&G letter NLR-N89112 STATE OF.NEW JERSEY SS.
COUNTY OF SALEM
)
- s. LaBruna, being duly sworn according to law.deposes and says:
I am Vice President - Nuclear Operations of Public Service Electric and Gas Company, and as such, I find the matters set forth in our letter dated June 13, 1989
, concerning the Salem Unit Nos. 1 and 2 and Hope Creek Generating Stations, are true to the best of my knowledge, information and belief.
I Subscrib~and Sworn t~re t~
dayof~
-~
me 1989 lARAINE Y. BEA.RO M Noto~ ~ublic of New Jersey y Comm1ss1on ExpiresMciy 1, 1991 My Commission expires on
- r-r::,)~-N8 9112 ATTACHMENT 1 NON-TRACEABLE MOLDED-CASE CIRCUIT BREAKERS IN STOCK AS OF 6/12/89 PO NUMBER STATION QUAN.
MANUFACTURER AMPS VOLTS POLES MODEL NUMBER VENDOR 9261IT HOPE CREEK 4
GENERAL ELECTRIC 15 600AC 3
THED1~601511L FRCMI ELECTRIC 9261IT HOPE CREEK 4
GENERAL ELECTRIC 25 600AC 3
THED13602511L FRCMI ELECTRIC 9261IT HOPE CREEK 2
GENERAL ELECTRIC 30 600AC 3
THED13603011L FRCMI ELECTRIC 9261IT HOPE CREEK GENERAL ELECTRIC 30 125DC,2ITAC 1
THED113030 FRCMI ELECTRIC 9381IT HOPE CREEK 5
GENERAL ELECTRIC 20 240AC 2
THQC212011L ARROtl ELECTRONICS 9381IT HOPE CREEK GENERAL ELECTRIC 600 240AC 3
TJ36FMD ARROtl ELECTRONICS 9381IT
' HOPE CREEK GENERAL ELECTRIC 80 600AC 3
THED136080 ARROtl ELECTRONICS 9381IT HOPE CREEK GENERAL ELECTRIC 400 250DC,600AC 2
THJK42640011L ARROtl ELECTRONICS 940452 HOPE CREEK 2
ITE 20 250DC,240AC 2
E22B020 CONSOLIDATED CONTROLS P2-194454 HOPE CREEK ITE 15 125DC I 120AC 1
E21B015 CVI INC.
P2-198534 HOPE CREEK ITE 30 240AC 3
E23B030 TELEMECANIQUE P1-115390 HOPE CREEK AIRPAX 2.5 480AC 3
PETRO CHEMICAL ASSOCIATES P1-115390 HOPE CREEK HEINEMANN 5
480AC.
3 CF3-G3-AB PETRO CHEMICAL ASSOCIATES 906474 SALEM 2
llESTI NG HOUSE 125 600AC 3
HFB3125 llESCO 886559 SALEM 4
llESTI NG HOUSE 100 250DC,600AC 2
HFB-2100 llESCO 861600 SALEM 3
WESTINGHOUSE 100 250DC,600AC 2
HFB-2100 llESCO 756344 SALEM GENERAL ELECJRIC 30
.250DC,240AC 2
TEB122030 Po.IELL APPARATUS SVC.
845110 SALEM 2
GENERAL ELECTRIC 30 250DC,240AC 2
TEB122030 Po.IELL APPARATUS SVC.
837108 SALEM 5
GENERAL ELECTRIC 15 600AC 2
TED126015 RESCO ELECTRIC SUPPLY P2-160734 SALEM 4
SQUARE D 15 120/240 1
QOB JONES ELECTRICAL SUPPLY P2-160734 SALEM 4
SQUARE D 20 120/240 QOB JONES ELECTRICAL SUPPLY P2-160734 SALEM 4
SQUARE D 30 120/240 QOB JONES ELECTRICAL SUPPLY 859747 SALEM 15 ITE 100 600AC 3
EF3B100 FRCMI ELECTRIC
. 837048 SALEM 2
GENERAL ELECTRIC 225 600AC 3
TFK236FOOO FRCMI ELECTRIC 575983 SALEM 2
HEINEMANN 1.5 65DC 2
AM2-B3-A HEINEMANN 729839 SALEM 3
HEINEMANN 2
50DC 2
AM2-B3-A HEINEMANN 575983 SALEM 1
HEINEMANN 0.5.
65DC 2
AM2-B3 HEINEMANN 912329 SALEM 3
HEINEMANN 5
250AC 2
JA2-A3-A ARROtl ELECTRONICS 673713 SALEM 2
HEINEMANN 5
250AC 2
AM1-A2-A GRAYBAR ELECT 912221 SALEM 2
HEINEMANN 7.5 50 2
AM2-B3 BALLOU 829791 SALEM HEINEMANN 1.5 50DC AM33 BAILEY METER 829791 SALEM 2
AIRPAX 1.5 65DC BAILEY METER 486982 SALEM 1
ITE 50 240AC,250DC 2
EE2-B050 ITE IMPERIAL