r-;:,.1.,-;;

I PS~G Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station Ellen Radow -

Chief Bureau of Permits Admin.

Division of Water Resources CN-029 Trenton, NJ 08625 Dear Ms.

Radow:

NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM DISCHARGE MONITORING REPORTS SALEM NUCLEAR GENERATING STATION PERMIT NO.

NJ0005622 October 11, 1985 Attached are the Discharge Monitoring Report forms for Salem Nuclear Generating Station containing the information as required in Permit No.

NJ0005622 for the month of September, 1985.

The information contained in this report presents the observed results required by the Environmental Protection Agency and the New Jersey Department of Environmental Protection, obtained in accordance with approved methods with respect to sampling, analysis, monitoring and methods of reporting.

The reporting of the data and the accuracy of the results reflect the working environment, design capabilities and reliability of the instrumentation.

Discharge sampling locations 482 and 485 are set up and used for ongoing entrainment studies.

This precludes any sampling activities.

Since all chemical treatments of or discharges to the circulating water system are common with at least one other discharge, those values are assumed to be identical.

This assumption is made for all identified parameters.

The columns labeled, "No. Ex.", in the enclosed Discharge Monitoring Report forms tabulate the number of observed results that were above or below, as appropriate, the limits::'contained the permit; the limits are reflected on the enclosed forms.

( ------ ---------

es 10--, ~--

i PDR c::40J~

\\

R ADoc;< N9J.9J1~

osooo:z7;z PDR i

The Energy People in

r-NJ PD ES Discharge Monitorin.

Reports 10/11/85 Exclusion explanations are included on an additional sheet..

PDB: slg Attachment C

Executive Director, DRBC Very truly yours,

~--;-*

t/5'ohn Trej~

Chemistry/Rad. Prot. Manager -

Salem Operations Director, USNRC Office of Nuclear Reactor Regulation Dr. Ric hard Baker Vice President -

Nuclear FI LE:

NPDES2. RPT

NJPDES Report Explanation of exclusions September 10/11/85 The following exclusions are included in the attached report and explained below.

Exclusions have not endangered nor significantly impacted health or the environment.

DMR NO.

FAG 48C 487A EXPLANATION Net Heat Release -

This is a calculated value based on assumed pump flow rates for two Unit operation and is subject to programatic errors.

Ammonia -

Current facility operating configuration is not conducive to ammonia removal. Increased removal rates are expected with the commencement of mixer instal-lation and operation.

BOD, Coli form -

Fecal, pH -

Atypical high flows, peaking during normal sample date, caused an upset resulting in the noted exceedances.