DEADLINE RE TURN DATE RECORDS FACILITY BRANCH Appendix XI 11 Intake Technologies and Practices
I I
I I
INTAKE TECHNOLOGIES AND PRACTICES SALEM GENERATING STATION 316(b) DEMONSTRATION APPENDIX XIII NPDES Permit No. NJ0005622 NRC Operating Licensing DPR-70 & DPR-75 NRC Docket Numbers 50-272 & 50-311 Public Service Electric and Gas Company 80 Park Plaza Newark, N.J.
07101 May 1984
PREFACE The Salem Generating Station 316(b) Demonstration summarizes the results of 15 years of environmental studies conducted by Public Service Elec-tric and Gas Company (PSE&G) and its consultants on the Delaware*River estuary.
Early studies responded to Nuclear Regulatory Commission requirements.
Later studies were conducted according to a plan approved by the U.S. Environmental Protection Agency--Region II. The "Salem Generating Station 316(b) Ecological Impact Assessment Plan-of-Study" listed nine fish species and two macroinvertebrate species as target species. It directed that in-depth studies be conducted for these species and that species-specific reports be prepared.
These reports are Appendixes II through XII of the Salem Generating Station 316(b)
Demonstration.
i
Salem 316(b) Demonstration:
Appendix XIII APPENDIX XIII:
INTAKE TECHNOLOGIES AND PRACTICES PREFACE CONTENTS XIII.l INTRODUCTION XIII.2
SUMMARY
XIII.3 XIII.4 XIII.5 XIII. 6 XIII.2.1 XIII.2.2 XIII.2.3 XIII.2.4 XIII.2.5 Cooling Water Systems Intake Location Intake Structure Design Features Intake Guidance and Diversion Technologies Intake and Cooling System Maintenance and Operation COOLING WATER SYSTEMS XIII.3.1 XIII.3.2 XIII.3.3 XIII.3.4 Open-Cycle Cooling Closed-Cycle Cooling Cooling Ponds or Lakes Cooling System Retrofits INTAKE LOCATION XIII.4.1 XIII.4.2 XIII.4.3 Shoreline Intake Structures Off shore Intake Structures Approach Channel Intake Structures INTAKE STRUCTURE DESIGN FEATURES XIII.5.1 Intake Velocity XIII.5.2 XIII.5.3 XIII.5.1.1 XIII.5.1.2 Intake Size Approach Velocity Through-Screen Velocity Intake Screen Design, Mesh Size, and Screen Material INTAKE GUIDANCE AND DIVERSION TECHNOLOGIES XIII.6.1 Behavioral Barriers XIII.6.1.1 XIII.6.1.2 XIII.6.1.3 XIII.6.1.4 Light Sound Velocity Gradients Air Bubble Screens ii Page i
ii XIII.1-1 XIII.2-1 XIII.2-1 XIII.2-1 XIII.2-1 XIII.2-2 XIII.2-2 XIII.3-1 XIII.3-1 XIII.3-1 XIII.3-2 XIII.3-3 XIII.4-1 XIII.4-1 XIII.4-1 XIII.4-3 XIII.5-1 XIII.5-1 XIII.5-1 XIII.5-2 XIII.5-2 XIII.5-3 XIII.6-1 XIII.6-1 XIII.6-1 XIII.6-2 XIII.6-2 XIII. 6-3
XIII. 7 XIII.8 Salem 316(b) Demonstration:
Appendix XIII XIII.6.1.5 XIII.6.1.6 XIII.6.1. 7 XIII.6.1.8 XIII.6.1.9 XIII.6.1.10 Electrical Barriers Chemicals Magnetic Barriers Chains and Cables Louvers Velocity _Cap with Relocated Offshore Intake XIII.6.2 Physical Barriers XIII.6.2.1 XIII.6.2.2 XIII.6.2.3 XIII.6.2.4 XIII. 6.2.5 XIII.6.2.6 XIII.6.2. 7 XIII.6.2.8 XIII.6.2.9 XIII.6.2.10 XIII.6.2.11 Rapid Sand Filters Porous Dike Radial-Well Collectors Conventional Stationary Mesh Screens, Perforated Plates, and Pipes Cylindrical Wedge-Wire Screens with Relocated Intake Structure Drum Screens Horizontal Traveling Screens Rotating Disc Screens Centerflow, or Passavant and Cogenel Traveling Screens Vertical Traveling Screens Other Physical Barriers XIII.6.3 Fish Collection, Removal, and Conveyance Systems XIII.6.3.1 XIII.6.3.2 XIII.6.3.3 XIII.6.3.4 XIII.6.3.5 Vertical Traveling Screen Fish Buckets and Accessories Fish-Return Conveyance Systems Fish-Pump Systems Fish Basket Collectors Fish By-Passes and Escape Channels INTAKE MAINTENANCE AND OPERATION XIII. 7.1 XIII.7.2 XIII. 7.3 XIII.7.4 XIII. 7.5 XIII. 7.6 CONCLUSION Dredging Reduc{ug Circulating Water Flow Curtailing Plant Operation Biofouling Procedures Modifying Cooling Water System Components Regulation of Thermal Elevations LITERATURE CITED iii Page XIII.6-3 XIII.6-4 XIII.6-4 XIII.6-4 XIII.6-5 XIII.6-6 XIII.6-7 XIII.6-8 XIII.6-8 XIII.6-11 XIII.6-12 XIII.6-12 XIII.6-15 XIII.6-16 XIII.6-16 XIII.6-17 XIII.6-19 XIII.6-20 XIII.6-20 XIII.6-21 XIII.6-23 XIII.6-24 XIII.6-25 XIII.6-26 XIII. 7-1 XIII. 7-1 XIII. 7-1 XIII. 7-2 XIII.7-3 XIII.7-3 XIII. 7-4 XIII.8-1
Number XIII.6-1 XIII.6-2 Salem 316(b) Demonstration:
Appendix XIII LIST OF TABLES:
APPENDIX XIII Title Impingement survival of juvenile white perch under various conventional vertical traveling screen operational modes and screenwash pressures at three Hudson River power plants during November and December 1976.
Initial and long-term impingement survival of young-of-the-year and yearling fish impinged on a continuo.usly rotating fine-mesh modified vertical traveling screen.
l..*
Number XIII.4-1 XIII.4-2 XIII.5-1 XIII.6-1 XIII.6-2 XIII.6-3 XIII.6-4 XIII.6-5 XIII.6-6 XIII.6-7 XIII.6-8 XIII.6-9 XIII. 6-10 Salem 316(b) Demonstration:
Appendix XIII LIST OF FIGURES:
APPENDIX XIII Title Plan view of a typical shoreline intake configuration.
Schematics of offshore intake.
Relationship between square mesh screen opening size required for 90 percent retention and length, for 12 species of fish.
Schematic representation of an offshore intake with velocity cap.
Intake structures using porous dike design concepts.
Characteristics of flat wedge-wire screen panels used in the TVA hydraulic test.
A design concept for cylindrical wedge-wire screens at power plant cooling water intakes.
Horizontal traveling screen.
Centerf low traveling screen.
Double-entry/single-exit screen.
Conventional vertical traveling screen.
Ristroph modified traveling screen with fish buckets, a modified spray system, and a sluiceway for.fish.
Probability of surviving impingement for young-of-the-year white perch and adult Atlantic tomcod collected at the Danskammer Point Plant.
Salem 316(b) Demonstration:
Appendix XIII APPENDIX XIII:
INTAKE TECHNOLOGIES AND PRACTICES XIII.!
INTRODUCTION As a consequence of enactment of Section 316(b) of the Clean Water Act (PL.92-500. and 95-217), a number of cooling water system intake technologies and operational and maintenance practices have been proposed or are currently in use in power plant cooling water systems to minimize adverse impacts to aquatic organisms.
These technologies can be generally categorized as involving (1) cooling system alterna-tives, (2) intake location alternatives in the source waterbody, (3) intake structure design features, (4) intake guidance and diversion technologies, (5) intake maintenance practices, or (6) operational methods (EPA 1976).
Operation of a cooling water intake structure may result in either entrainment or impingement of source water organisms.
Entrainment is the pumping of arganisms into and through a cooling water system.
Impingement occurs when aquatic organisms are caught, trapped, or held against the screens of a cooling water intake as a result of water withdrawal from the source water through the screening system.
Preced-ing these two types of events, organisms may be entrapped within the intake structure for varying periods depending on intake velocity rela-tive to swimming ability and the behavioral.characteristics of each species.
Organisms that do not escape the intake flow field eventually are entrained or impinged depending on their size.
One way to reduce cooling system effects on aquatic organisms is to reduce the probability of their encountering the intake, thus reducing the number of organisms entrained or impinged.
A second approach is to increase the survival rates among those organisms that are entrained or impinged.
The bio-logical and engineering considerations involved in selecting and imple-menting alternative technologies and practices to achieve these goals are discussed in this Appendix to the Salem 316(b) Demonstration.
An attempt has been made to identify alternatives that appear to be biologically effective in reducing losses of organisms, while incorpo-rating both demonstrated engineering feasibility and direct applica-bility to Salem's circulating water system intake, which already has been modified to employ some of the features discussed.
Intake designs that have not proven effective at other plants are also identified so that unsuccessful alternatives need not be given detailed site-specific intake evaluations.
Information has been assembled from published literature and reports, and from discussions with plant operators, design e~gineers, utility/regulatory personnel, and equipment vendors.
This review is general and does not consider all details of the present Salem intake design, operational characteristics, or specific population effects in determining what alternatives might constitute an economic-ally practical, biologically beneficial candidate for more detailed XIII.1-1
Salem 316(b) Demonstration:
Appendix XIII consideration.
Detailed site-specific criteria are applied to the most promising candidate intake alternatives in Section 8 of the Salem 316(b)
Demonstration.
XIII.1-2
Salem 316(b) Demonstration:
Appendix XIII XIII. 2
SUMMARY
XIII.2.1 COOLING WATER SYSTEMS Two principal types of cooling systems are employed currently in thermal power plants:
open-cycle (or "once-through_~*) and closed-cycle cooling.
Closed-cycle cooling systems require withdrawal of substantially smaller volumes of water from the source waterbody and have therefore been sug-gested as a means of reducing impingement and entrainment rates.
Use of closed-cycle cooling, however, can result in 100 percent mortality of entrained organisms, in contrast to lower mortality rates reported for many species entrained into once-through cooling systems.
Even though closed-cycle cooling systems withdraw a smaller volume of cooling water, they consume more water due to evaporative losses.
Less evapor-ation occurs with once-through systems which return withdrawn water to the source waterbody.
The effectiveness of closed-cycle cooling as an alternative to once-through cooling for reducing biological losses must be determined on a site-specific basis.
Closed-cycle cooling systems are very expensive to retrofit at existing open-cycle plants, and can impose a significant operating cost in the form of reduced thermal efficiency.
Once-through cooling systems are appropriate for sites having a reliable water supply of high volume, since such systems pass large quantities of water through the cooling '
system and return it to the source waterbody.
XIII.2.2 INTAKE LOCATION A cooling water intake structure may be located along the shoreline of a waterbody, submerged offshore, or recessed into the shoreline.
To minimize biological impact, a primary factor in siting an intake structure is to avoid areas of high fish and invertebrate population densities, such as spawning grounds and nursery areas.
This may affect the siting of the entire generating station.
XIII.2.3 INTAKE STRUCTURE DESIGN FEATURES The principal intake design parameters which determine biological effects are:
intake velocity intake screen design, mesh size, and screening material intake configuration and orientation Intake velocity design criteria include considerations of approach velocity and through-screen velocity.
Swimming performance capabilities of fish provide a biological basis for establishing approach velocity criteria.
Survival of impinged organisms is one factor to be considered in establishing through-screen velocity criteria. Engineering and bio-logical considerations for the design of intake screens and selection of screen mesh sizes and materials must be addressed.
Specific criteria for intake screen design must be developed on a site-specific basis.
The configuration of the intake structure should be designed to minimize XIII.2-1
Salem 316(b) Demonstration:
Appendix XIII the entrapment of organisms. Additionally, provisions for returning entrapped or impinged organisms to the source waterbody may be desirable to reduce biological losses associated with the intake structure.
XIII.2.4 INTAKE GUIDANCE AND DIVERSION TECHNOLOGIES Behavioral barriers are intended to cause a guidance or avoidance res-ponse to divert organisms into bypass channels, but, as detailed in Section XIII.6, they have not proven consistently effective in reduc-ing the impingement of fish or macroinvertebrates.
Sound, lights, and bubble curtains have not been shown to consistently increase fish avoid-ance of an intake structure.
Induction of velocity gradients and water-jet deflectors often cause sediment deposition or erosion, and also may trap organisms within intake structures.
Louvers and velocity caps rely on specific behavioral responses and swimming performance capabilities to be effective, and hence are of little or no value in protecting planktonic organisms.
Because of variability in response patterns between species and age-classes of fish, behavioral barriers are con-sidered appropriate only in cases where a single species of fish of relatively uniform size and age is of concern.
This circumstance does not apply at Salem station.
Physical barriers are designed tCl block the passage of entrained or entrapped organisms.
Some physical barriers rely on impinging the organisms, which are then transferred mechanically to a by-pass or return channel.
Some physical ba=riers are designed to act as both a physical and behavioral barrier to exclude organisms from a cooling system.
Recently, several physical barrier systems have been modified to include fine-mesh screens in an attempt to minimize the number of fish eggs and larvae entrained by cooling water systems.
In specific applications, fish conveyance and removal systems have proven effective. Factors such as intake structure configuration and design, the size and species of fish, and the behavioral response of the fish to various conditions encountered within an intake structure all affect the design and efficiency of a fish guidance and diversion system.
XIII.2.5 INTAKE AND COOLING SYSTEM MAINTENANCE AND OPERATION Dredging to remove accUm.ulated sediment from in front of and within an intake can help to ensure that design velocities are maintained and that velocity gradients are uniform.
Some cooling system or intake structure designs may heighten the need to use biofouling control agents such as chlorine.
The location and management of the biofouling control system can minimize the effects on entrained organisms.
Insufficient understanding of the role of shear forces, pressure regimes, and mechanical abrasion exists to permit recommendations of structural modifications to cooling system components (e.g.,
circulating water pumps) to reduce stresses on entrained organisms.
XIII.2-2
Salem 316(b) Demonstration:
Appendix XIII Reducing cooling water volume reduces the rates of entrainment and impingement but also results in losses in generation capacity and thermal transfer efficiency of the cooling system, and increased cool-ing water discharge temperatures (delta-T).
The increased delta-T and resulting thermal stress may substantially reduce the survival of entrained organisms, and may have effects in the waterbody.
Cooling system shutdown eliminates entrainment and impingement during critical periods but precludes electrical generation.
Curtailment for short time periods on a seasonal basis may be effective in reducing biological losses, but the costs of replacement power and reduced generation reliability throughout the service area must be considered.
XIII.2-3
Salem 316(b) Demonstration:
Appendix XIII XIII.3 COOLING WATER SYSTEMS There are two basic power plant cooling system designs:
open-cycle
("once-through) and closed-cycle cooling.
In open-cycle systems, water is pumped directly from the source waterbody to the condenser and subsequently discharged into the receiving waterbody.
In closed-cycle cooling systems, the cooling water is recirculated continuously between the condenser and a cooling tower, or cooling pond.
In an evaporative closed-cycle cooling system, water is withdrawn from the source water-body to make up for water lost during operation.
Blowdown containing sediments. and impurities within the make-up water is discharged back to the source waterbody.
The selection and design of a thermal power plant cooling system is dependent upon a number of factors, including water availability, engineering constraints, and regulatory limitations.
XI II. 3.1 OPEN-CYCLE ("ONCE-THROUGH") COOLING Open-cycle cooling may be feasible at power plant sites if a reliable water supply of sufficient volume is available.
Variations in water quality and suspended sediments generally do not significantly influence the feasibility of once-through cooling, but do affect its thermal efficiency and therefore the costs of electrical generation.
A large and reliable supply of water is available at Salem.
At full design flow, the cooling water system uses less than 2 percent of the average tidal annual flow rate past the site.
The zone of measur-able influence presently extends outward from the Salem intake 15-46 m into the Delaware River, which has a total width at this location of 4,000 m.
XIII.3.2 CLOSED-CYCLE ("EVAPORATIVE") COOLING Closed-cycle cooling decreases the volume of water withdrawn from a water source and thus reduces the numbers of phytoplankton, zoo-plankton, and ichthyoplankton entrained.
However, water consumption is increased due to evaporation.
For organisms that are entrained, 100 percent mortality usually results from exposure to increased tem-peratures, biocides, and mechanical abrasion.
Therefore, the effect-iveness of closed-cycle cooling in reducing entrainment and impingement losses as an alternative to once-through cooling must be determined 0n a site-specific basis.
Other factors which must be considered include the costs and electrical generation penalties associated with closed-cycle systems and the potential for adverse environmental side-effects (such as cooling tower drift, land use or space constraints, esthetic consideration, etc).
Evaporative closed-cycle systems have had widespread freshwater appli-cation in the United States where insufficient volumes of water are available for open-cycle cooling.
A survey of operating experience with saltwater closed-cycle cooling systems prepared for the Utility Water Act Group (Stone and Webster Engineering Corporation 1978) concluded that there are no known oper-ating or proposed electric generating facilities in the United States XIII.3-1
Salem 316(b) Demonstration:
Appendix XIII which use seawater (salinity 26-36 ppt) make-up in closed-cycle cooling systems.
The only power-generating facility in the world that uses seawater in cooling towers is the Fleetwood Power Station in England, a small peaking plant (three 32-MWe units) with a low capacity factor (Stone and Webster Engineering Corporation 1978).
The units are cooled by two natural draft cooling towers with a circulating water flow rate of 1.9 m3/sec (67 cfs) per unit. Salinity of the cooling water make-up at the Fleetwood Power Station typically ranges from 26 to 27 ppt.
The circulating water is normally concentrated 1.2-1.5 times. Opera-,
tional problems associated with corrosion and material deterioration have been reported.
There are approximately 25 power plants in the United States, ranging in capacity from 10 to 1,510 MWe and with cir-culating water rates of 4,900-540,000 gpm (0.3-34 m3/sec; 11-1,200 cfs),
that use brackish water (0.5-26 ppt) make-up in evaporative closed-cycle cooling systems.
The units at Salem would fall within this group if closed-cycle cooling systems were to be implemented at the site.
There are a number of additional factors that must be considered before designing or building a closed-cycle cooling system which will use brackish water.
These include preventing corrosion or degradation of cooling system components, air quality and terrestrial effects of salt deposition, and possibly further reduced thermal efficiency of the cooling system.
Dry closed-water-loop cooling systems are attractive as water-saving devices.
They are technically feasible, but are very costly and offer poorer plant performance than evaporative systems.
The California Energy Commission reports that, "effective heat transfer in dry cooling towers requires significantly more heat exchanger surface area than in wet cooling systems (closed-cyc;J..e).
Construction costs are therefore much higher *. Although dry cooling systems use essentially no water, they work less effectively the higher the air temperature" (Stamets 1977).
The annual peak electrical demand on the Pennsylvania/New Jersey/Maryland (PJM) Interconnection occurs during the hottest months of the year when such cooling would be least effective. Accordingly, dry closed-cycle cooling systems are not feasible for use at Salem.
A combination of wet and dry closed-cycle cooling is technologically possible.
Public Service Company of New Mexico faced a limited water allotment and has installed a wet/dry cooling tower of new design on its 500-MWe San Juan Unit No. 3.
The plant will soon become operational.
Cooling will be 70 percent dry (air) and 30 percent wet, resulting in roughly a 1,200 gpm (0.075 m3/sec; 2.7 cfs) maximum make-up rate compared to a wet tower rate of 4,400 gpm (0.28 m3/sec; 9.8 cfs)
(Rittenhouse 1979).
The value of the savings in water must be consid-ered in relation to the high capital costs of the wet/dry cooling tower as opposed to wet cooling towers.
A wet/dry system would not appear to have significant advantages for use at Salem.
XIII.3.3 COOLING PONDS OR LAKES The use of constructed ponds or lakes in conjunction with power plant cooling systems and intakes generally is chosen for locations where once-through water requirements cannot be met on a continuous basis by XIII.3-2
\\~-
Salem 316(b) Demonstration:
Appendix XIII the source water supply~ the discharge volume and heat would substan-tially alter the character of the receiving waterbody, or it is other-wise desirable to segregate the cooling water supply or discharges from waters designated for other uses.
In these cases, large impoundments are constructed to contain a sufficient volume of water and with a large enough surface area to receive the plant discharge and dissipate the heat to the atmosphere.
The flow in the impoundment is controlled such that heat loss cools the water so it may be discharged to a receiving waterbody or reused for condenser cooling.
Evaporative and seepage loss.or the portion of the volume discharged is routinely made up from the source water supply.
Creating a cooling pond for Salem is not considered an environmentally sound alternative, because several hundred acres of tidal marsh land would have to be excavated to supply the surface area necessary to dis-sipate the discharged heat.
Loss of this ecologically important land would not eliminate the intake screening requirement since biological communities would become established in the pond, resulting in the continued entrainment and impingement of organ.isms.
Therefore, the construction of a cooling pond to reduce water use from Delaware Bay is excluded from further consideration as an alternative intake technology.
XIII.3.4 COOLING SYSTEM RETROFITS The feasibility of retr,of itting a once-through cooling system at an existing generating station with a closed-cycle cooling system requires extensive investigation.
Since the cooling system is a major and integral part of the station design, its proposed change would require careful examination of overlapping operational, environmental, and economic considerations, and could be more complex than the design of a new facility.
Operational considerations include the loss of electrical generation resulting from increased cooling system power demands, reduced thermal performance, and more stringent operating requirements; a reduction in the service life of system components; generation loss during conver-sion; and reduced plant reliability.
Economic factors include the large capital costs for cooling system conversion, plant performance penalties, increased operation and maintenance costs, higher site-related ~osts, and costs associated with the effect on system relia-bility of reduced generating capacity of the modified unit(s).
Environmental effects of closed-cycle cooling may include air quality effects of cooling tower drift, a visible plume, salt deposition, increased land-use needs, and esthetic considerations.
A complete discussion of this alternative is included in Section 8.10 of the Demonstration.
XIII.3-3
Salem 316(b) Demonstration:
Appendix XIII XIII.4 INTAKE LOCATION Each source of cooling water has unique characteristics which affect the location, design, and operation of intake structures.
Site selection involves consideration of the potential environmental impact and the location of suitable waterbodies to provide cooling water.
Locating a cooling water intake structure to avoid areas of high fish and invertebrate population densities is desirable.
This requires consideration of both the type of waterbody (e.g., lake, river, bay, open ocean) and the location of the intake structure within it (onshore or offshore).
The most favorable intake locations are in areas of low biological value (EPA 1977).
Few, if any, intake locations are com-pletely free of entrainable and impingeable organisms.
A cooling water intake in a waterbody may be located in one of three basic orientations with respect to the shoreline:
(1) at the shoreline, with the intake circulating pump well and screens combined into a single structure, (2) off shore, with the inlet and screenwell-pump well sepa-rated by some distance and connected through an enclosed conduit, and (3) inland, with an approach channel to divert cooling water from the source waterbody to the intake screens (a "recessed intake"). All three basic intake locations are used currently in the. United States.
The suitability of a particular intake structure locatiou is partly depen-dent on the distribution of fish populations within the source water (EPA 1977-).
XIII.4.1 SHORELINE INTAKE STRUCTURES Shoreline intake structures similar to that shown in Figure XIII.4-1 are used commonly to supply cooling water to power plants located on lakes, rivers, estuaries, and bays.
Lateral fish escapes between the bar racks and traveling screens are generally considered to be a desirable feature of.shoreline intake structures.
Low approach velocities and cooling water system transit times,.and minimization of turbulence are other desired features of shoreline intakes.
Locating a shoreline intake requires consideration of the vertical and horizontal distributions of aquatic organisms to avoid siting the intake in an area of high abundance.
Consideration of the hydrology of the-area is important to minimize recirculation and allow for variations in water level.
Sediment deposition and debris accumulation along shorelines also have to be considered.
The existing shoreline intake structure at Salem has many design features considered state-of-the-art for once-through cooling water systems (EPA 1976). It is considered the best of these technologies for minimizing biological losses.
XIII.4.2 OFFSHORE INTAKE STRUCTURES Offshore intake structures similar to that shown in Figure XIII.4-2 can be used to supply cooling water to power plants located on large lakes and on beach zones along the coasts of oceans.
Offshore intakes allow removal of cooler subsurface water in waterbodies that are vertically XIII.4-1
Salem 316(b) Demonstration:
Appendix XIII stratified and isolation of the cooling water intake from the discharge to minimize thermal recirculation.
They avoid disruption of littoral drift of beach sand and can be used where the topography prohibits use of a shoreline intake structure such as on a high energy shoreline.
Offshore intake structures provide more flexibility in selecting an intake location than is available for a shoreline intake, but the cost is substantially higher.
Locating an off shore intake structure requires consideration of the spatial distribution of aquatic organisms, vertical stratification of water temperature, and the hydrological patterns of the area.
Sedi-mentation, biofouling control, fish removal and return, and possible obstruction of navigable waters must be addressed in the design and location of offshore intakes.
Use of offshore intake structures requires an enclosed conduit to convey the cooling water to the power plant, and an onshore screenwell.
This design can result in a zone of fish entrapment between the off shore intake structure and the intake screens.
Attempts to alleviate the entrapment of fish within the int~ke have focused on preventing the entry of fish into the intake and on developing removal systems to return entrapped fish to the waterbody.
One method used to reduce entry of fish into. the intake inclvdes a velocity cap that eliminates vertical flows into the intake entrance in favor of horizontal flows.
Alternative methods of reducing entry of fish into offshore intake structures include use of infiltration galleries, stationary fine-mesh screens, or traveling screens (caisson intake design) at the point of water withdrawal.
These alternatives, and also fish removal and return systems, are discussed in later sections.
General recommendations for the location of offshore intake structures are summarized as follows:
- 1.
Avoid locating the intake in areas that are highly productive or have high population densities of fish and shellfish.
- 2.
Locate the intake in an area that will minimize the recirculation of cooling water, entrained organisms, and debris.
- 3.
Base design intake velocities on the swimming perform-ance capabilities and behavioral response of resident and migratory fishes as well as engineering constraints.
- 4.
Include provisions to preclude entry into or to remove organisms from the intake structure.
- 5.
Locate the intake where it will not impede navigation, will not be breached by ice flows, and will not be clogged by debris or formation of frazil ice.
XIII.4-2
Salem 316(b) Demonstration:
Appendix XIII
- 6.
Locate the intake where sediment movement and accumulation will not impede its function.
Conditions at Salem not conducive to offshore intake structures include high sediment accretion; high t~rbidity and detritus load; absence of appreciable temperature or organism stratification in the relatively shallow, well-mixed Delaware River waters; potential for clogging by formation of frazil ice subject to ice flow damage due to shallow water depth, and inaccessibility for maintenance to assure reliability of flow to the power stations, especially during winter conditions.
XIII.4.3 APPROACH CHANNEL INTAKE STRUCTURES Approach channel intake structures (recessed intakes or canals) are used to provide a protected area for intake screens, to separate the intake and discharge locations to-minimize thermal recirculation, or for other engineering reasons.
Such a system generally consists of an approach channel conveying water some distance from the shoreline to an intake structure, in either an enclosed conduit or an open canal.
One main disadvantage of recessed intakes is the potential for fish to become entrapped in the confined conduit or canal.
As with offshore intakes, these organisms may become stressed or fatigued, and eventually may be impinged.
Open approach channels generally have lower water velocities than do enclosed intake conduits; therefore they offer the possibility of greater behavioral avoidance and may reduce the entrapment of organisms.
In general, the design of intake structures which utilize confined or enclosed conduits should be avoided in proposed installations whenever an alternative intake configuration can be used.
Because retrofitting an approach channel intake at Salem could not be expected to produce any biological benefit, would be infeasible.from an engineering' standpoint given the nature of the site, and would be extremely costly even if it were feasible, this alternative will not be considered further.
XIII.4-3
Shoreline Public Service Electric and Gas Company Salem 316(b) Demonstration Bar racks Feet 0
5 0,
Metmrs 10 15
~
I 2
l '
.5 e
Plan View of a Typical Shoreline Intake Configuration Figure Xlll.4-1 J
~--Short line*
Intake 6
1ou~ -
_ =.-1}-
- - --.JL WATER SOURCE z __ z._ __ --
z __ '!Z.. __ --
z WATER Intake Pipe SOURCE Velocity Cap Public Service Electric and Gas Company Salem 316(b) Demont.~ration Trash Bars PLAN i !
SECTION Schematic~ of Offshore Intake Figure Xlll.4-2
Salem 316(b) Demonstration:
Appendix XIII XIII.5 INTAKE STRUCTURE DESIGN FEATURES In addition to proper intake location, the principal design features that influence organism losses are (1) intake velocities; (2) intake screen design, mesh size, and screen material; (3) intake configuration; and (4) fish return system (Kerr 1953).
A brief discussion of intake velocity and intake screen design follows.
A discussion of intake configuration is presented in Appendix Section XIII.2.3.
Fish return systems are described in Appendix Section XIII.6.3.
XIII.5.1 INTAKE VELOCITY Intake velocities as measured at two locations have received wide bio-logical attention:
the approach velocity of water entering the intake (generally in front of the bar rack structure), and the through-screen velocity.
To reduce impingement, the approach velocities should be chosen, in part, based on the swinr:ning performance of fishes present in the vicinity of the intake.
Through-screen velocity should be chosen, in part, based on the relationship b~tween velocity and survival of impinged organisms.
These velocities are primarily a function of the volume of water passing through the cooling system, and of the size of the intake.
XIII.5.1.1 Approach Velocity The species of fish t6 be protected, their susceptibility to entrapment and subsequent impingement at each life stage, and environmental param-eters such as water temperature, salinity, illumination, and dissolved oxygen concentration all influence the effect of approach velocity.
Extensive studies of fish swimming capabilities have been done on a variety of species by a number of researchers.
It is difficult, however, to correlate their observations and establish highly accurate approach velocity design criteria for swimming ability because of vari-ations, inconsistencies, or applicability of study results regarding pretest conditions, experimental design, physiological *conditions, and environmental considerations that may have been established for specific site characteristics.
Approach velocity design criteria typically range below 1.0 fps for shoreline intake structures (EPA 1976) and from 1.5 to 2.5 fps for offshore velocity cap intake structures (Moss et al. 1981).
An intake structure design generally should allow for an essentially uniform velocity profile across the entrance to the intake.
In addition to biological considerations, the approach velocity for any intake struc-ture is dependent on engineering constraints associated with the intake design and configuration, hydrology, and water quality of the source waterbody--all of which must be determined on a site-specific basis.
Dredging to remove sediment deposits from an existing intake structure may result in reduced approach velocities if resedimentation is not rapid.
Routine maintenance of the bar racks and intake entrance area to remove accumulated debris and obstructions helps to assure that intake operation is within the range of design parameters establisherl for the specific intake structure.
XIII.5-1
Salem 316(b) Dem~nstration: Appendix XIII XIII.5.1.2 Through-Screen Velocity Studies on the survival of impinged fishes have been conducted by Bibko et al. (1974), Prentice and Ossiander (1974), Landry and Strawn (1974),
King et al. (1978), and many others.
(See Oak Ridge National Laboratory and Atomic Industrial Forum, Inc. [1979] for an extensive review.)
Findings of these studies indicate that, in addition to being affected by through-screen velocity, impingement survival is a function of the species, size, and life stage of impinged organisms; the season in terms of changing salinity and water temperature; spraywash pressure; and the duration of impingement.
As a result of the number of inter-acting factors which influence impingement mortality, it is difficult to isolate the contribution of through-screen velocity.
Through-screen velocities at intakes of U.S. utilities typically range from 15-46 cm/sec (0.5-1.S fps) for vertical traveling screen intake structures.
As the available open area: for water to pass through the intake screen mesh decreases, the through-screen velocity increases.
Establishing appropriate through-screen velocity and impingement dura-tion relationships ~s essential if a fine-mesh intake screen is being considered to remove fish eggs and larvae from the cooling water (Tomljanovich et al. 1978).
Data necessary to establish through-screen velocities based on ;.mpingement survival are presently not available for most fish.
Data which are available on the relationship between impingement survival, duration of impingement, and. through-screen velocity are, in many cases, inconclusive and do not provide a reliable basis for establishing biological design criteria for through-scre_en velocity for a broad variety of fish species and life stages.
Techniques which can be used to lower or achieve uniform approach and intake velocities include dredging in front of the intake (Appendix Section XIII.7.1), reducing cooling water flow volumes (Appendix Section XIII.7.2), and physical modification of the intake structure such as increasing its size or changing its shape (Appendix Section XIII.5.2).
XIII.5.2 INTAKE SIZE The size of an intake for a power plant site is generally determined by the requirements for water flow to the condensers, the size and con-figuration specifications, the cooling water pumps, and provisions for maintenance of individual intake wells while allowing continued plant operation.
The dimensions and engineering limitations of commercially available intake screening units and economic constraints of construc-tion and operation maintenance affect the design and dimensions of the intake facility and cross-sectional opening for water supply.
The water depth and the width of each.intake well define the area through which circulating water is drawn by the cooling water pump(s).
The capacity of the circulating pump and the area of the approach opening define the average approach velocity, which is generally lower than the through-screen velocity by virtue of the portion of the open area occupied by the screenmesh and intake screen support structures.
Both the approach and through-screen velocity can be reduced if the open area for each circulating pump is increased while flows remain constant.
XIII.5-2
Salem 316(b) Demonstration:
Appendix XIII Although costs for construction, lo.st power generation, and increased equipment operation and maintenance are substantial for retrofitting an enlarged intake, certain biological benefits may result.
Lower velocities could reduce the potential for impingement of some organisms.
This might be accompanied by reduced mortality among those impinged due to lower through-screen velocity pressure.
Since the potential benefit of reduced impingement mortality is dependent on organism size, swimming ability, and physiological state on a species-specific basis, this alternative will be explored further in Sections 8.3, 8.7, and 8.11 of the Demonstration for those target species impinged at Salem.
XIII.5.3 INTAKE SCREEN. DESIGN, MESH SIZE, AND SCREEN MATERIAL A variety of intake screen designs are available commercially for use in.cooling-water intake structures.
(Appendix Section XIII.6 includes a review of intake screening devices.)
The major engine.ering and biological design requirements for an intake screen include:
- 1.
Sufficient area to accommodate the design cooling water flow and maintain through-screen velocities within the design parameter limits
- 2.
Efficient removai of debris that would otherwise clog the condenser s_ystem
- 3.
A mesh configuration and texture to ensure reliable cleaning and an adequate supply of cooling water
- 4. Ability to minimize abrasfon or suffocation of organisms during impingement on screen surf aces Designing an intake screen for a specific site requires knowledge of the cooling system, the source waterbody (including sediment and debris loads), and *the species and size of organisms to be protected.
No sin-gle intake screen can be identified that would be best for all sites.
Intake screen mesh size has historically been approximately 50 percent of the condenser tube diameter.
As a result, the majority of power plant cooling systems~ which are designed with 22.2-mm (7/8-in.) diam-eter condenser tubes, have 9.5-mm (3/8-in.) square woven-wire mesh intake screens.
Recently, increased emphasis has been placed on deter-mining screen mesh sizes according to the size of organisms susceptible to entrainment, and whether those organisms and life stages involved are better able to withstand impingement stresses or the stresses associated with entrainment.
The length of fish larvae retained by screen meshes of various sizes is presented in Figure XIII.5-1.
Screen mesh with 0.5-mm (0.02-in.)
openings is available commercially and will retain the majority of egg and larval fishes present in most source waterbodies.
However, before selecting a specific mesh size, it is important to consider the relative survival of impinged versus entrained individuals of each of the impor-tant species involved~ Tomljanovich et al. (1978) present a detailed discussion of experimental studies conducted under laboratory conditions XIII.5-3
Salem 316(b) Demonstration:
Appendix XIII to determine the feasibility of protecting larval fish at water intakes using fine-mesh screening. Additional considerations in selecting a screen mesh size include debris loading and screen clogging, available open area and through-screen velocity, and screen reliability under site-specific operating conditions.
Screen mesh configurations currently available include square mesh woven-wire, rectangular slot configurations using woven wire, and horizontal slot configurations using a welded wedge-wire design.
Each is available in a variety of mesh sizes.
Investigations are proceeding (e.g., Cook 1978; Heuer and Tomljanovich 1978; Walker and Kamata 1979) to determine the advantages and disadvantages of the various conf igura-tions.
Insufficient data are currently available to conclude that one among the available intake screen mesh configurations_ is superior.
Intake screens are *available in a variety of materials, including poly-ester, nylon, Monel, and stainless steel.
The appropriateness of a material depends on the screen mesh size and configuration and on the desired durability of the screen.
Polyester and nylon is used where a fine-mesh screen (0.05-1.5 mm; 0.02-0.06 in.) is desired and when screen mesh is expected to be altered seasonally.
Stainless steel is used where durability in a corrosive environment such ~s saltwater is needed.
Monel is used extensively in both fresh-and sal::.water environments, but requires greater maintenance and more frequent re11lacement than stain-less steel. Capital c_ost and replacement cost must also be considered in selecting screening material.
No comparative studies are available that indicate how the screen material alone determines the survival of impinged organisms.
More detailed consideration of alternative screen-ing materials is provided in Section 8.4 (Small Mesh Screens) of the Demonstration.
XIII.5-4
5.0 I\\
4.0
'E i
C>
c *c:., a.
3.0 0
c.,
e!
~
.c :c 2.0 e!..
~
g 1.0 Public Service Electric and Gas Company I
5 Salem 316(b) Demonstration
~........ --.. -.---------~-
10 I
15 I
20 Length of Fish (mm)
I 25 I
30 I
35 40 Relationship Between Square Mesh Screen Opening Size Required for 90 Percent Retention and Length, for 12 Species of Fish. (Data from Erkkila et al. 1950; Karr 1953.
Clay 1961; Prentice and Osslander 1974; Fisher 1978; Tomljanovich et al. 1978)
Figure XIII.5-1
I I Salem 316(b) Demonstration:
Appendix XIII XIII.6 INTAKE GUIDANCE AND DIVERSION TECHNOLOGIES XIII.6.1 BEHAVIORAL BARRIERS Various types of stimuli, such as light, sound, velocity gradients, electric currents, and chemicals, have been tested to deter fish from entering cooling water intakes.
Louvers and velocity caps also have been used to guide fish away from intakes.
Because these behavioral barriers rely on the ability of an organism to respond to a stimulus, they are of little or no value in protecting planktonic organisms.
In addition, the behavioral response of fish to artificial stimuli varies among species and also within a species because of differences in age or physiological state (Sonnichsen 1975).
As a result of the variability in responses to a stimulus, behavioral barriers are considered to be most appropriate in those cases where a single species of fish of rela-tively uniform size and age is of concern.
The primary application of most behavioral barriers has been in addition to, or in combination with, conventional intake systems (physical bar-riers) on either an intermittent or continuous basis.
Many behavioral barriers-have not been subjected to rigorous testing under field condi-tions, so conclusions as to their effectiveness have been drawn, where possible, from laboratory studies.
XIII.6.1.1 Light Available data on the effectiveness of light as a behavioral barrier are contradictory.
In some tests, fish are attracted to light, whereas fish are repelled by it in others.
Intense illumination was charac-terized by Bibko et al. (1974) as a passive deterrent for striped bass, only temporarily deterring fish passage under experimental conditions.
Fields (1966) reported that the avoidance response of salmonids to arti-ficial light varied, depending on the light adaptation of the species, water clarity, and flow conditions.
Constant light was reported by Fields to be more effective than interrupted or flashing light for guid-ing young salmon.
Even for species that are repelled by light, adapta-tion to light intensity substantially decreases the guidance efficiency of light barriers.
More recent studies by Patrick and Vascotto (1981) showed that under experimental conditions strobe light in the visible range (400-750 nm) was effective in repelling both alewife (Alosa pseudoharengus) and gizzard shad (Dorosoma cepedianum) in current velocities from 0.15 to 0.32 m/sec.
The deterrent capabilities were enhanced when the strobe was used in conjunction with a hanging chain barrier. Attraction of alewife to filtered mercury vapor light was suggestive of its potential use in guidance systems for that species.
Tests have not been conducted at opera~ing intakes so general responses of a variety of fish species is not known.
In addition, light can not provide an effective barrier during the daytime or in highly turbid water such as prevail at Salem.
Thus, light barriers are not currently considered to be an effective method of reducing the numbers of organisms entrained or impinged and are not considered further.
XIII.6-1
Salem 316(b) Demonstration:
Appendix XIII XIII.6.1.2 Sound Although fishes are initially frightened by sound barriers, tests con-ducted under laboratory conditions and at power plant intakes indicate that they rapidly become habituated to sound stimuli, rendering the barrier ineffective.
Sonic techniques for repelling fish from industrial water intake struc-tures have been studied by Moore and Newman (1956), Burner and Moore (1962), VanDerwalker (1964), and Trefethen (1968).
Moulton and Backus (1955) have reviewed the *literature regarding the guidance efficiency of sonic barriers.
In general, maximum avoidance has been observed for low-frequency, high-intensity sound, but variation in hearing ability among species and high-level background noise leads to poor repeatability of the behavioral response of fish to sonic barriers.
Burner and Moore (1962) reported that the behavioral response to sound frequency or intensity was insufficient to be effective in guiding young salmonids to safe passage around dams and diversions.
The Virginia Electric and Power Company (Vepco) attempted to use relatively high-intensity, multi-frequency sound to repel fish from power plant intakes (White 1976, personal communication).
It concluded that, although sound was par-tially effective, sound alone was inadequate for repelling* fish from the cooling water intake, because of the diversity of species, the diversity of sizes of fish encountered, and the diversity of behavioral patterns.
An underwater pneumatic impact device (popper) was tested as a sonic barrier at a power plant intake structure by Schuler and Larson (1975).
They concluded that the effective range of sonic device tested was limited to 5-10 ft in reducing the numbers present.
On the basis of these results from field and laboratory studies, no further consid-eration of sonic barriers at Salem is warranted.
XIII.6.1.3 Velocity Gradients Flow acceleration barriers produce an increase in the approach velocity over a relatively short distance by use of wedges in approach channels.
Their use within an intake structure would require a confined approach channel to the intake structure and relatively high approach velocities.
This combination is expected to result in*a condition which would entrain and entrap fish and would require effective guidance of diverted organisms into a by-pass system.
Further, this combination may also lead to the establishment of a resident predator population. -
Kerr (1953), Clay (1961), Bates (1964), Bates and VanDerwalker (1964),
Niggol (1964), and Prentice (1966) discussed flow acceleration or deceleration barriers for guiding or deflecting fishes.
Bates and VanDerwalker reported a 70 percent diversion efficiency for an experi-mental water-jet deflector at an approach velocity of 76 cm/sec (2.5 fps).
High diversion efficiencies (81 percent) have been reported by Prentice and Ossiander (1974) for experimental vertical flow accelera-tors oriented at a 200 deflection angle for channel velocities ranging XIII.6-2
I I
I Salem 316(b) Demonstration:
Appendix XIII from 37 to 73 cm/sec (1.2-2.4 fps).
Experimental horizontal flow accelerators had an average deflection efficiency of 56 percent at channel velocities from 46 to 70 cm/sec (1.5-2.3 fps) (Prentice and Ossiander 1974).
No differences in diversion efficiency was observed for tests conducted during the day and night.
Blinded fish, tested by Gerold and Niggol (1964), were guided by flow acceleration barriers with diversion efficiencies comparable to those for normal fish.
Because. they require approach channels with high velocities (resulting in entrainment and entrapment), no application of velocity gradients for diverting fish from power plant intake structures has been tested.
Velocity gradients currently are not a reliable technique for reducing entrainment or impingement at power plant intakes and are not suitable for further consideration at Salem.
XIII.6.1.4 Air-Bubble Screens Air-bubble screens generally are unsuccessful at consistently diverting fish (Brett and MacKinnon 1953; Fields 1966; Mayo 1974).
However, sev-eral cases have been reported where partial success was observed.
Bibko et al. (1974) reported that striped bass would not actively pass through an air-bubble screen at 4.5 or 11.lOC (40 or 520F), but were found to drift passivelv through the screens when the water temperature was a.soc
.(330F).
Striped bass were found to pass through an air-bubble screen at all test temperatures if openings 5.2 cm (2 in.) or greater were allowed in the screen.
Gizzard shad would not pass through an air-bubble screen at water temperatures *of 11.1oc (520F), but were not deterred at o.soc (33°F) (Bibko et al. 1974).
Bates and VanDerwalker (1964), studying juvenile migrant salmon, reported that air-bubble screens produced diversion efficiencies up to 95 percent during daylight, but declined to 28 percent at night and were not improved by artificial lighting.
Alevras (1974) observed that an air-bubble screen at the Indian Point Power Station on the Hudson River did not appear to repel fish during the daytime, and his preliminary data indicated that the air-bubble screen may attract fish to *the intake at night.
Because of the variability in response among species, poor effectiveness at night and in turbid water, and lack of success in field applications, air-bubble screens are not an effective method of reducing either entrainment or impingement and will not be examined further for use at Salem.
XIII.6.1.5 Electrical Barriers Electrical barriers have been used in fresh water to divert fishes from several small power plants, dams, irrigation canals, and municipal water supply systems with variable success.
Because of low electrical resis-tance, no application of electrical fish barriers has been made. in salt or brackish waters.
Holmes (1948) discussed the history, developmental problems, and practical applications of electrical techniques for fish diversion.
Applegate et al. (1954) reviewed the literature related to the use of electric fish screens.
XIII.6-3
Salem 316(b) Demonstration:
Appendix XIII Pugh (1962), Pugh et al. (1964), and Elliott (1970) reported that pulsed current was most effective in terms of guidance, diversion, and power requirements.
The behavioral reaction of fishes to an electric field are:
(1) avoidance, (2) electrotaxis, and (3) electronarcosis leading to paralysis and eventual dea,:th (Applegate et al. 1954; Elliott 1970; Maxwell 1973).
In general, the required current density and resulting behavioral response varies among species and sizes of fish (Pugh 1962; Pugh et al. 1964).
Trefethen (1955) reported 68 percent guidance efficiency of electric barriers in large scale laboratory experiments using fingerling salmon.
Efficiency decreases as water velocity exceeds 15 cm/sec (0.5 fps) (Pugh 1962; Pugh et al. 1964).
Maxwell (1973) reported variable success of electric barriers used at small freshwater intakes, usually with resi-dent rather than migrating fish.
Electrical barriers are most effective at intake structures where the impingement of only a few species of relatively uniform size is of concern.
At intakes such as Salem's, where a variety of species and sizes of fish are encountered, or at intakes sited in marine or estuarine waters, electrical barriers are not effective in minimizing entrainment (EPA 1976). Accordingly, they will not be examined further for application at.Salem.
XIII.6.1.6 Chemicals A barrier consisting of a fish-repelling chemical, discharged near the entrance of an intake structure, may be used to discourage the entry of fish into the intake. Fish-repelling chemicals are available, but no large-scale testing h~s been conducted.
Chemical barriers would be of little practical value at Salem because of the large volumes of cooling water involved and the adverse effect of the discharge of fish-repelling chemicals on nontarget organisms inhabiting the receiving waterbody.
Accordingly, they will not be examined for further application at Salem.
XIII.6.1.7 Magnetic Barriers Magnetic fields have been examined as a potential method of guiding juvenile salmonids past water diversions (Cannon et al. 1979).
Sal-monids did not respond to changes in magnetic fields under experimental conditions.
No tests have been conducted to examine the effectiveness of magnetic barriers at power plant intake structures.
In the absence of any information suggesting the applicability of magnetic fields for reducing entrainment or impingement, further consideration of magnetic barriers is not warranted for Salem.
XIII.6.1.8 Chains and Cables Chains and cables hung vertically at the entrance to a water intake structure or water diversion have been examined as a potential behav-ioral barrier..Results of experiments conducted with juvenile salmonids (Brett and Alderdice 1958) suggest that chain and cable barriers are not effective in consistently diverting fish.
Chain curtains were among those alternatives considered undependable based on ambiguous test XIII.6-4
Salem 316(b) Demonstration:
Appendix XIII results (Sharma et al. 1981).
In the absence of demonstrated effect-iveness, chain and cable barriers are not considered to be a reliable technique for reducing the entrainment or impingement of fish at water intakes, and will not be considered further for Salem.
XIII.6.1.9 Louvers The application of fixed louvered deflectors for diverting juvenile migrant salmonids and striped bass has been discussed by Bates and Vinsonhaler (1957), Bates and Jewett (1961), and Skinner (1974).
Diversion of downstream migrants of anadromous species with louver deflectors has had variable success.
Diversion efficiency is influenced by the approach velocities and the species and sizes of fish.
Louvers have proven to be a relatively well-developed engineering and biological design concept, requiring minimal fish handling.
They do not, however, divert fish eggs and larvae, are vulnerable to biofouling accumulations, and are not self-cleaning.
Skinner (1974) discussed the diversion efficiency of the Delta Fish Protective Facility near Byron, California, which diverts water from the Sacramento I San Joaquin River system primarily for agricultural usage.
The facility is a fixed-louver design oriented 150 to the flow, with primary and secondary by-pass facilities.
Present diversion capacity of the facility is approximately 170 m3/sec (6,000 cfs).
Louver efficiency for white catfish was found to be directly related to fish length.
Primary diversion efficiency ranged from 4 percent for white catfish 10-12.5-mm (0.4-0.5-in.) long to 68 percent for those 75-100-mm (3.0-3.9-in.) long.
Diversion efficiency for salmonids was related to fish length and water velocity.
Velocity was found to influence diversion efficien<;y of smaller fish greatly, but as fish increased in size and swimming capability, velocity became less critical. Diversion effi-ciency for salmonids ranged from 65 to 84 percent in 1970 and from 84 to 90 percent in 1971 for salmon 50-150-mm (2.0-5.9-in.) long.
Differences in diversion efficiency between the two years was thought to be related to the operator's ability to attain and maintain test parameters.
Based on observations of 1.3 million striped bass 5-125 mm (0.2-4.9 in.) in length, there appeared to be an inverse relationship between diversion efficiency and channel approach water velocity.
Lower approach veloc-ities were most favorable for striped bass less than 30-mm (1.2-in.)
long.
The diversion efficiency of the louver system for striped bass was 69 percent.
Schuler (1974), using an experimental approach, observed the behavioral reaction of marine fish to fixed louvers oriented at various angles to the flow, to various louver vane spacings, and to various approach velocities.
For marine fish, highest guidance efficiency was observed for louvers oriented 200 and 300 to the flow with vanes 2.5 cm (1 in.)
apart.
Maximum diversion efficiency occurred at a mean approach veloc-ity of 61 cm/sec (2 fps).
Schuler (1974) observed for marine species that the guidance component extended 15-20 cm (5.9-7.9 in.) from the louver face and that test species guided better along an array of louvers than along s.creens.
XIII.6-5
Salem 316(b) Demonstration:
Appendix XIII Results of flume studies of a louver diversion system with a fine-mesh screen modification have been reported for several coastal California marine fish species (McGroddy et al. 1981).
When smooth woven wire slot mesh (1.2-mm by 14-mm openings) was placed on the louvers of 2.5-cm (1-in.) width and spaced at 2.5-cm (1-in.) intervals, diversion effi-ciency increased and mean lengths for 50 and 100 percent diversion decreased with respect to louvers alone for all fish tested in both conditions.
Approach velocities of 30 cm/sec (1 fps) and 61 cm/sec (2 fps) were tested and the data show decreased diversion at higher velocities due primarily to decreased survival of smaller fish unable to avoid repeated contact with the screen.
More sensitive species, like northern anchovy (Engraulis mordax), demonstrated poor post-diversion survival (18-28 percent at 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br />), reducing the effec-tiveness of the high diversion percentages for fish of lengths greater than 20 mm (0.78 in.). Quantitative relationships between survival of diverted larval fish and approach velocity, fish size, and other stress-related parameters (i.e., length of diversion structure, mesh size, and texture) are not available for species of concern at Salem.
Fouling of diversion structures and its effects have not been tested under opera-tional conditions at any power plants.
Louvers have been used effectively for diverting migrating anadromous fishes from several large agricultural water diversions, but the exclu-sive application of louvers ~o power plant cooling water intakes has not been attempted.
Louvers do not provide a positive barrier for eliminat-ing either entrained planktonic organisms or debris from a cooling water flow, and entrainment could result in blockage of the condenser tube system and lead to reduced operating reliability and increased mainte-nance of the cooling water system.
Southern California Edison has recently begun preoperational testing of a combined louver/traveling screen intake for application at a power plant cooling-system intake.
The structure is designed to provide the guidance characteristics of louvers and the positive physical barrier of a screen.
The louver system is backed up by a conventional traveling screen in a forebay supplied with water through an offshore velocity cap.
Preliminary observations indicate effective diversion of several species at lengths >150 mm (>5.9 in.), but poorer diversion of smaller fish.
Since the vast majority of fish impinged at Salem are <150 mm
(<5.9 in.) in length and louver systems do not reduce entrainment, the use of louvers will not be considered further for use at Salem.
XIII.6.1.10 Velocity Cap with Relocated Offshore Intake During the early 1950s, operation of offshore intakes wotild occasionally result in schoolS of fish becoming entrapped within the intake conduit.
These offshore intake conduits were unscreened and oriented vertically in the water column to minimize sediment deposition within the onshore intake structure.
The entrapped fish would eventually become impinged on the onshore intake screens.
Experimental testing showed that fish sense and react to vertical flow fields much more slowly than to hori-zontal flow fields.
As a result of these observations, velocity caps (Figure XIII.6-1) were placed over the entrance to the offshore intakes XIII.6-6
Salem 316(b) Demonstration:
Appendix XIII to reorient the flow patterns from a vertical to a horizontal flow field.
The quantity of fish removed from one intake structure decreased by nearly 95 percent (Weight 1958).
Velocity cap intake structures are presently in use in offshore intakes in the Pacific Ocean off southern California and in Lake Michigan.
A velocity cap functions as a behavioral barrier and is used in combina-tion with onshore intake screens, which function as a positive physical barrier for those fish that enter the intake.
Velocity caps are not expected to reduce the numbers of planktonic organisms entrained and subsequently subject to predation by biofouling organisms residing and growing on conduit surfaces.
Extensive biofouling control systems may be required to maintain operational reliability and prevent the propoga-tion of heat tolerant nuisance organisms.
Velocity caps fitted to an off shore intake conduit are not a proven technology for power station sited on rivers or estuaries. At Salem, the high rate of sediment accretion, absence of appreciable vertical temperature stratification or strata with low organism density, poten-tial for biofouling, poor accessibility (especially during winter con-ditions, and the continuing need to maintain and operate the existing intake screen structure contribute to eliminate this as a reasonable alternative.
In addition to its relatively high cost of installation, the side effects of the extensive dredging required for the conduit, and the navigational hazard an offshore intake system might ere.ate, exclude the alternative from further consideration.
XIII.6.2 PHYSICAL BARRIERS During recent years, extensive effort has been devoted to designing and
'* modifying physical barriers to provide exclusion of entrained fish and
- '. invertebrates from the water supply while minimizing mortality resulting from impingement.
In addition to excluding debris and organisms from a cooling water supply, an acceptable physical barrier must be mechani-cally dependable and operate as designed under a variety of conditions.
Physical barriers are designed to block the passage of entrained or entrapped organisms on the basis of the size of organisms encountered at specific intake systems.
Some physical barriers rely on impinging organisms for brief periods while they are mechanically transferred to a by-pass channel.
Recently, many physical barrier systems (e.g.,
vertical traveling screens and centerf low screens) have been modified on an experimental basis to include fine-mesh (0.5-2.5-mm; 0.02-0.l-in.) screen material, in an attempt to minimize the numbers *of eggs and larval fishes entrained into cooling water systems.
The following sections review the biological and engineering consider-*
ations associated with the use of various physical barri~rs at power plant intakes.
They present the results of laboratory studies, proto-type field studies, and actual operating experience at water intake and diversion structures, and discuss various media filters and infiltration systems, fixed-screen concepts, and traveling screen designs
- XIII.6-7
r--
Salem 316(b) Demonstration:
Appendix XIII XIII.6.2.l Rapid Sand (Media) Filters The high-capacity rapid sand filter (infiltration gallery) has the potential to prevent entrainment, entrapment, and impingement of all species and life stages of fish in power plant cooling systems, but only when the proper conditions exist in the adjacent waterbody.
Free flow across the filter surf ace and low approach velocity combine to eliminate potential fish kills and the need for handling and disposal of debris.
These filter systems, however, are plagued by operational problems, primarily those associated with clogging of the filter media.
As a result of these operational problems, filters have had limited use at power plant intake structures.
They require sediment stability and source waters with low suspended sediment loads and low productivity to be considered reliable.
These conditions are not present in the Delaware.
The Montour Stream Electric Generating Plant, located on the Susquehanna River, Pennsylvania, used a filter bed designed to provide make-up cooling water at a rate of approximately 33,000 gpm (2 ~3/sec; 73 cfs).
Filter operation was considered to be unacceptable because algae and fine sediment clogged the filter media.
Despite several modifications to the original design, the filter was unreliable and wa1 replaced by a perforated pipe intake.
The feasibility of using a filtration bed as a cooling water intake structure in the marine environment was examined by Stober et al. ( 197 4) and Strandberg (1974). It was concluded that a filter intake system is an effective means of excluding planktonic eggs and larval fish from power plant cooling systems.
However, the present technology is not considered to be sufficiently developed to allow reliable design and operation of filter intake systems.
Low infiltration rates of media filters require large surface areas, approximately 10 acres for every 1,000 gpm (0.07 m3/sec; 2 cfs) of cooling water, which makes their application at many sites infeasible even when used to supply make-up water for closed-cycle cooling systems.
This is the case at Salem where more than 2,000 acres of sand filters would be required to supply required cooling water flow, assuming that clogging could be avoided.
Operational problems and poor reliability of filter intake systems, as a result of clogging, siltation, and biofouling, make further con-sideration of the concep~ for use at Salem unwarranted.
XIII.6.2.2 Porous Dike A porous dike uses a filter medium of stone and gravel to exclude organisms from a cooling water system.
Porous dikes are in the devel-opmental stage and have not been used to date in estuarine or marine environments.
The porous-dike concept is applicable for both shoreline and offshore intakes, may provide a behavioral and physical barrier for larval and juvenile-adult fishes, and eliminates the necessity of a fish return system.
Operatione: reliability under actual field conditions XIII.6-8
Salem 316(b) Demonstration:
Appendix XIII and maintenance associated with biofouling, clogging, and sediment accumulation would have highly site-specific characteristics.
Preliminary criteria for the design and use of a porous dike as an intake structure include:
- 1.
The dike must be stable and resistant to erosion caused by water currents and storm wave action.
- 2.
The size and composition of the media must provide structural integrity, acceptable water flow rates, and exclusion of organisms.
- 3.
The hydraulic efficiency must be high and biofouling and sediment accumulation low.
- 4.
The dike must not require excessive maintenance.
S. 'The design should include provision for backflushing and recirculation of heated water to eliminate clogging due to biofouling and ice.
Hydraulic investigations of flow-throu~h porous-dike structures under laboratory conditions (Roberge 1978) provide the foundation for the design of large-scale porous dikes.
Engineering evaluation of porous-dike intake structures (Roberge 1978) indicates that the concept is*
feasible, but long-term prototype testing under field conditions is required to determine the practicality and performance of a porous-dike intake at a specific site.
The primary biological advantage of a porous dike is its potential effectiveness in excluding larval and juvenile fishes from the cooling water system.
Schrader and Ketschke (1978) reviewed the biological aspects of porous-dike intake structures and concluded that a porous dike may act as both a behavioral and a physical barrier for larval and adult fishes.
Available information, however, is insufficient to determine operational exclusion efficiency for various sizes and species of estuarine fish at various approach velocities; nor have the exclusion efficiency and survival of entrained fish eggs been determined for porous-dike intake structures.
Two operating power plants located on the western shore of Lake Michigan have intake structures designed to obstruct organisms and debris from entering the cooling systems with stone barriers (Michaud 1981).
At the Lakeside Power Plant (310 MWe), the onshore intake structure is supplemented with a rubble dike that has been in operation for nearly 60 years.
The Point Beach Nuclear Plant (994 MWe) has a 10-year history of operation with an offshore intake crib comprised of quarry stone.
Cross sections of these intake designs are shown in Figure XIII.6-2.
The operation of these structures has been relatively trouble free except for the following (Michaud 1981):
XIII.6-9
Salem 316(b) Demonstration:
Appendix XIII Lakeside
- Shoreline screen clogging due to fish populations and algae growing in the diked pond
- Periodic dredging of the diked pond to remove settled sediments Shift and slippage of larger stones requiring retrieval and reconstruction
- Sedimentation along outer base of dike decreasing porous surf ace area Point Beach Ice build-up causing blockage of water passage through stones
- Inefficient heated water recirculating system requiring redesign for winter operation
- Washout of sand and.gravel causing settling of dike Silt acumulation in crib feeder pipes
- Storm erosion Although these problems are not *severe where water quality is good and sediment loads and biofouling is minimal, they indicate the ciisadvan-*
tages that must be considered on a site-specific basis.
The effectiveness with which the porous dike can reduce impingement rates is indicated by a comparison with rates measured at adjacent power plants for juvenile and adult alewife over a three-month period.
For Lakeside, impingement rates ranged from 2.3 to 33.3 percent of those at adjacent plants.
At Point Beach, impingement rates ranged from 4.8 to 86.4 percent compared' to the same plants during the same period.
Real differences in population levels near these intakes could not be taken into account and high variability.in the data precludes precise quan-tification of exclusion efficiency of these dike designs.
Similarly, apparent reductions in entrainment rates of greater than 60 percent could not be unequivically attributed to intake design or intake loca-tion at the several plants (Michaud 1981).
Field and laboratory testing of porous dike characteristics has been conducted at the Brayton Point Station, Massachusetts (Ketschke and Toner 1982; Ketschke 1981a,b).
Rock gabions constructed with either 3-or 8-in. test stones were used to evaluate hydraulic performance and potential pump-condenser exclusion of entrainable eggs and larvae of locally abundant species.
Flume studies showed that bay anchovy larval passage through 8-in. stone dike material was essentially pre-cluded (94-99 percent exclusion), whereas winter flounder showed a size dependent trend C.23-87.5 percent exclusion).
Juveniles of all species XIII.6-10
Salem 316(b) Demonstration:
Appendix XIII tested avoided entrainment through the dike material in the test flume.
Laboratory approach velocities ranged between 0.02 and 1 fps and the field approach velocity was 0.1 fps for these tests.
Hydraulic studies showed that biofouling and detrital accumulation decreased the gabion void volume by approximately 25 to 30 percent and increased gabion weight by 10 to 15 percent in the first 6-12 months of operation.
Flow-through volumes per surf ace area apparently stabilized at approximately 0.025 cfs/ft2 after 6-12 months of operation with periodic backflushing (Ketschke 198lb).
On the basis of the operational history of porous-dike structures at Lake Michigan power plants, which indicates that even in waters with low suspended sediments some clogging occurs, and the results of prototype testing at Brayton Point, which ultimately excluded the porous-dike concept as a feasible alternative in estuarine waters, it would appear that accretion of sediment in the Delaware would rapidly clog such a structure at Salem.
In addition, sediment passing through the dike
,would have to be dredged periodically and the operation of the present intake continueG to screen fish populations confined within the dike structure. Available stability-flow information (Ketschke 198lb) indicates that a structure of a 6-m (20-ft) depth would have to be a minimum of approzimately 6,048 m (10,000 ft) in length to accommodat~
the present Salem ~ooling water requirements.
The extensive creat~d habitat would be suitable for a biofouling and predator community thet preys upon fish eggs and larvae drawn to the dike surface.
Exclusive of the high capital and outage penalty costs of construction, the require-ment for an extensive hot water backflushing system to prevent or retard icing, biofouling, and clogging is not a readily available technology.
The combination of all these factors makes the alternative to construct a porous dike at Salem untenable from a biological benefits and engi-neering viewpoint.
This option will therefore not receive further consideration.
XIII.6.2.3 Radial-Well Colle~tor~
The radial well is a subterranean intake system that withdraws water from an aquifer or from an overlying water source such as a river or lake.
Radial wells have been used to supply water for domestic and industrial usage and are planned to be used to supply cooling tower make-up water at several steam electric power plants.
The maximum capacity of a typical radial well collector is approximately 55,500 gpm (3.5 m3/sec; 124 cfs), which is insufficient to meet the demands of most once-through cooling systems.
Limitations in aquifer size, sediment permeability, and groundwater hydrology tend to make it technically and economically impractical to build radial wells large enough to provide adequate water volume for once-through cooling.
Radial-well collectors rely on induced infiltration through unconsoli-dated alluvial deposits; they furnish water that is typically low in turbidity and concentrations of suspended solids.
In addition, because of the extremely large surface area associated with radial-well col-lectors, the water velocity at the waterbody/sediment interface is extremely low, less than 0.01 cm/sec (0.0003 fps) (Mikels and Bennett XIII.6-11
,(***
L Salem 316(b) Demonstration:
Appendix XIII 1978).
The low velocities and positive physical barrier created by the substratum result in complete exclusion of egg and larval fish and microzooplankton from the water being withdrawn.
Engineering and operational considerations include the suitability of geological structures and groundwater hydrology of a particular site, sediment deposition, presence of iron bacteria, biological fouling, and accumulation of debris.
Before a radial-well collector can be considered acceptable for a specific site, the potential for depleting groundwater storage reserves, particularly during droughts, and the operational reliability of the intake system through the life of the power plant must be evaluated.
The radial-well collector provides a biologically effective intake structure that eliminates entrainment and impingement.
The use of radial wells, however, is limited to specific sites because of substrate permeability and aquifer characteristics, and is limited to meeting small water demands comparable to the make-up water requirements for close-cycle cooling.
The limited capacity and siting constraints make radial-well collectors unsuitable at power plant intakes such as Salem.
XIII.6.2.4 Conventional Stationary Mesh Screens, Perforated Plates, and Pipes Stationary screens have. long been used in irrigation canals and indus-trial water intake systems.
Debris accumulations on screen surfaces reduce water flow volume and the efficiency of these screen instal-lations.
Blockage of a stationary intake screen by impinged debris results in unacceptable operational reliability of stationary screens
- for use in once-through cooling water intakes, particularly in areas with heavy detrital and sediment loads, such as the lower Delaware River, so are not acceptable alternatives for Salem.
Perforated plates and pipes provide a positive barrier for adult and subadult fish and have the potential for the protection of eggs, larvae, and juvenile fish (Maxwell 1973; Richards 1978).
Biofouling and debris accumulations reduce reliability of perforated intakes, since they are not self-cleaning.
Perforated pipe intake structures are being used to supply make-up water at several power plants, but they have not been used for once-through cooling systems.
These devices are not proven technology for large-volume, once-through cooling systems.
Biofouling and heavy debris load coupled with absence of self-cleaning make these devices untenable as alternative technologies for Salem.
XIII.6.2.5 Cylindrical Wedge-Wire Screens with Relocated Intake Structure Stationary cylindrical screens are presently being considered for use on offshore power plant cooling water intakes.
The application of stationary cylindrical screens for once-through cooling system intakes has undergone extensive evaluation (Key and Miller 1978; Cannon et al.
1979; Browne 1980; Gulvas and Zeitoun 1980; McGroddy et al. 1981; ASCE XIII.6-12
Salem 316(b) Demonstration:
Appendix XIII 1982).
Until recently, wedge-wire cylindrical screens have been in the developmental stage and have not been considered to be available technologies for application to once-through cooling water systems (Cada et al. 1979).
The design of stationary, submerged, cylindrical screens typically includes the use of a wedge-wire material.
Wedge-wire screen is manu-factured by welding wire of triangular cross sections to a support structure (Figure XIII.6-3).
Wedge-wire screen is generally constructed with slot widths ranging from 0.25 to 2.5 mm (0.01-0.1 in.) and offers 20-35 percent open area for water passage.
This design results in a smooth screen surface and screen openings that widen inwards, facili-tating screen cleaning (backwashing) and increasing hydraulic efficiency (Cook 1978).
The cylindrical screen configuration, which promotes radial flow into the screen, and the use of wedge-wire screen material are expected to reduce screen clogging~
A typical intake system design with stationary, completely submerged, cylindrical screens is shown in Figure XIII.6-4.
The cylindrical screens can be used individually, in pairs, or in a manifold design to provide the necessary cooling water volume.
The fish protection potential of a cylindrical wedge-wire screen depends on the location and orientation of the screen with respect to ambient water currents, on the size of the screen openings, and on the through-screen velocity.
The absence of a confining screenwell which may entrap organisms and the design of screens with through-screen velocities less than 15 cm/sec (0.5 fps) serve to reduce the numbers of organisms entrained and impinged.
The once-through cooling water intake system for Unit 3 of the J.H. Campbell Plant on Lake Michigan consists of 28 pairs of 1.37 m (4.5 ft) diameter by 1.2-m (4-ft) long, 9.5-mm (3/8-in.) opening Wedge-Wire screen modules.
Each pair is mounted 4 m (6.5 ft) above the bottom 2,117 m (3,500 ft) offshore starting at the 21-m (35-ft) contour.
Seven pairs of screen are mounted on each of four manifold headers emptying into an 5.48-m (18-ft) diameter intake pipe which delivers water at a rate of 1,280 m3/min to the onshore intake channel.
Although numerous difficulties were encountered in the design and construction phase, the intake has been operating since November 1979 without substantial clogging, biofouling, or ice damage problems.
The biological effects associated with the intake operation were studied by the University of Michigan (1982) and concluded the following:
- 1.
Biofouling of over 60 percent of some screens did not affect function of the screen modules.
- 2.
No impingement of live fish was observed to occur.
- 3.
Entrainment may have been increased due to spawning activities and attraction of fish to the intake structure.
XIII.6-13
Salem 316(b) Demonstration:* Appendix XIII Biological data on the potential effectiveness of cylindrical screens using wedge-wire screening of smaller slot widths to minimize entrain-ment and impingement have been collected in prototype flume experiments conducted by Hanson et al. (1978).
The entrainment and impingement of fish of various sizes (eggs, larvae, and subadults) on screen cylinders 0.3 m (1 ft) in diameter and 0.6-m (2-ft) long, made up of Wedge-Wire screen with slot widths ranging from 0.25 to 1.0 mm (0.01-0.04 in.)
was tested.
Through-screen velocity was 15 cm/sec (0.5 fps) and chan-nel velocity ranged from 0 to 79 cm/sec (0-2.6 fps).
Results of these experiments indicate that:
- 1.
Impingement of fish larger than 15 mm (0.6-in.) in fork length was virtually eliminated on screens with 0.5-mm (0.02-in.) slot width.
- 2. Fish 12-17 mm (0.5-0.7 in.) in fork length impinged on the screen showed excellent ability to escape impingemejt.
- 3.
Less than 0.1 percent of the striped bass eggs test~d were entrained through screens with slot widths of 0.25-0.5 mm (0.01-0.02 in.).
- 4. Mortality of striped bass eggs impinged on 0.5-mm (0.02-in.) Wedge-Wire screen for 0.5-2 minutes ranged from 0 to 11 *. 9 percent and averaged 1.4 percent for*
all tests.
Primary engineering concerns for stationary cylindrical wedge-wire screens focus on maintenance and operational reliability of the intake, which are influenced by the extent and frequency of debris clogging and biofouling accumulation on the screen surface.
Each cylindrical screen must be equipped for either air-burst or hydraulic backwashing to remove accumulated debris.
An ambient water velocity past the screen greater than the through-screen velocity promotes self-cleaning.
The signifi-cance of a tangential velocity component across the screen to minimize clogging is discussed by Hanson et al. (1978); the problem of removing biofouling organisms from screens in brackish water or marine environ-ments is described by Key and Miller (1978).
The effects of clogging and biofouling on the operational reliability of stationary cylindrical screens should be investigated for intake sites in the marine environ-ment.
Similar evaluations should be conducted in areas of heavy detri-tal and silt loading, before they can be confidently used in once-through power plant cooling water intakes in estuarine environments.
It is noted that Hansen et al. (1978) found that detrital material from the vicinity of Salem clogged the wedge-wire.test screen more rapidly than other sources of detritus.
The design and operation of stationary screening systems have been established in many small industrial applications.
Stationary screening systems such as the wedge-wire cylindrical screens have only recently been applied to power plant intakes. Field and laboratory testing has been underway for several years to establish the biological effective-ness of stationary screens and to refine engineering design criteria for screen location, orientation, through-screen velocity, and mesh opening XIII.6-14
Salem 316(b) Demonstration:
Appendix XIII size.
Operational reliability, screen clogging and biofouling, and maintenance requirements for stationary screens sited in various water-body types is required before site-specific adoption of this alternative can be considered.
Offshore intake conduits fitted with cylindrical Wedge-Wire screens have not been used for large-volume intakes in estuarine waters.
Entrainment may be increased by attraction of spawning activity to the vicinity of the submerged intake structure. Detrital clogging was more rapid on test panels at Salem than with other materials at other sites examined.
Based on the measurement of maximum detrital loading on the present screens being in excess of 500 gm/100 m3 and maintenance of cooling water system flows at 2.2 million gpm, it can be calculated that approximately 500,000 kg of detrital material could accumula,te around the intake Wedge-Wire screen array during an hour period surrounding slack tide.
With insufficient tidal currents to remove material from the area, reduction in backwashing system efficiency could result in
- unreliable operation and water supply at Salem~ Methods have _not been developed for effective cleaning of marine encrusting organisms from the surf ace of such submerged screens.
Deposition of sand and silt in this zone of natural accretion may be a serious impediment to operation of such a system.
Inaccessibility for needed cleaning and maintenance, especially during winter conditions, is a major concern.
To assure a reliable supply of cooling water, the existing intake would have to be maintained.
For these reasons, further consideration of this technology as an alternative for Salem is not warranted at this time.
XIII.6.2.6 Drum Screens Vertical drum screens have.been used for fish diversion in irrigation canals, and in British steam electric stations for the protection of salmonids, with varying success (Eicher 1974).
Vertical drum screens with diameters of approximately 3 m (9.8 ft) are commonly aligned in rows leading to a by-pass channel.
Screen rotation carries imping~d fish toward the by-pass and provides self-cleaning of debris.
Vertical drum screens provide a positive barrier for adult and subadult fish, but do not appear capable of protecting fish eggs and larvae.
Fluctuations in water depth do not affect the performance of vertical drum screens.
Horizontal drum screens have been used for fish diversion in irrigation facilities, power plants, and hydroelectric projects, as discussed by Maxwell (1973), Eicher (1974), and Mayo (1974).
'rhese well-developed and proven screens provide a positive barrier for adult and subadult fish, but do not protect their eggs or larvae.
The screen surf ace is cleaned through screen rotation, but screen rotation is detrimental to impinged fish if no by-pass facility is provided.
Diversion efficiency of horizontal drum screens is sensitive to fluctuating water levels.
Drum screens, although acceptable for use in intake structures of orice-through power plant cooling systems, of fer no biological or engineering advantages over conventional vertical traveling screens.
Drum screens have not been utilized extensively in electric generating stations in XIII.6-15
Salem 316(b) Demonstration:
Appendix XIII the United States, partly because of problems associated with the carry-over of debris into the condensers, which reduces system reliability.
They accordingly will not be considered further for application at Salem.
XIII.6.2.7 Horizontal Traveling Screens The horizontal traveling screen (Figure XIII.6-5) developed by Bates (1969) has been proposed for fish diversion in canals, hydroelectric dams, irrigation intakes, and power plant intakes.
Major attributes of the horizontal traveling screen concept include (1) formation of a complete physical barrier, (2) high diversion efficiency of juvenile migrant fish, and (3) release of impinged fish into a by-pass without aerial exposure.
Operation of horizontal traveling screens is not greatly affected by fluctuations in water depth.
The screen is self-cleaning, thereby minimizing head loss, and is capable of operating under higher approach velocities than is normally possible with other types of screens.
Research and development of the horizontal traveling screen has been reported by Bates (1969), Bates et al. (1970), Farr and Prentice (1974), and Prentice and Ossiander (1974).
Prentice and Ossiander (1974), studying 70-mm (2.8-in.) fingerling chinook salmon (Oncorhynchus tshawytscha), observed 98 percent diversion efficiency of a traveling screen aligned at an angle of 30o to a flow of 46 cm/sec (1.5 fps) under lighted conditions, and a 91 percent diver-sion efficiency under dark conditions.
Diversion efficiency for 170-mm (6.7-in.) salmonids tested under similar conditions was 99.6 and 99.8 percent during day and night tests, respectively.
No screen impingement was observed during these tests, and 48-hour posttest survival exceeded 97 percent for all experiments.
Unfortunately, mechanical performance of horizontal traveling screens is not, at present, acceptable for continuous operation at a power plant intake such as Salem's.
Operation is limited by both screen depth and screen weight.
Prototype tests designed to examine mechanical operation and to assess performance limitations are discussed by Farr and Prentice (1974). Potential solutions to mechanical problems, resulting from sus-pended sediment and sediment bedload, have yet to be perfected.
Horizontal traveling screens promise to be effective in reducing fish impingement but are not expected to reduce the number of organisms entrained into a cooling system.
The lack of reliable operation of horizontal traveling screens, however, precludes any further consider-ation for their use in cooling water intake structures applicable for Salem.
XIII.6.2.8 Rotating Disc Screens Rotating disc screens have been used in both small irrigation diversions and municipal water supplies.
No application of rotating disc screens in power plant intake structures has been reportedG Rotating disc screens of fer no biological or engineering advantage over conventional vertical traveling screens for use in cooling water intakes.
XIII. 6-16
Salem 316(b) Demonstration:
Appendix XIII XIII.6.2.9 Centerflow or Passavant (Single-Entrance, Dual-Exit) and Cogenel (Dual Entrance, Single-Exit) Traveling Screens The centerflow or Passavant traveling screen represents a relatively new intake screening technology in the United States, although it has been used extensively in European industrial and electric generating facili-ties for almost three decades.
Centerflow screens (Figure XIII.6-6) are oriented parallel to the approaching waterflow, and water enters through the center of the screen and exits through both vertical faces.
Screen panels on centerflow screens are attached to a continuous drive chain and unlike conventional vertical traveling screens, each screen panel forms a concave basket, increasing available screening surf ace area.
Screen mesh sizes range from 0.5 to 9.5 mm (0.02-0.4 in.), with many units having from 1.0 to 2.5-nnn (0.04-0.1-in.) mesh.
Because debris can accumulate rapidly on the small mesh commonly used in centerf low screens, they are designed to rotate continuously.
The hydraulic flow patterns associated with centerf low screens are more complex than those associated with vertical traveling screens.
Water flows into the scree~ chamber through a keyhole-shaped opening in the front wall of the intake screen structure, turns 900 to flow through the screen mesh, and turns 900 to complete its transit to the circulat-ing water pump.
Ef fec.tive screening occurs on both the ascending and descending sides of centerflow screens, increasing available screen surface area.
As a result, the average through-screen velocity of a centerf low screen is less than the approach velocity to the screen.
However, through~screen velocities are highly variable across the screen face because of flow patterns and screen orientation, and velocities tend to increase with distance downstream from the chamber entrance.
The turbulence of the flow may negate potential benefits from reduced average through-screen velocities.
High velocities at the entrance to the screen may also prevent the escape of fish entrapped within the screen structure.
Screenwash mechanisms are similar for both centerf lo~ and vertical traveling screens.
Spraywash pressures generally range from 50 to 100 psi. Debris and 1mpinged organisms dislodged from the screens fall directly into a single sluiceway for return to the source waterbody.
Fish-protection systems for centerflow screens, although not currently commercially available, may involve such modifications as watertight holding troughs at the base of each screen panel, low-pressure (10-20 psi) spraywashes, and an additional sluiceway to return impinged organisms to the source waterbody.
Murray and Jinnette (1978) examined the initial survival of organisms impinged on continuously rotating centerflow screens located at the Barney M. Davis Steam Power Plant, Corpus Christi, Texas.
Initial impingement survival of 15 species of invertebrates and 37 species of fish was estimated to be 86 percent (10,406 individuals alive; 1,654 individuals dead) during the 12-month study.
Impingement survival was found to vary among species and among months of the year.
Lowest initial mortality of the predominant species during a month occurred in February, when menhaden (mean standard length= 21 mm; 0.8 in.)
experienced a 5 percent initial impingement mortality.
Highest initial XIII.6-17
Salem 316(b) Demonstratiqn:
Appendix XIII mortality of a predominant species by month occurred in June, when bay anchovy (mean standard length= 25 mm; 1.0 in.) experienced a 98 percent initial impingement mortality.
No studies were performed to examine long-term survival of organisms previously impinged on centerflow screens.
Fine-mesh centerflow screens are being investigated in laboratory studies to determine their potential effectiveness in protecting larval fish at power plant intakes (Magliente et al. 1978). Field and laboratory studies are required to evaluate the initial and long-term survival of eggs and larval fish impinged on fine-mesh centerf low screens.
Insufficient data preclude a detailed comparison of the potential survival of egg and larval fish impinged on modified vertical traveling screens (fine-mesh screen material, fish buckets, low-pressure spraywash, continuous rotation) and centerflow screens (fine-mesh screen material, continuous rotation). Significantly increased impingement survival has not been satisfactorily demonstrated for these systems.
Centerf low screens require increased screen-to-pump distance over that requir~d for conventional vertical traveling screens.
This may make a screen retrofit of an existing intake infeasible because of space limi-.
tations.
Irregular velocity patterns, turbulence, and attendant head losses are inherent with the waterflow patterns for centerflow screens.
Highest water velocities occur in the entrance area of centerflow screens and could contribute to fish entrapment.
Within the screen chamber,_ velocity varies irregularly as current changes direction, resulting in non~uniform flow through the screening surf ace.
Use of average approach and through-screen velocities for centerf low screens is thus an inappropriate and misleading design parameter.
The turbu-lence associated with centerf low screen systems was examined by Alden Research Laboratory (1974), which found that circulating water pmnp performance was adversely affected by flow irregularities if screen-to-pmnp distances were too short or baffling was inadequate.
Operating and maintenance experience with centerf low screens in the United States is limited to one installation, *the Barney M. Davis Steam Power Plant, where centerflow screens have been in use since 1974.
Originally, a 0.5-mm (0.02-in.) polyester mesh screening material was.
used.
However, the polyester screen material fatigued and subsequently failed during operation and was replaced with a nylon mesh material having 1.0-mm (0.04-in.) openings which is now performing satisfac-torily.
Other than operational problems encountered during start-up of the centerflow screens, routine maintenance has been described as minimal (Benes 1978, personal communication).
Details of operating and maintenance experience for centerflow screens outside the United States are unavailable.
Several alternative design configurations for the centerflow screen concept have been proposed in an attempt to minimize the probability of organisms becoming entrapped within the screen structure by higher velocities through the opening than through the screen mesh.
A double-entry /double-exit screen design has also been proposed.
- XIII.6-18
.1
Salem 316(b) Demonstration:
Appendix XIII In addition to the single-entrance/dual-exit design shown in Figure XIII.6-6, there is a double-entry/single-exit "Cogenel" design in which water enters the screen from two sides and passes out through one end.
This design can be located either within a screenwell or supported from a platform with no confining concrete housing (Figure 13.6-7).
A prototype of a double-entry/single-exit traveling screen equipped with 0.5-mm square mesh panels has been tested at Big Bend Station on Tampa Bay, Florida.
A six-month study of postimpingement survival of organisms removed from the screen with a low-pressure (10 psi) spraywash showed substantial 96-bour survival (Taft et al. 1981).
Survival among impinged invertebrates generally exceeded 90 percent while survival of fragile fish larvae,. e.g., bay anchovy, an4 the scianidae was less than 25 percent.
Hatcbability of impinged eggs was also high (>60 per-cent for most species). Results of the engineering evaluation (Mussalli et al. 1981) showed that the 1:5 scale prototype performed favorably at 0.5 and 1.0 fps with respect to differential bead and automatic rotation speed.
Existing vertical traveling screens would back up the double-entry /single-exit screens if the modifications were adopted.
To date, biological and engineering data are not available to compare the rela-tive effectiveness of these alternative screen configurations.
Centerf low or Passavant and cogenel screens can be an acceptable intake screening technology for proposed new units depending on site-specific engineering performance, o~erational reliability, and maintenance con-siderations. Retrofit installation into an existing intake structure would probably require extensive modification of the intake, and might adversely affect the performance and reliability of circulating water pumps.
Although these screens do not appear to offer any major bio-logical advantag~s over conventional vertical traveling screens, their use is considered in greater detail in Section 8.9 of the Demonstration due to their widespread use in Europe and low through-screen water velocities.
XIII.6.2.10 Vertical Traveling Screens The conventional vertical traveling screen (VTS), the most commonly used intake screening device by power plants in the United States including Salem, is available commercially from a nuniber of manufactur-ers in a wide range of lengths, widths, and materials. It consists of a series of screen panels attached to a chain drive, mounted vertically in a concrete structure which normally functions as the screen well and circulating pump well (Figure'XIII.6-8). Although the vertical travel-ing screen was originally.designed to prevent clogging of the condenser tubes, in *recent years modifications have been made to enhance the fish protection capabilities of the screens.
The screens are designed to remove particles whose diameters are more than one-half that of a con-denser tube.
In most situations, 9.5-mm (3/8-in.) mesh is used.
In a conventional installation the screens rotate intermittently, either at regular intervals of several hours or when debris buildup yields a predetermined pressure differential across the screen; most screens are not equipped to rotate continuously for extended periods of time.
XIII.6-19 J
- .~..
Salem 316(b) Demonstration:
Appendix XIII During rotation, material caught on the screen is removed by either a low-pressure (10-20 psi) or a high-pressure (50-100 psi) spraywash and is either returned to the source waterbody or transferred to refuse bins for disposal.
A design recently proposed by Western LNG Associates (California Public Utilities Commission 1978) would locate the vertical traveling screens, but not the circulating water pumps, in an offshore intake structure in the form of a caisson.
XIII.6.2.11 Other Physical Barriers A wide variety of physical barriers, in addition to those previously discussed, either have been or are currently being examined for their application to power plant intakes.
Many of these alternative designs originated as intake structures £or industrial or municipal water sup-plies, at irrigation water diversions, or in association with hydro-electric dams.
There is an expanding effort to identify, design, and test the potential effectiveness of intake design concepts under labora-tory conditions (ASCE 1982).
A promising concept for alternative intake design is the use of vertical traveling screens oriented at an angle to the intake flow and leading to a by-pass.
This design concept bas been tested under laboratory conditions (Taft and Mussal li 197 8) *and was effective in diverting alewife into a by-pass.
The angle-screen intake design is currently being incorporated into the intake structure design of several proposed and existing power plants.
Field verification of the diversion ef fi-ciency of an angled-screen intake under actual operating conditions is not yet available.
Engineering performance and operational reliability under field conditions is unknown.
Attempts have been made to exclude fish from the area around an intake by encircling the intake area with netting.
The netting is believed to form both a physical and behavioral barrier for fish.
Results of field testing conducted to date haye been inconclusive.
Problems associated with debris accumulation on the net, the maintenance of the integrity of the net barrier, especially in areas where bottom topography is irregular or following storms, and the hazard to navigation have not been adequately resolved.
Net barriers are applicable only in lacus-trine (lake) environments, where currents are minimal.
Variations of intake designs previously discussed include the use of offshore louvers, a caisson offshore intake structure which is sur-rounded by vertical traveling screens, inclined traveling screens (con-veyor screen), and "hump-back" screens.
Sonnichsen (197 5) discusses the development and use of many of these alternative designs.
Few of these alternatives are generally applicable to power plant intake screening, but may have site-specific applicability depending on the particular biological characteristics and engineering requirements.
XIII.6-20
Salem 316(b) Demonstration:
Appendix XIII XIII.6.3 FISH COLLECTION, REMOVAL, AND CONVEYANCE SYSTEMS The following sections review the design considerations, effectiveness, and application of fish return/conveyance systems and fish removal systems at power plant intakes.
Such systems remove impinged organisms after brief periods and return them to the receiving waterbody, or con-centrate entrapped organisms within an intake structure and remove them by use of pumps, elevator baskets, or by-pass channels.
XIII.6.3.1 Vertical Traveling Screen Fish Buckets and Accessories Impingement survival of aquatic organisms depends upon a number of interrelated factors:
the species, life stage, size, duration of impingement, stress, fatigue, hydraulic parameters, and debris loading.
Impingement survival for some species has been improved by the incorpo-ration of watertight collection buckets along the base of each screen panel to prevent repeated impingement of organisms and to provide a wet holding area for organisms during screen rotation (Figure XIII.6-9).
In conjunction with this addition, a low-pressure wash system may be installed to remove impinged organisms from the screen and reduce the stress and abrasion from exposure to the high-pressure debris removal spraywash.
A separate fish-return sluiceway can be incorporated to transport organisms back to the receiving waterbody.
Continuous screen rotation has also been used to reduce stress on impinged organisms.
Incorporating some of these features into an existing vertical traveling screen requires consideration of the specific intake.structure and its performance.
Potential problems include (1) alteration of the hydraulic characteristics of the intake structure, which could affect the perfor-mance and reliability of circulating water pumps; (2) requirements for additional screen area to maintain acceptable approach velocities, while providing adequate cooling water volumes; and (3) increased maintenance resulting from screen clogging and reduced reliability of drive motors from continuous operation.
A dual spraywash system would require separate sluiceways for fish and debris, additional pumps,.control mechanisms, piping, and result in increased maintenance costs.
Installation of either watertight buckets on each screen panel or fine-mesh screen material would necessitate reinforcement of structural supports to maintain the structural integ-rity of the screen under increased static and dynamic loads.
In the absence of extensive operating information for the modified screens, especially for those equipped with fine mesh, predictions.of operation and maintenance problems that might influence reliability cannot be made with certainty.
Salem is presently equipped with vertical traveling screens with 9.5-nnn square mesh modified to include fish buckets, low-pressure spraywash~
and a special fish handling trough to provide for the return of impinged fish to the estuary* alive.
Continuous rotation of the existing screens minimizes the impingement time and therefore tends to improve impinge-ment survival.
The biological benefits of the current operation mode are a part of the bases of comparisons among alternative intake designs.
XIII.6-21
- --\\
Salem 316(b) Demonstration:
Appendix XIII King et al. 0978) compared the effects of different screen rotation frequencies and screenwash pressures on the survival of fish impinged on conventional vertical traveling screens at three power plants on the Hudson River (Table XIII.6-1).
Continuous screen rotation resulted in better impingement survival for young-of-the-year white perch than screenwash at either 2-or 4-hour intervals (Figure XIII.6-10).
Low-pressure screenwash sprays (SO psi) resulted in better initial and long-term (84-hour) survival of impinged white perch on several occa-sions, but the results of screenwash pressure studies were generally inconclusive.
White and Brehmer (1976) evaluated the initial survival of fish impinged on a modified vertical. traveling screen similar to the one shown in Figure XIII.6-9, which has been in operation since 1974 at the Surry Power Station, James River, Virginia.
Average initial survival for 58 species of impinged fish was 93.3 percent.
Survival of impinged fish beyond* the IS-minute holding and observation period was not de~ermined.
Impingement survival of the relatively hardy juvenile chinook 8a~mon on modified vertical traveling screens located on the Columbia River was reported by Page et al. ( 1976, 1978). Initial survival was 95.6 and 97.2 percent, respectively, in 1976 and 1977.
Long-term (96-hour) survival of impinged chinook salmon in 1976 was 94.8 percent; long-term survival was not report*ed for 1977.
In addition, Page et al. estimated initial impingement survival of yellow perch fry to be approximafely 92 percent (1978). Additional information on the initial and long-term survival of a variety of species and sizes of fish, impinged on modified vertical traveling screens under a variety of enviromnental conditions, is needed before the general effectiveness of intake screen modif ica-tions designed to reduce impingement mortality can be assessed.
Ecological Analysts (1979) investigated the use of fine-mesh screen material (2.5-mm; [0.1-in.] nylon mesh) in a vertical traveling screen tested under field conditions, in an effort to reduce the number of larval fish entrained into a power plant cooling system. It was con-cluded that early life stages of striped bass were not able to withstand the stresses imposed by impingement and collection.
- For larval striped bass (IS mm; [0.6 in.] mean length) 96-hour survival was estimated to be 60 percent.
For juvenile striped bass (19 mm; [0.8 in.] or greater in length) survival is expected to exceed 7S percent.
The survival of entrained striped bass passing through the Indian Point Power Plant cooling system was compared with survival of striped bass impinged on the 2.5-mm (0.1-in.) screen at the Indian Point cooling water intake (Ecological Analysts 1979). It was concluded, based on the low retention and survival of eggs and smaller larvae impinged on the fine-mesh traveling screen, that fine-mesh screens would not.be
- effective for reducing entraimnent losses for these life stages.
In addition, since the survival of larger larvae and juveniles following entrainment was comparable to that following impingement on the fine-mesh screens, selectively diverting these fish at the intake would not appreciably affect their survival.
XIII.6-22 I
I I
I I l Salem 316(b) Demonstration:
Appendix XIII Texas Instruments, Inc. (1977) examined the survival of young-of-the-year and yearling fish impinged on a modified vertical traveling screen (low-pressure spraywash, dual screenwash sluiceways, fish buckets) equipped with 2.5-mm (0.1-in.) nylon screen mesh.
The vertical travel-ing screen was rotated continuously during the impingement survival studies.
Most of the 3,619 fish collected were bay anchovy, blueback herring, and white perch.
Mean initial survival of all species was 41 percent, and mean survival of each species is presented in Table XIII.6-2.
Species-specific survival patterns are apparent, with high long-term survival for species such as white catfish, white perch, and Atlantic tomcod and low survival for species such as bay anchovy and rainbow smelt.
Tomljanovich et al. (1978) conducted a series of laboratory studies designed to examine factors influencing the retention and post-impinge-ment survival of larval fish impinged on fine-mesh screen material.
Four square-mesh screen sizes ranging from 0.5 to 2.5 mm (0.02-0.1 in.)
were tested; only the 0.5-mm (0.02-in.) screen provided 100 percent retention of the larval fish tested.
Post-impingement survival of lar-val fish was shown to be inversely related to the duration of impinge-ment and dependent on the species and size of fish tested and, to a lesser extent, on water velocity.
Survival of larval fish 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after impingement for 16 minutes ranged from less than 1 percent for striped bass to 96 percent for bluegill and smallmouth bass.
The results of studies available to date suggest that the entrainment of larval fish through power plant cooling water systems can be virtually eliminated by use of 0.5-mm (0.02-in.) intake screen mesh.
But survival of larval fish passing through a cooling water.system may be relatively high (Cada et al. 1979), and survival on a fine-mesh screen that is operated in an intermittent screenwash mode or is subject to high detri-tal loads may be extremely low (Tomljanovich et al. 1977).
Vertical traveling screens are an acceptable intake screening technol-ogy.
The vertical traveling screen has demonstrated performance capa-bility and an extensive. history of operational reliability.
Two major classes of modifications have been developed for vertical traveling screens to collect impinged organisms and return them to the waterbody:
(1) "fish buckets, 11 a system of troughs and low-pressure sprays to minimize damage to impinged fish, as is in present use at Salem, and (2) fine-mesh screens, which impinge ichthyoplankton instead of entrain-ing them.
The merits of these systems depend on the specific biological and engineering conditions at the particular plant where they would potentially be installed. Accordingly, they are detailed in Sections 8.2 and 8.4 of the Salem 316(b) Demonstration.
XIII.6.3.2 Fish-Return Conveyance Systems A fish-return conveyance system, which is generally used in association with vertical traveling intake screens, is simply an open or enclosed trough which returns organisms removed from the intake screens to the receiving waterbody.
The sluiceway troughs are typically made of con-crete or steel and use either gravity-induced _:flow or a pumping system.
XIII.6-23
Salem 316(b) Demonstration:
Appendix XIII The design of conveyance systems has not been standardized or exten-sively studied, so they vary widely from one power plant intake to the next.
The limited data available on the relationship between conveyance system design and survival of organisms returned to the receiving water-body make it difficult to identify and quantify the effects of various design parameters on the biological effectiveness of conveyance systems.
The difficulties in extrapolating generalizations from one site to another at the present time are particularly important in considering the design of a fish-return conveyance system for use with a fine-mesh intake screen for removing eggs and larval fish from th~ intake.
Cada et al. (1979) proposed a set of recommendations concerning fish return conveyance systems which can be expected to contribute to the survival of fish being returned to the waterbody.
These recommendations include:
- 1. Maintain sufficient water levels and velocities to expedite return.
- 2. Avoid hydraulic turbulence in the conveyance wherever possible.
- 3. Prevent ice formation in the conveyance in cold weather.
- 4. Maintain smooth surfaces in the conveyance.
- 5. Enclose the conveyance to minimize avian predation.
- 6.
Consider multiple release locations to minimize predation at the outfall.
- 7.
Prevent re-entrapment.
- 8. Avoid thermal shock.
- 9.
Separate debris sluiceways from fish sluiceways.
Because sluiceway and pipeline returns are usually part of a physical barrier technology and an intake design technology, their implementation must be considered on a site-specific basis. *The existing fish return system at Salem and potential modifications to it are discussed in Sections 8.2 and 8.5 of the Demonstration.
XIII.6.3.3 Fish-Pump Systems Fish-pump removal systems have been developed in response to entrapment problems in which fish are known to be concentrated in a confined area of,the intake structure and are susceptible to removal using a pump system.
The first application of a fish-pump removal system at a power plant intake occurred at the Contra Costa Power Plant (Kerr 1953).
Prior to installing the fish pump system, the behavioral responses of fish to various pump collector (intake) designs were tested in a number of velocity gradients.
Based on observations and tests, a zone of fish concentration between the vertical traveling intake screen and a curtain XIII.6-24
Salem 316(b) Demonstration:
Appendix XIII wall was located within the intake structure.
The placement of a large intake collector (similar in design to the inlet of a vacuum cleaner) in the zone of fish concentration, in combination with low suction velocities, resulted in high diversion efficiency and high survival of all species removed from the intake structure.
Kerr estimated the survival of fish following passage through the fish pump system to be greater than 98 percent.
Recent studies of the Contra Costa fish pump system (PGandE 1981) indicate that the number of fish impinged on the power plant intake screens is reduced by approximately 80-98 percent by the fish-pump removal system.
Following passage through the fish pump, initial and latent (96-hour) survival of juvenile striped bass were approximately 100 and 85-95 percent, respectively (PGandE 1981).
Pres-ently available data indicate that the fish-pump systems at the Contra Costa Power Plant effectively reduce the numbers of fish impinged while main~aining high survival of those fish returned to the receiving water-body.
Some problems have been encountered with maintenance and with loss of pump prime at yery low tides.
Other fish-pump installations have had mixed success.
Studies of the Monroe Nuclear Generating Station estimate rem.oval efficiencies of 52-99 percent and gizzard shad survival of 10-99 percent (Cannon et al. 1979).
- Southern California Edison reports a lack of success at its Huntington Beach and El Segundo gererating stations (Stipanov 1976).
Mussalli and Taft (1977, cited in Cannon et al. 1979) have investigated the use of jet pumps as en alternative to either single-port or dual-port centrifugal pumps for use in a fish-removal system.
Based on results of laboratory testing, a peripheral-type jet pump fish-return system has been designed for inclusion into the intake structures of the Nine Mile Point Nuclear Station Unit 2 and Oswego Steam Station Unit 6, both located on Lake Ontario.
Available data indicate that fish pump return systems may substantially reduce the entrapment and impingement of fish at many cooling water intake structures, but data are insufficient to permit evaluation of the conflicting nature of many of the findings.
Additional research is needed to identify the specific behavioral responses of fish, which can be used to concentrate organisms within a confined area of an intake structure, and the design parameters for a fish pump system, which will minimize fish mortality during removal from an intake.
Accordingly, such systems are not yet sufficiently developed to warrant further consideration for use at Salem.
XIII.6.3.4 Fish Basket Collectors Testing of fish basket collectors has been conducted at the Alden Laboratory (Stone and Webster Engineering Corporation 1975) and at the Redondo Beach test facility* of the Southern California Electric Company (Schuler and Larson 1975).
In both series of tests, a fish basket col-lector provided acceptable removal of fish.
A full-scale fish basket collector has been developed and is being tested for use at the San Onofre Nuclear Generating Station.
XIII.6-25
Salem 316(b) Demonstration:
Appendix XIII Fish basket collectors are not expected to be effective for all species and sizes of fish.
In addition, the hydraulic conditions within an intake structure, debris loading, and the configuration and design of an intake structure are expected to influence the effectiveness of fish basket collectors for removing entrapped fish.
Fish basket collector systems are not generally applicable to shoreline intake structures and will not be considered further for Salem.
XIII.6.3.5 Fish By-Passes and Escape Channels Two intake structure configurations have been developed which provide by-passes or escape channels to minimize entrapment within the intake structure.
A shoreline intake structure has been designed, and is cur-rently in use at several power plants, in which the vertical traveling intake screens are located flush with the shoreline.
In this shoreline intake configuration, concrete dividing walls between forebays have been eliminated and bar racks have been installed as a cage-type structure on both the front and lateral sides of the intake structure.
The con-figuration allows a lateral flow of water across the face of the intake screens tending to guide entrapped fish away from the intake screens and out of the intake structure.
A second p~oposed intake struc.ture configuration. use~ vertical traveling screens orJ.ented at an angle to. the inflow of water (Section 6.2.10).
The angled intake screens are intended to divert entrapped fish later-ally ac~oos the face of the screen and into a by-pass channel.
This approach combines the advantages of intake screening with the diversion capability typical of louver intake structures.
Results of prototype testing (Taft and Mussalli 197 8) indicate that high diversion efficiencies and survival rates of fish diverted by angled screens are possible.
At present, however, no full-scale tests have been conducted to evaluate the efficiency of angled intake screens under field operating conditions.
One aspect of the use *of angled screens to divert fish into a by-pass which requires detailed consideration is the hydraulic flow pattern associated with the by-pass.
Concentration of fish in a by-pass channel requires a nonturbulent flow in order to guide fish into the by-pass.
Backflows, eddies, and rapid changes in velocity of the water approach-ing a by-pass will stimulate avoidance in fish, which interfere with their transit past the intake screens and into the by-pass.
A gradual acceleration of flow in the direction of the by-pass provides the optimal hydraulic conditions for fish diversion (Taft et al. 1976).
The performance of shoreline intake structure with fish escape chan-nels has been demonstrated at power plant intakes.
The angled-screen diversion appears promising based on prototype evaluations; however, full-scale operation under field conditions is needed to confirm the effectiveness of diverting entrapped fish.
The use of fine-mesh screen material on an angled-screen diversion may not be effective in diverting
-larval fish (McGroddy et al. 1981). Angled-screen diversions can be made applicable for use in either offshore intake structures with a fish-return system, or in shoreline intake structures.
XIII.6-26
Salem 316(b) Demonstration:
Appendix XIII Unidirectional flow past the screen is required for effective diversion of fish.
To achieve this in tidal waters such as at Salem would require placement of such a screen recessed in a constructed channel so that the circulating pt.nnps behind the screen could induce a unidirectional flow of water through and across the face of the screen.
In effect, all fish that enter such an intake canal have to be induced to move past the screen into a by-pass (or else become impinged) from which they must be removed by pump or other device.
Currently there is no basis for concluding that such an intake would provide biological benefit compared to the existing intake at Salem.
Therefore, no further consideration of this technology is warranted for Salem.
XIII.6-27
Salem 316(b) Demonstration:
Appendix XIII TABLE XIII.6-1 IMPINGEMENT SURVIVAL OF JUVENILE WHITE PERCH UNDER VARIOUS CONVENTIONAL VERTICAL TRAVELING SCREEN OPERATIONAL MODES AND SCREENWASH PRESSURES AT THREE HUDSON RIVER POWER PLANTS DURING NOVEMBER AND DECEMBER 1976 Washwater Survival (%}
Screen Pressure Power Plant Operational Mode (psi}
Initial Long-Term Ros et on Continuous 50 98 44 100 79 6
2-hr intermittent 50 96 8
100 92 5
4-hr intermittent 50 96 17 100 71 0
Danskammer Point Continuous 55-65 82 29 2-hr intermittent 55-65 62 15 Bowline Point Continuous 10-20 98 56 30-50 96 55 2-hr intermittent 10-20 90 26 30-50 90 32 4-hr intermittent 10-20 75 19 30-50 69 19 (a)
Long-term survival at Roseton and Danskammer Point determined 84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> after impingement; at Bowline Point, 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> after impingement.
Source:
King et al. 1978.
(a)
TABLE XIII.6-2 INITIAL AND LONG-TERM IMPINGEMENT SURVIVAL (JF YOUNG-OF-THE-YEAR AND YEARLING FISH IMPINGED ON A CONTINUOUSLY ROTATING FINE-MESH (2.5-mm) MODIFIED VERTICAL TRAVELING SCREEN Tax on Age( a)
Number Survival (%)
Common Name Scientific Name Class Collected Initial 84-hour Striped bass Morone saxatilis 1
13
- 85.
75 White perch Morone americana 1
223 45 26 en White perch Morone americana 2
37 41 18 Ill Atlantic tomcod Microgadus tomcod 1
78 92 58 m
Atlantic tomcod Microgadus tomcod 2
2 100 100 w....
Blueback herring Alosa aestivalis 1
509 93 19 0\\ -
Blueback herring Alosa aestivalis 2
1 100 0
c' Bay anchovy Anchoa mitchilli 1
2,415 25 1
Bay anchovy Anchoa mitchilli 2
65 55 13 t:i m
Alewife Alosa pseudoharengus 1
107 69 6
0 American shad Alosa sapidissima 1
4 100 0
i:s tll Hogchoker Trinectes maculatus 1
4 100 100 r-t t;
American eel Anguilla rostrata 2
4 100 100 Ill r-t Banded killifish Fundulus diaphanus 1
1 100 0
White catfish Ictalurus catus 1
27 100 100 i:s Spottail shiner Notropis hudsonius 1
2 100 100 Sea lamprey Petromyzoa marinus 1
1 100 100 "d
Largemouth bass Micropterus salmoides 1
1 100 100 "d
!I>
Yellow perch Perea flavescens 1
1 100 100 i:s p..
Weakfish Cynoscion regalia 1
3 67 67
~
Bluefish Pomatomus saltatrix 1
4 100 0
~
Rainbow smelt Osmerus mordax 1
20 10 0
H H
Rainbow smelt Osmerus mordax 2
4 25 0
H (a) Age-class:
1 = young of the year; 2 = yearling or older.
Note:
(--) indicates no data available.
Source:
Texas Instruments 1977.
TABLE XIII.6-2 (Page 2 of 2)
Taxon Age Common Name Scientific Name Class(a)
Menhaden Brevoortia spp.
1 Gizzard shad Dorosoma cepedianus 2
Unid. clupeids Clupeidae 1
Centrarchids Centrarchidae 1
Northern pipefish S:yngnathus fuscus 1
Number Collected 1
5 80 5
1 Survival (%)
Initial 84-hour 100 100 51 100 0
0 100
' t:::I
. ID s 10
'j:j
. en rt
- 11 I IU i rt 10
. j:j "d
'"d
. ID
- j:j
!~
- M H
H H
Original Intake Vertical flow traps fish Public Service Electric and Gas Company Salem 316(b) Demonstration Capped I ntal<e High velocity horizontal flow scares fish Schematic Representation of an Offshore Intake with Velocity Cap (Weight 1958)
Fig1.ire XII 1.6-1
-~ONO lUVATIOH
. L.AlCt -
I C:JHTUI LIN Io* I IHTAl(l C:lll&I I..
~""'......
r1./_:;n.::,*_.::.S :_;;..:O:_* _
t T
I I
I i
t 1
n.o.o-AVllAGt I
ft I
i
!T jl
~ I WA?lll LIVU.
I I I
I
~
u
~
I ii I
I
- ~
- o* !HTAKI l'll't If 1" _,,__
1 QUAR.llT STONl f
'I l
I
- f ii' U I SC:lUfH OVH
~---?!' **1---;;;J
"! " =o--**-**r-1';( ""' IHO 1~--
"---. -rr--nl.
~;:.-~-;;,. 'I... ***.*c.. :~I~!..... s...,.-.... 1
, *_.-~~~.1.. s_r~,'~::n:~.;
I
- .:*.. ::,'. f:".':::.-":~ *::-::-i*-:*:'~.;*:.1:.:.~
I I
......... (f:/:;.
- :**=.***.-..... -.-=:-*.*.*:
I' ---11!
- ).....
I I
. *.:I I
--i~
ra'-o" INT.AKI "'"'~
w Public Service Electric and Gas Company Salem 31 S(b) Demonstration Intake Structures Using Porous Dike Design Concepts 1 Figure XI 11.6-2
I
,...._~~...__.__,__,__._,FLOW..
-~
r2.3r~
mlot,.dth 1.0 Section A-A Material: Stainless Steel Slot widths: 1.0-2.5 mm Open area: 22.3-39.5%
Dimensions (mm)
Public Service Electric and Gas Company Characteristics of Flat Wedge-Wire Screen Panels Used in the TVA Hydraulic Test (Cada et al. 1979)
Salem 316(b) Demonstration Figure XII 1.6-3
Public Service Electric and Gas Company Salem 316(b) Demonstration A Design Concept for Cylindrical Wedge-Wire Screens at Power Plant Cooling Water Intakes (Cada et al. 1979)
Figure XII 1.6-4
Public Service Electric and Gas Company Salem 316(b) Demonstration Horizontal Traveling Screen (Courtesy of Envirex)
Figure XII 1.6-5
I I
I I
/
I Public Service Electric and Gas Company Salem 316(b) Demonstration
/
""" \\
\\
\\
I I
Centerflow Traveling Screen (Courtesy of Passavant Corporation)
Figure XII 1.6-6
Public Service Electric and Gas Company Salem 316(b) Demonstration Double-entry/single-exit screen (Courtesy of FMC Corporation)
Figure Xlll.6-7
Public Service Electric and Gas Company Salem 316(b) Demonstration Conventional Vertical Traveling Screen (Courtesy of Envirex)
Figure XI 11.6-8
LOW PRESSURE FISH WASHING SYSTEM Public Service Electric and Gas Company Salem 316(b) Demonstration SID£ ElfVATIOH ASH SCREEN Ristroph Modified Traveling Screen With Fish Buckets, a Modified Spray System, and a Sluiceway for Fish (Courtesy of Envirex)
Figure XI 11.6-9
100 80 co 60
- J
(/)
Cl>
Cl t'O c:
Cl>
40 u
Cl>
a...
Public Service Electric and Gas Company Salem 316(b) Demonstration 6
12 18
- = Continuous Wash (n = 107) 0 = 2-Hour Hold (n = 28)
A = 4-Hour Hold (n = 62)
I = +/-1 Standard Deviation 36 84 Time Since Collection (hours)
Probability of Surviving Impingement for Young-of-the-Year White Perch and Atlantic Tomcod Collected at the Danskammer Point Plant Figure Xlll.6-10
Salem 316(b) Demonstration:
Appendix XIII XIII.7 INTAKE MAINTENANCE AND OPERATION Operational modifications of power plant cooling systems to reduce entrainment and impingement losses focus on reducing the exposure of organisms to physical, chemical, and thermal stresses.
Physical stresses result when an organism is impinged on intake screens or when an entrained organism is exposed to shear and pressure forces or mechanical abrasion during cooling system transit. Physical stresses may be reduced by maintenance dredging in front of the intake to keep approach velocities low, or by reducing the volume of cooling water used.
Cooling water volume reduction can be achieved by limiting the operation of circulating water pumps or by curtailing cooling system operation and, thus, electrical generation.
At the present time, insuf-ficient quantitative data are available to specify design parameters for cooling system components such as circulating water pump impellers which can assure reduction of the physical stress on entrained organisms.
Chemical stresses on entrained organisms result primarily from exposure to biocides used in cooling systems to control biological fouling.
Operational modifications to reduce chemical stresses on entrained organisms focus primarily on minimizing the frequency, duration, and concentration of chemicals used for biofouling control.
Thermal stresses on entrained organisms result from exposure to elevated temperatures in the condensers and cooling water discharge.
Operational modifications to minimize thermal stresses on entrained organisms focus on minimizing the temperature elevation (delta-T) and time of exposure during cooling system transit.
XIII.7.1 DREDGING Sediment transport, sediment deposition, and littoral drift are fre-quently encountered in the vicinity of an intake structure.
Such deposition may increase approach velocities.
Dredging may generally represent a simple and cost-effective means of* reducing physical stres-ses on aquatic organisms by helping to achieve design velocities and maintain uniform velocity gradients.
Complete discussion of this alternative appears in Section 8.3 of the Demonstration Document.
XIII.7.2 REDUCING CIRCULATING WATER FLOWS Reduction in the number of circulating water pumps in operation is a possible method for reducing cooling water volume and intake approach velocities and hence reducing the rate of entrainment and impingement.
A reduction in cooling water flow rate during full-load generation would result in losses in both generating capacity and thermal transfer ef fic-iency, with losses more significant at higher ambient inlet water tem-peratures.
Increases in condenser backpressure resulting in reduced turbine cycle thermal efficiency, and increased temperature differen-tials through the condenser system (delta-T) will occur when cooling water flow rates are reduced during generation.
Although a reduction XIII.7-1
Salem 316(b) Demonstration:
Appendix XIII in cooling water volume would be expected to result in a decrease in the number of entrained organisms, the associated increase in delta-T may substantially reduce the survival of those organisms that are entrained.
The biological effectiveness of reducing entrainment and impingement losses by reducing the volume of cooling water withdrawn cannot be completely examined within the scope of this appendix.
Quantitative information is needed on the relative contribution of physical stresses and thermal stresses for each species and life stage being considered before the benefits of reduced losses resulting from reduced cooling water volume can be determined.
Insufficient data are available to optimize the balance between cooling water volume and delta-T for most power plants and fish species.
The regulation of cooling system volume and delta-T becomes increasingly complex when a diverse array of species and life stages, each with individual and unique tolerances to physical and thermal stresses, are present at an intake simultaneously.
In addition, during those periods when the delta-T and absolute discharge water temperture exceed the upper lethal limit for thermal tolerance of a species, it may be desir-able to increase the volume of cooling water and thus decrease the dis-charge water temperat~Jre below a lethal limit.
The alternative approach of reducing cooling w~ter volume to a minimum and increasing the delta-T above the thermal tolerance of a species may result in an absolute increase in th~ total number lost from the populaton.
The biological complexities of cooling system operational modifications are compounded by engineering constraints.
Circulating water pumps, typically,. d*o not have the capability to be throttled or regulated.
In addition, reducing the volume of cooling water reduces the thermal efficiency of the cooling system, resulting in decreased generating capacity of the unit. Therefore, considerations of reduced generation in perspective with electrical demand are needed on a site-specific basis for a specific period of time.
This information is developed in detail in Section 8.7 of the Demonstration.
XIII.7.3 CURTAILING PLANT OPERATION Entrainment and impingement losses of aquatic organisms at a power plant can be entirely eliminated by shutting down a particular unit or units.
Cooling system shutdown, however, also curtails electrical generation and hence involves implications of cost and of reduced system.wide capa-bility for meeting electrical demand.
Cooling system curtailment may be feasible if the seasonal period of maximum abundance of a critical species is short and coincides with a period during the year when electrical generating capacity ex~eeds demand~ The cost implications. from loss of generation, electrical transmission from alternative sources, and availability of alternative sources of electricity must be evaluated on a site-specific basis.
Coordinating plant activities, such as scheduled outages for maintenance or refueling, with periods of high organism densities could also be considered.
XIII. 7-2
Salem 316(b) Demonstration:
Appendix XIII Coordinating cooling system curtailment with periods of highest abun-dance of a critical species requires an ongoing biological monitoring program at each site to identify the period of maximum abundance.
Coordinating scheduled outages with the temporal distribution of a particular species is also difficult in that outages require precise scheduling, generally months in advance, while the temporal pattern of species abundance may not be as predictable as necessary.
The feasibility of curtailing cooling system operation to minimize biological losses must be examined on a site-specific and species-specific basis, as is done in Section 8.6 of the Demonstration.
XIII.7.4 BIOFOULING PROCEDURES Schubel and Marcy (1978) have made the following recommendations for minimizing mortality associated with chemical stresses (most commonly from chlorine) during treatment to kill or remove biofoulers.
- 1. Chlorinate intermittently.
- 2. Reduce the concentration of free chlorine to the lowest possible level.
3, Minimize transit time through the cooling system and thus exposure to the bioc.ide.
- 4. Maximize the rate of dilution of the discharge water.
The use of alternative biocidal agents does not appear to be an ef fec-tive method of minimizing mortality of nontarget entr.aiiled organisms.
Mechanical fouling control techniques have not proven to be completely effective in controlling fouling accumulations in power plant cooling systems.
Better management of chemical biocide use is generally required.
Since optimal biofouling procedures are already in effect at Salem, this alternative will not be discussed further.
XIII.7.5 MODIFYING COOLING WATER SYSTEM COMPONENTS Structural modification of cooling system components in an attempt to reduce the mortality of entrained organisms is not effective given the present state of knowledge.
Insufficient quantitative data are avail-able to isolate specific sources of mortality within a cooling water system.
Design parameters for specifying pressure regimes, circulating water pump design and operation (e.g., rpm, impeller design), tolerable shear stresses, and cooling system designs for minimizing mechanical abrasion have not been developed.
Structural modifications have focused on the design and operation of intake structures, with particular emphasis on intake screening systems, which will reduce stresses imposed on impinged organisms (Appendix Section XIII.6.2).
To date, greater effort has been devoted to develop-ing methods for excluding fish eggs and larvae from cooling systems than on developing specific criteria for structural modifications which would reduce stresses imposed on entrained organisms.
XIII. 7-3
Salem 316(b) Demonstration:
Appendix XIII XIII.7.6 REGULATION OF THERMAL ELEVATIONS (delta-T)
To minimize mortality of entrained organisms resulting from thermal stress, Schubel and Marcy (1978) recommend that a once-through cooling system be operated in such a way that:
- 1. The minimum delta-T is used that is technologically practicable, based on cooling system design and load.
At Salem the design temperature rise is in the range of 8-12oc.
- 2. Transit time through the cooling system is minimized.
This is the case at Salem where the transit time is 6-8 minutes.
- 3. The cooling water is discharged in a way that will promote rapid mixing and dilution.
This is achieved at Salem with an exit velocity of 10 fps at the point of discharge back to Delaware River.
Regulation of thermal elevations requires the integration of information on plant generating loads and delta-T, and species-and size-specific thermal tolerance data for evaluating the effectiveness of various cool-ing system operating modes for reducing entrainment losses.
The recom-mended conditions for minimizing mortality of entrained organisms are already in effect at Salem, so this matter is discussed in conjunction with the examination of potential flow-reduction options in Section XIII.7.2 of this Appendix.
XIII.7-4
Salem 316(b) Demonstration:
Appendix XIII XIII.8 CONCLUSION Based on the foregoing discussions, the following alternatives deserve further consideration, either singly or in combination, as candidates for use or continued use at Salem:
- 1. Retaining the current Ristroph traveling screens, fish-return system, and planned outage schedule
- 2.
Dredging
- 3. Installing fine-mesh screens
- 4.
Improving the CWS fish-return system
- 5. Revising planned outage schedules 6'.
Reducing flows
- 7. Increasing CWS intake size
- 8. Installing Passavant or Cogenel intake and screens
- 9. Retrofitting closed-cycle-cooling
- 11.
Building a second intake Each of these alternatives is detailed in Section 8 of the Salem Demonstration.
XIII.8-1
Salem 316(b) Demonstration:
Appendix XIII LITERATURE CITED:
APPENDIX XIII Alden Research Laboratory (ARL).
1974. Hydraulic model study, Beloit-Passavant traveling screen, circulating water pump structure.
Prepared for Long Island Lighting Company and Stone and Webster Engineering Corporation.
Rep. 70-74/MlORF.
ARL, Holden, Mass.
Alevras, R.A.
1974.
Status of air bubble fish protection system at Indian Point Station on the Hudson River, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.),
pp. 289-291.
PRI Publ. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
American Society of Civil Engineers (ASCE).
1982.
Design of Water Intake Structures For Fish Protection.
ASCE, 345 East 47th St.,
New York, p. 163.
Applegate, V.C., P.T. Macy, and V.E. Harris.
1954.
Selected bibliography on the applications of electricity in fishery $Cience.
USFWS, Spec. Sci. Rep. Fish.
127 pp.
Bates, D.W. and S.G. Jewett, Jr. 1961. Louver efficiency in deflecting downstream.migrant steelhead.
Trans. Am. Fish. Soc. 90(3):336-337.
Bates, D.W.
1964.
Exploratory research on guiding juvenile salmon, in U.S. Bur. Commer. Fish., Fish-Passage Program, Review of Progress 1964, Vol. III. Seattle.
Bates, D.W. and J.G. VanDerwalker.
1964.
Exploratory experiments on the deflection of juvenile salmon by means of water and air jets, in U.S. Bur. Commer. Fish, Fish-Passage Research Program, Review of Progress 1964, Vol. III. Seattle.
Bates, D.W.
1969.
The horizontal traveling screen, in Engineering Aspects of Thermal Pollution (F.L. Parker and P.A. Krenkel, eds.), pp.
225-242.
Proceedings of the National Symposium on Thermal Pollution, Nashville, Tennessee, 14-16 August, 1968.
Vanderbilt Univ. Press, Nashville.
Bates, D.W., E.W. Murphey, and E.F. Prentice, 1970.
Design and operation of a cantilevered traveling fish screen (Model V), in Preliminary Designs of Traveling Screens to Collect Juvenile Fish, pp. 6-15.
USFWS, Spec. Sci. Rep. Fish.
Bates and Vinsonhaler.
1957.
Use of louvers for guiding fish.
Trans.
Am. Fish. Soc. 86:38-57.
Benes, P. 1978.
Personal communication.
Passavant Corporation, Birmingham, Ala.
Salem 316(b) Demonstration:
Appendix XIII Bibko, P.N., L. Wirtenan, and P.E. Kueser.
1974.
Preliminary studies on the effects of air bubbles and intense illumination on the swinnning behavior of the striped bass (Morone saxatilis) and the gizzard shad (Dorosoma cepedianum), in Proceedings of the second workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 293-304.
EPRI Publ. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
Brett, J.R. and D. MacKinnon.
1953.
Preliminary experiments using lights and bubbles to deflect migrating young spring salmon.
J. Fish.
Res. Board Can. 10(8):548-559.
Brett, J.R. and D.F. Alderdice.
1958.
Research on guiding young salmon at two British Columbia field stations.
Bull. Fish. Res. Board Can.
117.
Browne, M.T.
1980.
Progress report on profile wire intake screen testing--Forked River, New Jersey, pp. 27-38.
Passive Intake Screen Workshop, 4-5 December 1979, Chicago, Illinois, p *. 184.
Burner, C.J. and H.L. Moore.
1962.
Attempts to guide small fish with underwater sound.
USFWS, Spec. Sci. Rep. Fish. 403.
Cada, G.F., J.B. Cannon., and D.W. Le*e.
1979. Alternative screening devices at Indian Point Units 2 and 3, Bowline Point, and Roseton generating stations.
Testimony prepared for Hudson River NPDES case before the U.S. Environmental Protection Agency, Region II.
EPA Docket No. C/II-WP-77-01.
California Public Utilities Commission.
1978.
Decision against Application 57626.
Joint Western LNG Terminal Associates, Pacific Gas and Electric Company, and Pacific Lighting Service application to construct and operate an LNG terminal at Point Conception.
Filed 14 October 1977.
Interim Order No. 89177.
Decision date 31 July 1978.
Cannon, J.B., G.F. Cada, K.K. Campbell, D.W. Lee, and A.T. Szluha.
1979.
Fish protection at steam-electric power plants:
alternative screening devices.
Prepared for the U.S. Nuclear Regulatory Commission, Division of Site Safety and Environmental Analysis,. and the U.S. Environmental Protection Agency, Region II. Contract No.
W-7405-eng-26.
Oak Ridge National Laboratory, Oak Ridge, Tenn.
Clay, C.H.
1961.
Design of fishways and other fish facilities.
Dep. Fish. Canada, Ottawa.
Cook, L.E.
1978. The Johnson screen for cooling water intakes, in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 149-157.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Salem 316(b) Demonstration:
Appendix XIII Ecological Analysts, Inc. (EA).
1979.
Evaluation of the effectiveness of a continuously operating fine-mesh traveling screen for reducing ichthyoplankton entrainment at the Indian Point Generating Station.
Prepared for Central Hudson Gas and Electric Corporation, Consolidated Edison Company of New York, Inc., Orange and Rockland Utilities, Inc.,
and Power Authority of the State of New York.
EA, Middletown, N.Y.
Eicher, G.J.
1974.
Adaptation of hydro-fish facilities to steam-electric stations, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 273-276.
EPRI Publ. 74-049-00-5.
Electric Power Research Institute, Palo Alto, Calif.
Elliott, F.E.
1970.
On the status of electric fishing.
Mar. Technol.
Soc. J. 4(1):58-60.
Environmental Protection Agency (EPA).
1976.
Development document for best technology available for the location, design,. construction and capacity of cooling water intake structures for minimizing adverse environmental impact.
EPA 440/l-76/015a.
U.S. EPA, Washington, D.C.
Environmental Protection Agency (EPA).
1977.
Guidance for evaluating the adverse impact of cooling water inta!te structures on the aquatic environment:
section 316(b) P.L.92-500. Draft.
U.S. EPA, Office of Water Enforcement, Permits Division, Industrial Permits Branch, Washington, D.C.
Erkkila, L.F., J.W. Moffett, O.B. Cope, B.R. Smith, and R.S. Nielson.
1950.
Scaramento - San Joaquin Delta fishery resources:
effects of Tracy Pumping Plant and Delta Cross Channel.
USFWS., Spec. Sci *. Rep.
Fish 56.
Farr, W.E. and E.F. Prentice.
1974. Mechanical operation of horizontal traveling screen model* VII, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 215-222.
EPRI Publ. 74-049-00-5.
Electric Power Research Institute, Palo Alto, Calif.
Fields, P.E.
1966.
Final report on migrant salmon light guiding studies (Contract No. D.A.-45-108 CIVENG-63-29) at Columbia River dams.
U.S. Army Corps of Engineers, North Pacific Division, Fisheries Engineering Research Program, Portland, Ore.
Fisher, F.W.
1978.
Retention of young king salmon, American shad, and striped bass by perforated plate and woven wire screens.
Calif. Dep.
Fish Game, Anad. Fish. Branch.
Gerold, M. and K. Niggol.
1964.
Comparative response of blinded and non-blinded fingerling salmon to a louver barrier and to a sharp increase in water velocity, in U.S. Bur. Commer. Fish., Fish-Passage Research Program, Review of Progress 1964, Vol. III. Seattle.
Salem 316(b) Demonstration:
Appendix XIII Gulvas, J.A~ and I.H. Zeitoun.
1980.
Cylindrical wedge-wire screen investigations in offshore Lake Michigan for the J.B. Campbell Plant, 1979, pp. 39-46.
Passive Intake Screen Workshop, 4-5 December 1979, Chicago~ Illinois, p. 184.
Hanson, B.N., W.R. Bason, B.E. Beitz, and K.E. Charles.
1978.
A practical intake screen which substantially reduces the entrainment and impingement of early life stages of fish, in Fourth National Workshop on Entrainment and Impingement (L.D. Jensen, ed.),
pp. 393-407.
Ecological Analysts, Melville, N.Y.
Heuer, J.B. and D.A. Tomljanovich *. 1978.
A study on the protection of fish larvae at water intakes using wedge-wire screening.
Tennessee Valley Authority, Div. For. Fish. Wildl. Dev., Tech. Note.B26.
Holmes, H.B.
1948 *. History, development, and problems of electric fish screen.
U.S. Fish Wildl. Serv., Spec. Sci. Rep. 53.
Kerr, J.E.
1953.
Studies on fish preservation at the Contra Costa Steam Plant of the Pacific Gas and Electric Company.
Calif. Dep. Fish Game, Fish Bull. 92.
Ketschke, B.A., and R.C. Toner.
1982.
Porous Dike Intake Evaluation.
EPRI CS-2594 project 1181-1.
Ketschke, B.A.
l 98la.
E'ie1d and laboratory evaluation o'f the screening ability of a_porous dike.
pp. 87-94.
Workshop on Advanced Intake.
Technology, San Diego, Ca.
April 22...;.23.
- p. 306.
Ketschke, B.A.
198lb.
Hydraulic performance of a porous dike.
pp.95-104 Workshop on Advanced Intake Technology, San Diego, CA.
April 22-23.
- p. 306.
Key, T.H. and J.C. Miller.
1978.
Preliminary studies on the operating aspects of small slot width wedge-wire screens with conceptual designs for power station use, in Fourth National Workshop on Entrainment and Impingement (L.D. Jensen, ed.), pp. 385-392.
Ecological Analysts, Melville, N.Y.
King, L.R., J.B. Hutchison, Jr., and T.G. Huggins.
1978.
Impingement survival studies on white perch, striped bass, and Atlantic tomcod at three Hudson River power plants, in Fourth National Workshop on Entrainment and Impingement (L.D. Jensen, ed.), pp. 217-233.
Ecological Analysts, Melville, N.Y.
Landry, A.M., Jr. and K. Strawn.
1974.
Number of individuals and injury rates of fishes caught on revolving screens at the P.H.
Robinson Generating Station, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 263-271.
EPRI Publ. 74-049-00-5.
Electric Power Research Institute, Palo Alto, Calif.
l
- r.
Salem 316(b) Demonstration:
Appendix XIII Magliente, S.H., D.A. Tomljanovich, J.H. Heuer, S. Vigander, and M.N. Smith.
1978. Investigations on the protection of fish larvae at water intakes using fine-mesh screening.
Impingement-release concept:
laboratory study of a single-entrance, double-exit, vertical traveling screen concept, in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 69-77.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, February 7-8, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Maxwell, W.A.
1973. Fish diversion for electrical generating station cooling systems:
a state-of-the-art report.
Prepared for Florida Power and Light Company.
Southern Nuclear Engineering, Inc., SNE-123.
- NUS Corporation, Dunedin, Fla.
Mayo, R.D.
1974.
Conventional fish screening systems and some promising alternatives, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 277-279.
EPRI Puhl. 74-049-5. Electric Power Research Institute, Palo Altc, Calif.
McGroddy, P.M., S.J. Edwards, and P. Dorn.
1981. Diversion of marine fish larvae with angled louvers and fine-mesh screens.
pp. 225-234.
Workshop on Advanced Intake Technology, San Diego, CA.
April 22-23 1981.
McGroddy, P.M., S. Petrich, and L. Larson.
1981.
Fouling and clogging evaluation of fine-mesh screens for offshore intakes in the marine environment, pp. 5-21. Workshop on Advanced Intake Technology, San Diego, California, 22-24 April 1981, p. 304.\\
Michaud, D.T.
1981. Wisconsin Electric's Experience with Porous Dike and Leaky Dam Intake Structures on Lake Michigan, pp. 100-114.
Workshop on Advanced Intake Technology" San Diego, 22-24 April 1981,
- p. 306.
Mikels, F.C. and T.W. Bennett.
1978.
Cooling water intakes utilizing Ranney collectors or Ranney intakes, in Larval Exclusion Systems.for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.),
pp. 15-25. Proceedings cf the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-:66.
Argonne National Laboratory, Argonne, 'Ill.
Moore, H.L. and H.W. Newman.
1956. Effects of sound waves on young salmon.
USFWS, Spec. Sci. Rep. Fish. 172.
Moulton, J.M. and R.H. Backus.
1955. Annotated references concerning the effects of man-made sounds on the movements of fishes.
Maine Dep.
Sea Shore Fish., Fish. Circ. 17.
Salem 316(b) Demonstration:
Appendix XIII Moss, S.A., J.G.H. Hoff, and F~X. O'Brien~ 1981.
Forecasting fish entrapment by velocity cap intakes:
a comprehensive approach, in Proceedings of the Fifth National Workshop on Entrainment and Impingement.
(L.D. Jensen, ed.), pp. 183-198. Ecological Analysts, Inc., Sparks, Md.
Murray, L.S. and T.S. Jinnette.
1978.
Survival of dominant estuarine organisms impinged on fine-mesh traveling screens at the Barney M.
Davis Power Station, in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 79-87:
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Mussalli, Y.G. and E.P. Taft.
1977.
Fish return systems.
Presented at the 25th Annual Hydraulics Division Specialty Conference of the American Society of Civil Engineers, 10-12 August, 1977, at Texas A and M University, College Station.
Mussalli, Y.G., J. Williams, and J. Hockman.
1981.
Engineering evalu-ation of a dual-flow mesh traveling screen, pp. 169-182.
Workshop on Advanced Intake Technology, San Diego, California, 22-24 April 1981,
- p. 306.
Niggol~ K.
1964.
Response of juvenile migrants to flow accelerations, in U.S. Bur. Commer* Fish., Fish-Passage Research Program, Review of Progress 1964; Vol. III. Seattle.
Oak Ridge National Laboratory and Atomic Industrial Forum, Inc.
1979.
Impingement:
an annotated bibliography.
Interim report.
EPRI EA-1050, ORNL/EIS-135.
Electric Power Research Institute, Palo Alto, Calif.
Ohio Environmental Protection Agency (Ohio EPA).
1978.
Guidelines for the submittal of demonstrations pursuant to Sections 316(a) and 316(b) of the Clean Water Act and Chapter 3745-1 of the Ohio Administrative Code~ Ohio EPA Division of Industrial Wastewater, Columbus.
Pacific Gas and Electric Company (PGandE).
1981.
Contra Costa Power Plant intake structures 316(b) demonstration.
Prepared by Ecological*
Analysts, Inc.
PGandE, San Francisco.
Page, T.L., R.H. Gray, and D.A. Neitzel.
1976.
Fish impingement studies at the Hanford Generating Project (HGP), December 1975 through April 1976.
Repfort to Washington Public Power Supply System.
Battelle-Northwest, Richland, Wash.
Page, T.L., D.A. Neitzel, and R.H. Gray.
1978.
Comparative fish impingement at two adjacent water intakes on the mid-Columbia River, in Fourth National Workshop on Entrainment and Impingement (L.D. Jensen, ed.), pp. 257-266.
Ecological Analysts, Melville, N.Y.
Salem 316(b) Demonstration:
Appendix XIII Patrick, P.H., and G.L. Vascotto.
1981. Response of Fish to Light.
pp. 252-260, in P.B. Dorn and J.T. Johnson (ed) Advanced intake technology for power plant cooling water systems.
Proceeding of the Workshop of Advance Intake Technology held at the Sheraton-Harbor Island Hotel, San Diego, CA.
April 22-24, 1981.
Prentice, E.F.
1966.
Response of juvenile salmonids to four flow-accelerator wedge geometries.
U.S. Natl. Mar. Fish. Serv., Northwest Fish. Center, Seattle.
Unpublished.
Prentice, E.F. and F.J. Ossiander.
1974.
Fish diversion systems and biological investigation of horizontal traveling screen model VII, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.)t pp. 205-214.
EPRI Puhl. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
Public Service Electric and Gas Company.
1977.
Impingement monitoring program--Salem Nuclear Generating Station Unit No. 1. Report 2.
Docket No. 50-272.
Pugh, J.R.
1962.
Effect of certain electrical parameters and water resistivities on mortality of fingerling silver salmon.
USFS, Fish.
Bull. 62:223-234.
Pugh, J.R., G.E. Monan, and J.R. Smith.
1964. Effect of water velocity on the fish guiding effectiveness of an electric field, in U.S. Bur.
Commer. Fish., Fish-Passage Research Program, Review of Progress 1964, Vol. III. Seattle.
Richards, R.T.
1978.
Engineering considerations in the use of artificial filter beds, in Larval Exclusion Systems of Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 5-12.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Rittenhouse, R.C.
1979.
Power plant cooling systems:
trends and challenges.
Power Eng. 83(8):42-47.
Roberge, J.C.
1978.
An engineering evaluation of porous-dike intake screening systems, in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 37-50.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Robinson, R.E. and M.L. Kitchen.
1981.
Construction and operation of an environmentally permitted once-through cooling system for a 770 MW fossil fueled power plant, pp. 67-74. Workshop on Advanced Intake Technology, San Diego, California, 22-24 April 1981, p. 306
- Salem 316(b) Demonstration:
Appendix XIII Schrader, B.P. and B.A. Ketschke.
1978.
Biological aspects of porous*-
dike intake structures,. in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 51-63.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Schubel, J.R. and B.C. Marcy, Jr., eds.
1978.
Power plant entrainment:
a biological assessment.
Academic, New York.
Schuler, V.J.
1974. Experimental studies in guiding marine fishes of southern California with screens and louvers, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 305-315.
EPRI Puhl. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
Schuler, V.J. and L.E. Larson.
1975.
Improved fish protection at intake systems.
Proc. Am. Soc. Civil Eng., J. Environ. Eng. Div.
10l(EE6):897-910~
Sharma, R.K., E.S. Fritz, and I.P. Murarka.
1981.
Advanced intake technology for cooling water intakes, current status and future direction.
pp. 300-30L Workshop on Advanced Intake Technolgy,
- San Diego, CA.
April 22-23, 1981~ p. 306 Skinner, J.E.
1974. A functional evaluation of a large louver screen installation and fish facilities research on California water diversion projects, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 225-249.
EPRI Publ. 74-049-00-5. Electric Power Research Institute.
Palo Alto, Calif.
Sonnichsen, J.C.
1975.
Fish protective devices:
a compilation of recent designs, concepts, and operating experience of water intakes used in the United States.
Prepared for U.S. Energy Research and Development Administration.
Contract No. AT(45-1)-2170.
HEDL-TME 75-38, UC-79.
Hanford Engineering Development Laboratory, Richland, Wash.
Stamets, L.
1977.
Power plant cooling options for California.
California Energy Resour. Conserv. Dev. Comm., Alternatives Implementation Division, Rep. AID-20A.
Stipanov, J.A.
1976. Investigations into minimizing fish loss at steam electric generating stations, in Report of a Workshop on the Impact of Thermal Power Plant Cooling Systems on Aquatic Environments, Vol. II, pp. 198-218. Electric Power Research Institute, Spec. Rep. 38.
Palo Alto, Cal if.
I I
I I
I I
~-
I II Salem 316(b) Demonstration:
Appendix XIII Stober, Q.J., C.H. Hanson, and P.B. Swierkowski.
1974. A high capacity sand filter for thermal power plant cooling water intakes, part I:
model studies and fouling control techniques, in Proceedings of the Second Workshops on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 317-334.
EPRI Puhl. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
Stone and Webster Engineering Corporation.
1975. First progress report--Indian Point flume st_udy.
Prepared for Consolidated Edison Company of New York, Inc.
Stone and Webster Engineering Corporation.
Prepared for the Utility Water Act Group.
1978.
Ocean-sited plants.
2 vols.
Strandberg, H.V.
1974. A high capacity sand filter for thermal power plant cooling water intakes, part II: design concept, in Proceedings of the Second Workshop on Entrainment and Intake Screening (L.D. Jensen, ed.), pp. 335-343.
EPRI Puhl. 74-049-00-5. Electric Power Research Institute, Palo Alto, Calif.
Taft, E.P., P. Hofmann, P.J. Eisele, and T. Horst.
1976.
An experimental approach to ihe design of systems for alleviating fish impingement at existing and proposed power plant intake structures, in Third National Workshop on Entrainment and Impingement (L.D. Jensen, ed.), pp. 343-365. Ecological Analysts, Melville, N.Y.
Taft, E.P., T.J. Horst, and J.K. Downing.
1981.
Biological evaluation of a fine-mesh traveling screen for protecting organisms, pp. 159-168.
Workshop on Advanced Intake Technology, San Diego, California, 22-24 April 1981, p. 306.
Taft, E.P. and Y.G. Mussalli.
1978.
Angled screens and louvers for diverting fish at power plants.
Proc. Am. Soc. Civil. Eng.,
J. Hydraul. Div. 104(HY5):623-634.
Texas Instruments Incorporated (TI).
1977. Initial and extended survival of fish collected from a fine-mesh continuously operating traveling screen at the Indian Point Generating Station for the period 15 June - 22 December 1977. Draft.
Prepared for Consolidated Edison Company of New York, Inc.
TI, Dallas.
Tomljanovich, D.A., J.H. Heuer, and C.W. Voigtlander.
1977.
Investiga-tions on the protection of fish larvae at water intakes using fine-mesh screening.
Tennessee Valley Authority, Div. For. Fish. Wildl.
Dev., Tech. Note B22.
Tomljanovich, D.A., J.H. Heuer, and C.W. Voigtlander.
1978.
Investiga-tions on the protection of fish larvae at water intakes using fine-mesh screening, in Larval Exclusion Systems for Power Plant Cooling Water Intakes (R.K. Sharma and J.B. Palmer, eds.), pp. 125-139.
Proceedings of the workshop held at Shelter Island Inn, San Diego, California, 7-8 February, 1978.
NUREG/CP-002, ANL/ES-66.
Argonne National Laboratory, Argonne, Ill.
Salem.316(b) Demonstration:
Appendix XIII Trefethen, P.S.
1955. Exploratory experiments in guiding salmon fingerlings by a narrow D.C. electric field.
USFWS, Spec. Sci. Rep.
Fish. 158.
Trefethen, P.S.
1968. Fish-passage research:
review of progress, 1961-66.
USFWS, Circ. 254.
University of Michigan.
1982.
Evaluation of the Unit 3 Wedge-Wire Screens in Lake Michigan at the James H. Campbell Plant, 1981.
Prepared for Consumers Power Company.
319 pp.
VanDerwalker,
- J.
1964~ Studies of the response of fish to low frequency vibrations.
U.S. Bur. Commer. Fish., Fish-Passage Research Program, Review of Progress 1964., Vol. III.
Seattle.
Walker, W.F. and M. Kamata.
1979.
Hydrodynamic evaluation of traveling water screens.
Final report.
Submitted to Royce Equipment Company.
Rice Engineering Design and Development Institute.
Weight, R.H.
1958.
Ocean cooling water system for 800 MW power station.
Proc. Am. Soc. Civil Eng., J. Power Div. 84(P06):1888 1888-22.
White, J.C., Jr.
1976.
Personal communication.
Fishery Biologist, Virginia Electric and Po~er Company, Richmond, Va.
White, J.C., Jr. and M.L. Brehmer.
1976.
Eighteen-month evaluation
- of the Ristroph traveling fish screens, in Third National Workshop on Entrainment and Impingement (L.D. Jensen, ed.), pp. 367-380.
Ecological Analysts, Melville, N.Y. *