ML18092A194

From kanterella
Jump to navigation Jump to search
Forwards Four Revised Oversize Drawings Indicating Mod to Circuit Design to Extinguish Red Light Upon Loss of 125-volt Dc Power.Aperture Cards Are Available in PDR
ML18092A194
Person / Time
Site: Salem  PSEG icon.png
Issue date: 06/07/1984
From: Liden E
Public Service Enterprise Group
To: Varga S
Office of Nuclear Reactor Regulation
References
NUDOCS 8406120380
Download: ML18092A194 (4)


Text

I*

Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department June 7, 1984

u. s. Nuclear Regulatory Commission Off ice of Nuclear Reactor Regulation Division of Licensing Washington, D. C.

20555 Attention:

Mr. Steven A. Varga, Chief Operating Reactors Branch, No. 1 Gentlemen:

AUTOMATIC SHUNT TRIP MODIFICATION SALEM GENERATING STATION UNITS NO. l AND 2 DOCKET NOS. 50-272 AND 50-311 Our letter dated March 14, 1984, forwarded for your approval our plant specific design description of the subject modification.

During recent telephone discussions between Mr. T. Dunning of your staff and Messrs R. Beckwith and M.

Morroni of PSE&G, a concern was identified regarding the Bailey Control Module indication.

If 125VDC power were lost, the Bailey red light indicating breaker closed would remain lit following a plant trip via the breaker UV device.

As a result of our discussions with Mr. Dunning, we have revised the circuit design to extinguish the red light upon loss of 125 VDC power.

Attached~~are the revised prints incorporating this modification.

By this letter, as discussed with Mr. Dunning, we are also requesting approval to temporarily install a substitute relay for the Westinghouse recommended relay.

We are proposing to temporarily replace the recommended relay with a Struthers Dunn 219 frame relay.

The Westinghouse relays are not scheduled for delivery until August, 1984~ thus, installation of the automatic shunt trip feature in Unit 1 could not be completed during the present refueling outage.

,----~a=-4:-o-6_1_2_03808406()7------

~ 0 4*

ol~

~DR ADOCK 05000272

! A '

-:- ~. /.

~

PDR 1tf)f IJ.r J

'Al""

  • 1d:
  • ()~~II (

The Energy People 11 r!rc;}~

95-2168 (75M) 12-83

Mr. Steven 6/7/84 The Struthers Dunn 219 frame relays have been seismically qualified by PSE&G and by design would be located in a benign environment.

Attached, is the manufacturers catalogue sheet and a letter certifying coil current requirements.

The Struthers Dunn relays would be replaced once the Westinghouse relays are received and plant conditions permit installation.

Please contact us if we can be of further service.

Attachment c

Mr. Donald C. Fischer Licensing Project Manager Mr. James Linville Senior Resident Inspector Sincerely, E. A. Liden Manager -

Nuclear Licensing and Regulation att.

II

STRUTHERS-DUNN,. INC.

PITMAN, NEW JERSEY 08071 Manufacturers of Relays and Solid State Controls Telephone:609*589*7500 TWX=510*686-7510 Public Service Electric & Gas Corp.

Nuclear Department TB002 P.O. Box 236 Hancocks Bridge, N.J.

08038 Attention:

Mr. Mike Morroni September 30, 1983

Subject:

Coil Characteristics of Type 219 Relays

Dear Mr. Morroni:

The 48VDC coil type 219 series relay has a nominal cold resi.stance of 975 ohms.

By calculation, this would mean a cold current draw of 49 milliamps.

In general, DC versions of this relay draw approximately 80 percent of the cold current when hot.

If this holds true for the 48VDC version, the hot current draw would be 39 milliamps.

Maximum continuous over voltage is 110%.

The coils will withstand 115% intermittantly without damage.

All other specifications as shown in our current general catalog would apply to 48VDC versions of this relay.

We appreciate your continued interest in Struthers-Dunn products.

If we can be of any further assistance, please let us know.

TRM:blt cc:Home Office Very truly yours, STRUTHERS-DUNN, INC.

affey, Sales Engineer
  • . ~*... :

" *A<>

S-D 10-AMP 12-PIN & 14-PlN

  • Gold diffused SCO contacts
  • 1 O Amp Rating
  • Up to 6 poles
  • U.L. white card listed File #E13224
    • c.s.A. Listed File-9494 T*;pe 219 general purpose relays are available with contact
:~iigurations from DPDT to 6PNO. Models with DPDT con-

. ~::s plug into 12-pin sockets, and 4PDT or 6PST models plug

-:;; 1J-pin sockets. The relays are rated at 10 amps, and are

.;.a1iable in most coil voltages from 6 to 240 Vac and 6 to 125 MODELS AVAILABLE:

12-PIN CONTACTS 14*PIN CONTACTS 219BBXP 219XBXP

~* ~..\\BAP COILS:

DPDT + 2 NO DPDT DPDT + 1 NO

&1NC 219XDXP 219FXXP 219DXBP 4PDT 6PNO 4PNO + 2 PNC AC RELAYS, 50*60 Hz, 5 VA (Coil data at 60Hz)

Voltage 6

12 24 120 240 Milliamperes open closed 1500.

800.

750.

410.

375.

200.

75.

40.'

32.
17.

Impedance Ohms 7.2

27.

120.

2700.*

13,400.

Resistance Ohms 1.1 4.2 15.5 540.

1815 DC RELAYS, 1.SW Voltage 6

12 24(28).

32 "15(125).

Milliamperes Cold Hot 385 304 189 147 96 77 86 67, 20

16. '> ~>

Resistance Cold, Ohms 15.5 63.5 250.

375.

6200 '*

  • NOTE: Stock 24 Vdc and 115 Vdc relays have nameplates stamped 24-28 Vdc and 115-125 Vdc respectively. These relays c::ierate at 80% of the lower voltages and operate within allowable temperature rises at the higher voltages..

MIN. OPERATE:

AC -

85% nominal voltage DC -

80% nominal voltage CONTACT RATINGS:

Break Volts Make Carry Resist Induct t 24ac 30 120ac 30 240ac 30 28dc 30 125dc 30 GENERAL SPECIFICATIONS:

Insulation:

Dielectric:

Operate Time:

Release Time:

Ambient Temperature Range:

Life Expectancy:

Cover:

Sockets:

10 10 10 10 10 10 10 5

10 0.5 10 3

1 3

0.1 t inductive load is defined as other relay coil loads.

1/4" surface, 1/8" air 1500 Volt Test -.Y-25 ms max.

20 ms max.

-1o*to + 60°C 20 million mechanical operations Clear Polycarbonate 12-pin -

  1. 27390 1'4-pin -
  1. 33377 300VOLTGENERALPURPOSE PLUG-IN RELAYS 219 Series OPTIONS:

Feature Indicator Lamp:

(120 or 240 Vac &

115/125 de only)

Manual Actuator:

Bifurcated Contacts:

Suffix L

M 33 WIRING (circuits viewed from front of socket) -----

12*PIN MODELS liJ rn i'. :

7 10 11 IZ 1

8 9

LO II tZ 219ABAP 219BBXP DP*DT + 2NC 219XBXP DP*DT DP*DT + 1 NO & 1 NC 14*PIN MODELS 6

5 4

3 Z

I tr-LI t1J 7

765*321

~ tJ tJ tJ i r1 r1 r1

~ rn rJ*l
  • 8 9

10 II 12 1:5 14 9

9 10 1 L 12 1:5 14 219XDXP

-*4PDT 7

5 4

5 2

I

~ tJ tr! t,J i r~ r1. ti 8

9 10 II 12 13 14 219DXBP 4P*NO + 2P*NC 219FXXP 6P*NO DIMENSIONS (inches)----------

12*PIN MODELS Locking NO o:

n 0 <,.,

II I n I>
11*..

~,...


~-~


3"1,,,~.:

Models with a Manual Operator (suffix M or LM) Increase overall height by 'I* inch.

14-PIN MODELS COVER-CLEAR POLY CARBONATE OPTIONAL MANUAL

?.,..

I I

UJ.__..J.=====7i '!

1*...__.

I I

2~---1 f-*


3 il 32 11